36
Table 3. Alarm Faults
Alarm
Mgr
Alarm
ID
Category
Alert
Level
(Severe,
Low,
Info)
Local
Display:
Alert Title
Local Display: Alert
Detailed Description
M3-Specific
Description
IMC Error Description
IMC Action
102
Configuration
Info
GP Control
Setup Error
GP configuration error. Check
for proper installation of GP
board and settings.
GP Control Setup
Error
GP configuration error. Cases that can
cause this alarm:
• 1- ECTO 9.01 option 1-11, ECTO 9.12
option 1-11 or ECTO 9.23 option 1-15
selected, but no GP1(A133) (w/DIP
set to GP) present.
• GP1(A133) (w/DIP set to GP) present,
but no ECTO 9.01 option 1-11 nor
ECTO 9.12 option 1-11, nor ECTO
9.23 option 1-15 has been selected.
• ECTO 7.25 option 4-7 selected, but
no GP1 (A133) (W/DIP set to GP) is
present.
• ECTO 5.26 option 2-3 selected, but
no GP1 (A133) (W/DIP set to GP) is
present.
• ECTO 5.26 option 2-3 selected, but
ECTO 9.01 is not set to 5.
Affected features do not
operate.
103
Configuration
Low
Adv Ctrl Setup
Error
General configuration error.
Adv Ctrl Setup
Error
General configuration error. ECTO
option is set to use an input that is not
present. Cases that can cause this
alarm:
• ECTO 7.25 option 1 is selected.
• ECTO 7.25 option 2 or 3 selected,
but no A56 board present.
• ECTO 7.04 option is set to less than
71F (Reheat FAT enabled) but no
A56 board present.
• ECTO 5.04 option 4 (DACC) or
ECTO 5.09 option 1 (DACH)
selected on heat pumps. DACC and
DACH not allowed on heat pumps.
• ECTO 4.24 option is set to 1-3 or
5-7 (reheat modes) and ECTO 5.04
option 4 (DACC) is selected. DACC
is not allowed with reheat.
• ECTO 7.04 option is set to less
than 71F (Reheat FAT enabled) and
ECTO 4.24 is set to option 0 or 1.
Reheat FAT not allowed with ECTO
options 0 or 1.
• ECTO 7.22 Input source (X) is
greater than 9.
Affected features do not
operate.