background image

32

33

8.4.9 Auto-Restart function

The indoor unit is equipped with an auto-restart function, which 
is carried out through an auto-restart module. In the case of a 
sudden power failure, the module memorizes the set conditions 
before the power failure. The unit will resume the previous 
operation settings (not including swing function) automatically 
after 3 minutes when power returns.

If the previous condition was forced cooling mode, the unit will run 
in cooling mode for 30 minutes and turn to auto mode as 24°C 
set temperature.

There is a one (1) minute delay for the compressor to restart if 
power to the unit is switched off accidentally before turning the 
mains off. For other conditions, the compressor will have a three 
(3) minute delay when restarting.

8.4.10 Ionizer function (optional)

The indoor unit is equipped with an Ionizer, which is controlled 
by the CLEAN AIR button on the remote control. When the unit is 
turned on, press the CLEAN AIR button to activate the function. 
Press it again to stop the function. During the time that the Ionizer 
is controlled by remote control, the Ionizer will be turned off 
automatically if the indoor fan stops running due to a malfunction 
or anti-cold-wind. When the indoor fan restarts after a malfunction 
has been rectifi ed and anti-cold-wind has been released, the 
Ionizer option will be available again.

8.4.11 function (optional)

is a device that ionizes the air through positive and 
negative high voltage electrodes operating simultaneously. 

When the positive ions and negative ions are neutralized they 
release tremendous amounts of energy which sterilize the air 
passing through and alter the structure of any resident bacteria.

The residual negative ions not only eliminate odour, dust, smoke 
and pollen particles in the air, but also bring a fresh and healthy 
sensation to the user - just like being in a forest or standing close 
to a waterfall. This function is available only when the unit is on 
using the remote control. After the unit has been turned on, the 
function is switched on when the user presses the ”clean 
air” button on the remote control. Pressing the button again will 
switch off the ionizer function. The function only works 
when the indoor fan motor is running. If the indoor fan motor is 
off, the also stops working even though the  
function is available.

P.S. The function cannot be used at the same time as the 
Ionizer function.

8.4.12  8°C Heating (optional)

When using the heating function, the preset temperature of the 
air conditioner can be as low as 8°C, which keeps the room 
temperature steady at 8°C and prevents household things 
freezing when the house is unoccupied for a long time in severe 
cold weather.

9. TROUBLESHOOTING

9.1 Indoor Unit Error Display

Display

LED STATUS

E0

EEPROM parameter error

E1

Indoor/outdoor units communication protection

E2

Zero-crossing signal error

E3

Indoor fan speed out of control

E5

Open or short circuit of outdoor temperature sensor or outdoor unit 
EEPROM parameter error

E6

Open or short circuit of room or evaporator temperature sensor

E7

Outdoor fan speed out of control

P0

IBM malfunction or IGBT over-strong current protection

P1

Over voltage or too low voltage protection

P2

Temperature protection of compressor top

P4

Inverter compressor drive error

Note:

 E4 & P3: Reserved function.

9.2 Diagnosis and Solutions

9.2.1 EEPROM parameter error

Turn off the power supply and turn 
it back on 5 secs later

Is the EEPROM chip plugged into 
the indoor PCB properly?

Replace the main PCB for the 
indoor unit

Fix the connection

The problem returns

No

Yes

E963_Lennox Luna Inverter Service Manual 4.indd   32-33

E963_Lennox Luna Inverter Service Manual 4.indd   32-33

2/02/12   10:13 AM

2/02/12   10:13 AM

Содержание LNIV2610

Страница 1: ...is applicable only to the following models LNIV2610 LNIV3510 LNIV5010 LNIV6510 SERVICE MANUAL FOR ROOM AIR CONDITIONER Inverter Split Type E963_Lennox Luna Inverter Service Manual 3 indd 40 1 E963_Le...

Страница 2: ...ile the indoor unit need to be repaired 19 6 7 Re installation while the outdoor unit need to be repaired 21 7 OPERATION CHARACTERISTICS 23 8 ELECTRONIC FUNCTIONS 24 8 1 Abbreviations 24 8 2 Display f...

Страница 3: ...risk of damage or loss of property Do not block the air inlet or outlet vents Use a soft cloth to clean Do not use harsh detergents solvents etc Incorrect cleaning methods may increase the risk of fi...

Страница 4: ...LNEO65V 3 2 Outdoor Unit Model W D H W1 A B LNCO26V 760 285 590 823 530 290 LNCO35V LNCO50V 845 320 700 908 560 335 LNCO65V 900 315 860 980 590 333 3 DIMENSIONS L R H More than 30cm More than 60cm Mo...

Страница 5: ...HANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE CHECK VALVE Heating Model only CAPILIARY TUBE REVERSING VALVE Heating Model only COOLING HEATING ACCUMULATOR E963_Lennox Lun...

Страница 6: ...10 11 LNEO50V LNEO65V 5 2 Outdoor Unit LNCO26V LNCO35V E963_Lennox Luna Inverter Service Manual 2 indd 10 11 E963_Lennox Luna Inverter Service Manual 2 indd 10 11 21 12 11 10 28 AM 21 12 11 10 28 AM...

Страница 7: ...ecting power cord should be selected according to the following specifications Rated current of appliance Amps Nominal cross sectional area mm 3 and 6 0 75 6 and 10 1 0 10 and 16 1 5 16 and 25 2 5 The...

Страница 8: ...ide Gas side Vacuum pump Vacuum pump Lo Hi Handle Hi Two way valve Close Manifold valve Compound meter Pressure gauge 20Pa Handle Lo Charge hose Charge hose Outdoor unit Close Three way valve 1 Air pu...

Страница 9: ...the service port cap to a torque of 18Nm Be sure to check for gas leakage 1 Connect the charge hose to the charging cylinder open the 2 way valve and the 3 way valve Connect the charge hose which you...

Страница 10: ...ting the hose 7 Mount the valve stem caps and the service port Use a torque wrench to tighten the service port cap to a torque of 18Nm Be sure to check for gas leakage 1 Confirm that both the 2 way an...

Страница 11: ...the charge set and the charging cylinder and set the 2 way and 3 way valves to the open position Be sure to use a hexagonal wrench to operate the valve stems 7 Mount the valve stems nuts and the serv...

Страница 12: ...the 3 way valve s service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner turn off the air conditioner before disconnecting the hose 6 Moun...

Страница 13: ...3 5 Inverter Module Protection The Inverter module has a protection function related to current voltage and temperature If one of these protection functions occur the corresponding code will display...

Страница 14: ...he indoor fan runs continuously and the speed can be selected as high medium low and auto Auto fan in cooling mode acts as follow 8 4 2 4 Condenser temperature protection 55 T3 60 the compressor frequ...

Страница 15: ...nction is disabled Indoor fan speed can be set as high medium low or auto fan and the anti cold wind function is optional Auto fan action in heating mode 17 15 Low High 44 38 37 34 33 Setting Low Bree...

Страница 16: ...ion mode pressing the touch button will turn off the machine 8 4 6 2 In forced operation mode all general protections and remote control are available 8 4 6 3 Operation rules Forced cooling mode The c...

Страница 17: ...in the air but also bring a fresh and healthy sensation to the user just like being in a forest or standing close to a waterfall This function is available only when the unit is on using the remote co...

Страница 18: ...door PCB Re connect and re test Replace indoor PCB Replace the outdoor e box No No No Yes Yes Yes The unit does not work normally 9 2 3 Fan speed has been out of control 9 2 4 Open or short circuit of...

Страница 19: ...detect an over zero signal When such a failure occurs the main control board must be faulty Does the compressor work Is the refrigerant circulation volume normal Is the protector OK Replace the outdoo...

Страница 20: ...38 39 E963_Lennox Luna Inverter Service Manual 1c indd 38 39 E963_Lennox Luna Inverter Service Manual 1c indd 38 39 13 12 11 4 43 PM 13 12 11 4 43 PM...

Отзывы: