INNOV@ ECFAN DMR -AGU-0912-E
•
21
•
10.3 Checking the refrigerant level (DX version)
D
After a few hours of operation, check whether the liquid level indicator has a green ring: a yellow colour indicates the
presence of humidity in the circuit. In such a case the circuit must be dehumidified by qualified personnel.
D
Large quantities of bubbles should not appear through the liquid level indicator. A constant passage of numerous
bubbles may indicate that the refrigerant level is low and needs to be topped up. The presence of a few bubbles is
however allowed, especially in the case of high-glide ternary mixtures such as HFC R407C.
D
Make sure the overheating of the cooling fluid is limited to between 5 and 8 °C: to this end:
1 ) read the temperature indicated by a contact thermometer placed on the compressor intake pipe;
2 ) read the temperature indicated on the scale of a pressure gauge likewise connected to the intake side; refer to
the pressure gauge scale for the refrigerant R407C, marked with the initials D.P. (Dew Point).
D
Make sure that the Sub-cooling of the cooling fluid is limited to between 3 and 5°C: to this end:
1 ) read the temperature indicated by a contact thermometer placed on the condenser outlet pipe;
2 ) read the temperature indicated on the scale of a pressure gauge connected to the liquid inlet at the condenser
outlet; refer to the pressure gauge scale for the refrigerant R407C, marked with the initials B.P. (Bubble Point).
The degree of Sub-cooling is given by the difference between the temperatures thus determined.
Warning:
All INNOV@DM-R DX units are charged with dry nitrogen and you must empty them
before charging with refrigerant. This operation must be performed by qualified
personnel only.
Warning:
Any top-ups must be made using R407C only. This operation is to be considered
extraordinary maintenance work and must be performed by qualified personnel only.
Warning:
The refrigerant R407C requires “POE“ polyolester oil of the type and viscosity indicated
on the compressor rating plate.
For no reason should oil of a different type be introduced into the oil circuit.
The difference between the “Dew Point” and “Bubble Point” is known as “GLIDE” and this is a characteristic property of
refrigerant mixtures. If pure fluids are used, the phase change occurs at a constant T and thus the glide is equal to zero.
Average T
(T1+T2)/2
T1 (start of
condensation)
DEW POINT
T2 (end of condensation)
BUBBLE POINT
Enthalpy h
P
Real P
Compressor
Outlet
R407C
Содержание INNOV DM R Series
Страница 2: ......
Страница 32: ......
Страница 49: ...INNOV ECFAN DHR AGU 0912 E 17 6 Operating Diagrams DISPLACEMENT DOWNFLOW UPFLOW...
Страница 75: ...lennoxemeia com INNOV DM_C APPLICATION GUIDE Centrifugal close control unit 6 22 kW INNOVA CENT AGU 0912 E...
Страница 76: ......