Table 4. Building Automation and General Alarm Faults
Alarm
Mgr
Alarm
ID
Category
Alert
Level
(Severe,
Low,
Info)
Local Display: Alert Title
Local Display: Alert
Detailed Description
Comments
5119
Building
Automation
Installer
Defined
IOB Light Sensor, Alarm Condition 12
Description sent by LCC
IOB Light Sensor, Alarm Condition 12
5800
Building
Automation
Low
Analog Input 1 near zero
Description sent by Central
Hub
Shorted thermistor
5801
Building
Automation
Low
Analog Input 1 near maximum
Description sent by Central
Hub
Open thermistor
5802
Building
Automation
Low
Analog Input 2 near zero
Description sent by Central
Hub
Shorted thermistor
5803
Building
Automation
Low
Analog Input 2 near maximum
Description sent by Central
Hub
Open thermistor
5804
Building
Automation
Low
Analog Input 3 near zero
Description sent by Central
Hub
Shorted thermistor
5805
Building
Automation
Low
Analog Input 3 near maximum
Description sent by Central
Hub
Open Thermistor
5806
Building
Automation
Low
Analog Input 4 near zero
Description sent by Central
Hub
Shorted thermistor
5807
Building
Automation
Low
Analog Input 4 near maximum
Description sent by Central
Hub
Open Thermistor
5808
Building
Automation
Low
Analog Input 5 open pressure transducer
Description sent by Central
Hub
Analog Input 5 open pressure transducer
5809
Building
Automation
Low
Analog Input 5 shorted pressure
transducer
Description sent by Central
Hub
Analog Input 5 shorted pressure transducer
6000
General Fault
Severe
RTU not responding
RTU not responding (off-
line).
“Alarm 6000 is asserted if communication failed for 20 consecutive
attempts. 6000 will be cleared if communication is without error for 5
consecutive attempts.”
6001
General Fault
Severe
M-Bus Unit not responding
Unit not responding (off-
line).
6002
General Fault
Low
EM unit not responding
Energy Monitoring unit not
responding (off-line).
6003
General Fault
Low
Local display not responding
Local display not responding
(off-line).
6004
Reserved
6005
General Fault
Low
S-Bus communications degraded.
S-Bus communications
degraded.
Alarm 6005 is asserted immediately on any communication failure. 6005
will be cleared if communication is without error for one hour
6006
General Fault
Low
M-Bus communications degraded.
M-Bus communications
degraded.
6007
General Fault
Low
EM communications degraded.
Energy Monitoring
communications
degraded.
6008
General Fault
Low
Local display communications degraded.
Local display
communications
degraded.
Modbus specific alarm
6009
General Fault
Info
More than 4 IOBs are connected
More than four IOBs are
connected
Modbus specific alarm
6010
General Fault
Info
More than 30 devices are connected
More than 30 devices are
connected
6011
General Fault
Low
EM Model Mismatch
Configured meter model
does not match meter
reported model.