INNOV@ CENT -AGU-0912-E
.
8
.
1.4 Hydraulic section (CW version)
3-way valve
The 3-way valve used on INNOV@DM CW version units for inlet water flow regulation allowing a foundamentally
maximum precision’s regulation on CCAC applications.
Tab. 3 Technical characteristics
Frame 1
Frame 2
Frame 3
Brand / valve’s type
Controls VMT2
Controls VMT2
Controls VMBT3
Kvs valve
(m
3
/h)
4
4
6.3
PN valve
16
16
16
D
P max.
(kPa)
250
250
170
Connections
(inch)
1/2”
1/2”
3/4”
All INNOV@DM CW units are supplied with 3-way valve setted by 3 points motor. Upon request, is possible to
set an advanced precision control with 0 ÷ 10 V signal regulation.
Air presence on hydraulic circuit
It is necessary to leak air from the hydraulic circuit of unit after the connection to the external circuit. To do this,
open the frontal panels and remove the air filter; after this, open the small valve on the right-top side of the coil’s
collector (take the front side of unit in reference). Use adapted tools for the manual valve’s setting.
Fig. 5
Basic cooling circuit (CW version)
Pos.
Description
Pos.
Description
1
Chilled water inlet
5
Coil heat exchanger
2
Chilled water outlet
6
Breather valve
3
3-way valve
7
2-way valve (Opt.)
4
Plug fan
-
Standard
Opt. 2-way valve
M
5
6
2
3
1
7
2
1
6
5
4
M
4
Содержание INNOV DM R Series
Страница 2: ......
Страница 32: ......
Страница 49: ...INNOV ECFAN DHR AGU 0912 E 17 6 Operating Diagrams DISPLACEMENT DOWNFLOW UPFLOW...
Страница 75: ...lennoxemeia com INNOV DM_C APPLICATION GUIDE Centrifugal close control unit 6 22 kW INNOVA CENT AGU 0912 E...
Страница 76: ......