Page 35
XP17
Table 8. Outdoor Control Seven-Segment Unit Status Displays (
continued
)
Description
Example of Display
Idle Mode
: Decimal point blinks at 1 Hz
Idle Mode: Decimal point blinks at 1 Hz (0.5 second on, 0.5 second off).
Display OFF.
Soft Disabled
: Top and bottom horizontal line and decimal point
blink at 1 Hz.
Soft Disabled: Top and bottom horizontal line and decimal point blink at 1
Hz (0.5 second on, 0.5 second off). Note: Control should be replace.
O.E.M test mode
All segments flashing at 2 Hz (unless error is detected) Note: Control
should be replace.
Anti-Short Cycle Delay
Middle line shall blink at 1 Hz for 2 seconds, followed by a 2 second display
of the rounded up number of minutes left in the timer (2 minutes 1 second
shall be displayed as “3”). The Anti-Short Cycle Delay time remaining is
displayed whenever the delay is active.
Cooling Stage
: Shows what stage of cooling is currently operat
ing.
Following string is repeated if second stage cooling is active with outdoor
fan speed set at 700 RPM. Note:
A
- If available, displays outdoor ambient
temperature.
pause
pause
Heat Pump Stage
: Shows what stage of heat pump is currently
operating.
Following string is repeated if first stage heat pump is active with outdoor
fan speed set at 600 RPM. Note:
A
- If available, displays outdoor ambient
temperature.
pause
pause
Defrost Mode
: Shown only while in an active defrost.
Following string is repeated if defrost is active while unit was in 1
st
stage
heat pump heating mode:
pause
pause
Dehumidification mode:
Shows that the unit is providing dehu
midification instead of straight cooling.
Following string is repeated if dehumidification is active with outdoor fan
speed set at 225 RPM:
pause
pause
Diagnostic recall:
Shows the last 10 stored diagnostic error
codes.
If first error is
, second
:
pause
pause
pause
Next codes (up to 10) are show using same method.
If there is no error codes stored:
E
pause
0 0 0
Fault Memory clear
After the fault memory is cleared following string is displayed with 0.5 sec
onds character on/off time:
pause
Active error in outdoor control Idle mode
: Shown all active
error(s) codes.
Following string is repeated if Error E125 and E201 are present:
pause
Active error in run mode
: Shown current status and all active
error(s) codes.
Following string is repeated if Error E311 is present while blower speed at
700RPM:
pause
Outdoor Ambient Temperature (OAT)
: Any time OAT is sensed
in operating range value is displayed if unit is in diagnostic and
non-diagnostic modes.
Following string is repeated if second stage cooling is active with outdoor
fan speed set at 650 RPM and OAT is 104
o
F:
pause
pause
pause
Outdoor Coil Temperature (OCT)
: Any time OCT is sensed in
operating range value is displayed if unit is in diagnostic mode.
Following string is repeated if 2nd stage heat is active with outdoor fan
speed set at 550 RPM and OCT is 25
o
F:
pause
pause
pause
Discharge Line Temperature (DIS
): Any time DIS is sensed in
operating range value is displayed if unit is in diagnostic mode.
Following string is repeated if 2nd stage cooling is active with outdoor fan
speed set at 650 RPM and DIS is 185
o
F:
pause
pause
pause
Содержание iComfort SL18XC1 Series
Страница 44: ...Page 44 XP17 Figure 21 Typical XP17 Wiring XP17 XX 230 06...
Страница 45: ...Page 45 XP17 Factory Wiring Diagrams Figure 22 Typical Factory Wiring XP17 XX 230 01...
Страница 46: ...Page 46 XP17 Figure 23 Typical Factory Wiring XP17 XX 230 02...
Страница 47: ...Page 47 XP17 Figure 24 Typical Factory Wiring XP17 XX 230 03 and 05...
Страница 48: ...Page 48 XP17 Figure 25 Typical Factory Wiring XP17 XX 230 06...