NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

13

CHIMNEY 30° OFFSET THROUGH 
FLOOR OR CEILING

It may be necessary to assemble the chimney 
at 30° when passing through the fl oor or ceiling 
area. Use the F8FS30 fi restop spacer as shown 
in 

Figures 31 & 32

. Support the chimney at fl oor 

or ceiling penetration with a FTF8 stabilizer if 
distance of chimney below ceiling is 10' or more. 
Maintain 1"* minimum air space to combustibles 
from chimney sections.

Figure 31

Step 4.

 Note:

 Chimney sections are constructed 

with a unique locking tab design, which ensures 
an immediate, tight assembly between sections. 
Plan your chimney requirements carefully before 
assembly as chimney is diffi cult to disassemble 
after installation. If disassembled, the tabs 
might become damaged. Be certain tabs are 
properly formed to ensure locking tabs engage 
properly.

The Security Chimney's FTF8 chimney system 
is a two piece chimney, which snap together 
from the fi replace up. Start with the inner fl ue 
section with the lanced end up, snap lock it in 
to the matching collar on top of the fi replace. 
At all subsequent joints, the upper fl ue section 
fi ts into the preceding fl ue section. Each piece 
snaps together by means of locking tabs (9 
locking tabs per joint). Check each piece by 
pulling up slightly from the top to ensure proper 
engagement before installing the next section. 
If the fl ue has been installed correctly, it will not 
separate when you test it. Also, the inner fl ue 
joint where each section is joined should be 
tight and fl at without gaps (

Figure 34

)

.

The outer chimney section installs the opposite-
way; the lanced end goes down and each new 
section goes OVER the outside of the previous 
section installed (

Figure 35

)

.

For Canada Only

When installing the chimney system through 
an open attic space, the attic shield assembly-
fi restop spacer must be used (

Figure 33

).

 This 

installation is required only for use in Canada.

Note:

 For Canadian installations, all chimney 

installed outside the building must be con-
structed with galvalume (outer sections only).  
The appropriate model designations are located 
in the back of this manual.

F8FS30

Firestop Spacer

FTF8-S4 Stabilizer

1"

*

 Min.

Air Space

30  Firestop

And Attic Above

10'

Max.

Attic Space

1"

*

 Min.

Air Space

F8FS30

Firestop Spacer

FTF8-S4 Stabilizer

30  Firestop
And Room Above

10'

Max.

Room Above

1"

*

 Min.

Air Space

1"

*

 Min.

Air Space

Open Attic Space

Locking

Tabs

(Lances)

Figure 32

Figure 34

Figure 35

Figure 33

Note:

 Assemble one component of chimney at 

a time (inner section fi rst, then outer section 
last) before proceeding with the next complete 
section.

Continue to assemble the chimney up through 
framed opening. Assemble just enough to 
penetrate the roof fl ashing openings (

Figure 

36

).

 Always maintain 1"* minimum air space to 

insulation and construction materials.  Always 
check each chimney joint (inner and outer) 
to ensure proper engagement. Check vertical 
alignment of chimney so that it projects from 
the roof in true vertical position.

1"

*

 Min. Air Space

To Combustibles

Figure 36

Security's chimney sections do not need to be 
screwed together. Additional reinforcement is 
not necessary except in certain offset conditions 
(refer to 

Page 16, Figure 47

)

.

Step 5.

 The height of vertical chimney pipe 

supported only by the fi replace must not exceed 
30'. Chimney heights above 30' must be sup-
ported by a Model FTF8-S4 stabilizer installed 
at 30' intervals.

Note:

 The Model FTF8-S4 adds 3" net effective 

height to the total chimney system.

Install the Model FTF8-S4 stabilizer by fi tting 
inner section down into respective section of 
proceeding fl ue pipe and locking outer stabilizer 
section into place over the outer chimney pipe. 
Position for proper clearance through framed 
opening and nail straps securely (under tension 
in “shear”) into place on framing. Use 8d nails. 
Attach successive lengths of chimney pipe 
directly to stabilizer using same techniques as 
described in 

Step 4

 (

see 

Figure 37)

.

*Notes:

 

• 2" clearance to combustibles required in 
Canada.

• Outdoor installations less than 15’ height 
require chimney clearance of 2” air space to 
insulation and construction materials.

Содержание Merit Plus MP-420D

Страница 1: ...EQUIPPED TO BE READILY IN STALLED OUTDOORS IF INSTALLED INDOORS YOU MUST INSTALL THE COMBUSTION AIR COVER PROVIDED WITH THE INSTALLATION KIT OR PURCHASE THE OPTIONAL OUTSIDE AIR KIT GATE OAKG OD SEE...

Страница 2: ...tate and national codes and regulations 3 ThisfireplacemustbeinstalledwithSecurity Chimneys FTF8 8 203mm inside diam eter Chimney System only This fireplace is intendedforindoororoutdoorinstallations...

Страница 3: ...always maintain minimum clearances to combustible materials and do not violate any specific installation requirements These fireplaces have been tested and listed by OMNI Test Laboratories Inc Report...

Страница 4: ...materials Outdoor installations less than 15 height require chimney clearance of 2 air space to insulation and construction materials In Canada the chimney and fireplace outer wrapper require a minimu...

Страница 5: ...kept within the shaded areas illustrated in Figure 7 CLEARANCES Minimum clearance to combustibles for the appliance is as follows sides and back 1 25 mm floor 0 0mm adjacentwall 12 305 mm ceiling 37 1...

Страница 6: ...t If you plan to raise the fireplace and hearth extension build the platform assembly then position fireplace and hearth extension on top Secure the platform to the floor to prevent possible shifting...

Страница 7: ...the outside air kit is NOT installed you must install the Outside Air Cover provided with the instructions kit b IfanoutsideairkitISinstalled theOutside Air Kit Gate must be installed see Page 23 of o...

Страница 8: ...ons Outside Air Kit Installation provided These appliances are equipped with a com bustion air inlet collar so that it is possible to duct combustion air from the outdoors to the firebox To accomplish...

Страница 9: ...g Materials if any Rough Framing Face Unfinished Shown Combustion Air Kit Optional Framing Dimensions A 46 1 2 1181 mm B1 43 1 2 1105 mm B2 60 1 2 1537 mm C 33 828 mm D 17 1 2 445 mm E 76 1 4 1937 mm...

Страница 10: ...ions must not interfere with circulating grillwork Figure 19 Figure 20 A B Ceiling Framing C D Roof Framing Framing Dimensions for Ceiling Inches millimeters Flue Type A B FTF8 Vertical USA 14 1 2 368...

Страница 11: ...les espaceurs du dessus du foyer voir le sch ma 13 ne peuvent tre retir es ou modifi es vous ne pouvez pas entaillez le colombage pour ajuster autour ou tre install plus bas que les espaceurs Le colom...

Страница 12: ...and outer wrapper require a minimum 2 air space to insulation and construction materials Reference Figures 19 20 and charts Framing DimensionsforCeilingandRoof whichspecify minimum ceiling and roof di...

Страница 13: ...e the building must be con structed with galvalume outer sections only Theappropriatemodeldesignationsarelocated in the back of this manual F8FS30 Firestop Spacer FTF8 S4 Stabilizer 1 Min Air Space 30...

Страница 14: ...as noted in Step 4 Step 6 Select the proper Security Chimneys roof flashing based on pitch of roof Use chart below for selection Figure 37 Note Do not caulk or seal the ventilating open ings or seal t...

Страница 15: ...chimney must be at least 2 above this reference point In all cases thechimneycannotbelessthen3 above the roof at the edge of the chimney The 2 in 10 rule is necessary in the interest of safety but doe...

Страница 16: ...36 48 11 0 11 1 0 0 0 17 1 5 0 1 0 0 21 1 9 2 0 0 0 27 2 3 1 1 0 0 35 2 11 0 0 1 0 47 3 11 0 0 0 1 51 4 3 0 1 1 0 57 4 9 1 0 0 1 63 5 3 0 1 0 1 67 5 7 2 0 0 1 73 6 1 1 1 0 1 81 6 9 0 0 1 1 93 7 9 0 0...

Страница 17: ...the Straight Up In stallation Instructions for cutting and framing ceiling and roof openings Note See Framing and Dimension Chart for the sizes of the ceiling and roof openings The size of the roof op...

Страница 18: ...ilizer Considerthiswhen determining the need for a stabilizer Note Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing Ensure that each su...

Страница 19: ...c tions are placed lower than 18 inches from the fireplace opening These fireplaces have been marked with a maximum rating of 26 000 BTU to assure that homeowners do not exceed the allowable limits fo...

Страница 20: ...ux non combustibles il se pourrait qu il n y ait pas suffisament de d gagement pour installer les portes de verre de votre choix Assurez d avoir un d gagmet suf fisant tout moment afin de ne pasinterf...

Страница 21: ...es 416 x 1 Answer TheminimumrequiredthicknessoftheMicore160is 417 there fore round up to nearest standard thickness available which is 1 2 Using the r formula Note To convert inches to millimeters div...

Страница 22: ...ormal wall decor with elaborate mantels to rustic wood paneling or warm brick facings Only noncombustible materials like stone tile brick etc may overlap the black front facing Do not extend these mat...

Страница 23: ...ith fireplace Shownhereforre placement purposes only Locking Band 63L60 FLB Ref Form 750 080M Spark Arrester 63L57 FSA 2 Ref Form 750 198M INSTALLATION COMPONENTS The following items are available for...

Страница 24: ...n For open top shrouds 96L20 FTF8 CTT Ref Form 750 077M Chimney Pack conventional Convenience Pack Residential 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F8FS 1 F8F6 1 FTF8 CTD 7 P C 8 F T F R O I R E P U S...

Отзывы: