Electrical Control Function
Electrical Control System
116
If the value is higher than 99, the digital display shows single
and double digits.
For example, if the digital display shows “2.0", the EXV open
angle is 120×4=480p.
15
Frequency limit symbol
Bit7
Frequency limit
caused by IGBT
radiator
The display value is a
hexadecimal number. For
example,
the
digital
display show 2A, then
Bit5=1,
Bit3=1,
and
Bit1=1.
It means frequency limit
may be caused by T4, T3
or the current.
Bit6
Frequency limit
caused by PFC
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by T5.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
16
DC fan motor speed
0
:
Off, 1: Turbo, 2: High, 3: Medium, 4: Low, 5:
Breeze, 6: Supper breeze
17
IGBT radiator temperature
The display value is between 0–30
℃
. If the temperature is
higher than 99
℃
, the digital display shows single and double
digits.
For example, if the digital display shows “0.5", the IGBT
radiator temperature is 105
℃
.
If the digital display shows “1.6", the IGBT radiator
temperature is 116
℃
.
18
Indoor unit number
The indoor unit can communicate with outdoor unit.
General: 1, Twins: 2
19
Condenser pipe temperature of #1 indoor
unit
If the temperature is lower than 0
℃
, the digital display shows
“0”. If the temperature is higher than 70
℃
, the digital display
shows “70.”
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows:
“――”(heating T2
,
cooling T2B)
20
Condenser pipe temperature of #2 indoor
unit
21
Reserved
22
#1 Indoor unit capacity demand code
Actual data*HP*10
If a capacity demand code is higher than 99, the digital display
shows single and double digits.
For example, if the digital display reads “5.0”, the capacity
demand is 15.
If the digital display shows “60”, the capacity demand is 6.0.
If the indoor unit is not connected, the digital display shows:
“――”
23
#2 Indoor unit capacity demand code
24
Reserved
25
Indoor room temperature of #1 indoor unit
If the temperature is lower than -9
℃
, the digital display shows
“9”.
If the temperature is higher than 70
℃
, the digital display
shows “70”.
If the capacity demand is 0, the digital display shows “0”.
If the indoor unit is not connected, the digital display shows:
“――”
26
Indoor room temperature of #2 indoor unit
If the temperature is lower than 0
℃
, the digital display shows
“0”.
If the temperature is higher than 70
℃
, the digital display
shows “70”.
If the capacity demand is 0, the digital display shows “0".
Содержание LICH4012021T431E-1
Страница 12: ...Service Space Indoor Units 10 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Страница 13: ...Wiring Diagrams Indoor Units 11 4 Wiring Diagrams...
Страница 15: ...Air Velocity Distributions Reference Data Indoor Units 13 36K Cooling Heating...
Страница 16: ...Air Velocity Distributions Reference Data Indoor Units 14 48 60K Cooling Heating...
Страница 21: ...Field Wiring Indoor Units 19 10 Field Wiring...
Страница 27: ...Service Space Indoor Units 25 3 Service Space Ensure enough space required for installation and maintenance...
Страница 28: ...Wiring Diagrams Indoor Units 26 4 Wiring Diagrams 12k 18k 60k...
Страница 39: ...Field Wiring Indoor Units 37 10 Field Wiring 12K 18K 60K...
Страница 43: ...Ceiling Floor Type Indoor Units 41 3 Service Space...
Страница 48: ...Ceiling Floor Type Indoor Units 46 Floor installation Discharge angle 17 Discharge angle 50...
Страница 49: ...Ceiling Floor Type Indoor Units 47 Model 36k Ceiling installation Discharge angle 17 Discharge angle 50...
Страница 50: ...Ceiling Floor Type Indoor Units 48 Floor installation Discharge angle 17 Discharge angle 50...
Страница 51: ...Ceiling Floor Type Indoor Units 49 Model 48k 60k Ceiling installation Discharge angle 17 Discharge angle 50...
Страница 52: ...Ceiling Floor Type Indoor Units 50 Floor installation Discharge angle 17 Discharge angle 50...
Страница 54: ...Field Wiring Indoor Units 52 10 Field Wiring...
Страница 57: ...Features Indoor Units 55...
Страница 59: ...Service Space Indoor Units 57 3 Service Space...
Страница 60: ...Wiring Diagrams Indoor Units 58 4 Wiring Diagrams LICH4012021T431E 1 LICH4018021T431E...
Страница 64: ...Field Wiring Indoor Units 62 10 Field Wiring LICH4012021T431E 1 LICH4018021T431E...
Страница 67: ...Dimensions Outdoor Units 65 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Страница 69: ...Wiring Diagrams Outdoor Units 67 3 Wiring Diagrams LIHP012000T431E...
Страница 70: ...Wiring Diagrams Outdoor Units 68 LIHP018000T431E LIHP024000T431E...
Страница 71: ...Wiring Diagrams Outdoor Units 69 LIHP036000T431E...
Страница 72: ...Wiring Diagrams Outdoor Units 70 LIHP036000M431E...
Страница 73: ...Wiring Diagrams Outdoor Units 71 LIHP048000T431E LIHP048000M431E LIHP060000M431E...
Страница 98: ...Refrigerant pipe installation Installation 96...