12
13
LNCO50V
LNCO65V
6. INSTALLATION DETAILS
6.1 Torque wrench installation sheet
Outside diameter
Torque
Additional tightening torque
mm
Inch
N.cm
N.cm
∅
6.35
1/4
1500 (153kgf.cm)
1600 (163kgf.cm)
∅
9.52
3/8
2500 (255kgf.cm)
2600 (265kgf.cm)
∅
12.7
1/2
3500 (357kgf.cm)
3600 (367kgf.cm)
∅
16
5/8
4500 (459kgf.cm)
4700 (479kgf.cm)
∅
19
3/4
6500 (663kgf.cm)
6700 (683kgf.cm)
6.2 Connecting the cables
The connecting power cord should be selected according to the following specifi cations:
Rated current of appliance (Amps)
Nominal cross-sectional area (mm²)
>3 and
≤
6
0.75
>6 and
≤
10
1.0
>10 and
≤
16
1.5
>16 and
≤
25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which is located
on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
E963_Lennox Luna Inverter Service Manual 2.indd 12-13
E963_Lennox Luna Inverter Service Manual 2.indd 12-13
21/12/11 10:28 AM
21/12/11 10:28 AM