Page 32
XP17
Table 12. Seven-Segment Display Alert Codes
NOTE — System fault and lockout seven-segment display alarm codes takes precedence over system status codes
(cooling, heating stages or defrost/dehumidification). Only the latest active fault or lockout alarm code if present will be
displayed. If no fault or lockout codes are active, then system status are routinely displayed.
Alert
Codes
Alarm Description
Possible Causes and Clearing Alarm
E 105
The outdoor unit
has lost
communication with the rest of the
system.
Equipment is unable to communicate. This may indicate the existence of other alarms / codes. In
most cases errors are related to electrical noise. Make sure high voltage power is separated from
RSBus. Check for mis-wired and/or loose connections between the stat, indoor unit and outdoor
unit. Check for a high voltage source of noise close to the system. This is a self-recoverable error.
E 120
There is a delay in the outdoor unit
responding to the system.
Typically, this alarm/code does not cause any issues and will clear on its own. The alarm / code is
usually caused by a delay in the outdoor unit responding to the thermostat. Check all wiring
connections. Cleared after unresponsive device responds to any inquiry
E 124
The iComfort
-enabled thermostat
has lost communication with the out
door unit
for more than 3 minutes.
Equipment lost communication with the thermostat. Check the wiring connections, ohm wires and
cycle power. The alarm stops all associated HVAC operations and waits for a heartbeat message
from the unit that's not communicating. The alarm / fault clears after communication is re-estab
lished.
E 125
There is a hardware problem with the
outdoor unit control.
There is a control hardware problem. Replace the outdoor control if the problem prevents operation
and is persistent. The alarm / fault is cleared 300 seconds after the fault recovers
E 126
There is an internal communication
problem with the outdoor unit control.
There is an internal hardware problem on the control. Typically the control will re-set itself. Replace
the control if the problem prevents operation and is persistent. The alarm / fault is cleared 300 sec
onds after the fault recovers.
E 131
The outdoor unit control parameters are
corrupted
Reconfigure the system. Replace the control if heating or cooling is not available
E 180
The iComfort
-enabled thermostat has
found a problem with the outdoor unit's
ambient sensor.
In normal operation after outdoor control recognizes sensors, the alarm will be sent if valid
temperature reading is lost. Compare outdoor sensor resistance to temperature/resistance charts
in unit installation instructions. Replace sensor pack if necessary. At the beginning of (any)
configuration, furnace or air-handler control will detect the presence of the sensor(s). If detected
(reading in range), appropriate feature will be set as 'installed' and shown in the iComfort
-enabled
thermostat 'About' screen. The alarm / fault will clear upon configuration, or sensing normal values.
E 401
Either the compressor ran for more than
18 hours continuously.
Compressor ran more than 18 hours to satisfy a single thermostat demand. If the unit is 2-stage, the
high-speed will lock-out and the unit will run at low-speed. If it is a HP and ODT <65ºF, the system will
not raise an alarm. Confirm that the system is properly charged with refrigerant. Check for stuck
reversing valve, excessive cooling load and properly sized equipment. Confirm that the evaporator
coil is clean. The alarm clears after 30 consecutive normal run cycles or a power reset.
E 403
The compressor ran for less than 3
minutes to satisfy a thermostat demand
(short-cycling)
Compressor runs less than 3 minutes to satisfy a thermostat demand (short-cycling). Confirm that
the system is properly charged with refrigerant. Check the condensation float switch and TXV. The
alarm clears after 4 consecutive normal compressor run cycles or a power reset.
E 409
The secondary voltage for the outdoor
unit has fallen below 18VAC. If this
continues for 10 minutes, the system
will shut down.
Secondary voltage is below 18VAC. After 10 minutes, operation is discontinued. Check the indoor
line voltage, transformer output voltage. The alarm clears after the voltage is higher than 20VAC for
2 seconds or after a power reset.
E 410
The outdoor unit pressure is below the
required limit.
Unit pressure is below the lower limit. The system is shutdown. The low pressure switch for
HFC-410A will open at 40PSIG and close at 90PSIG. Confirm that the system is properly charged
with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Con
firm that the evaporator coil is clean. The alarm clears after the pressure switch closes or after a
power reset
E 411
The low pressure switch has opened 5
times during one cooling cycle. As a
result, the system will shutdown.
Open low pressure switch error count reached 5 strikes. The low pressure switch for R410A will
open at 40PSIG and close at 90PSIG. Confirm that the system is properly charged with refrigerant.
Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the
evaporator coil is clean. The alarm clears after a power reset
E 412
The outdoor unit pressure is above the
required limit. The system will shut
down.
Unit pressure is above the upper limit. System is shut down. The high pressure switch for HFC-410A
will open at 590PSIG and close at 418PSIG. Confirm that the system is properly charged with
refrigerant. Check condenser fan motor, TXV, indoor unit blower motor, stuck reversing valve or
clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm clears after 4 consecutive
normal compressor run cycles, the pressure switch closes or a power reset
E 413
The high pressure switch has opened 5
times during one cooling cycle. As a
result, the iComfort
-enabled
thermostat will shutdown.
Open high pressure switch error count reached 5 strikes. System is shut down. The high pressure
switch for HFC-410A will open at 590PSIG and close at 418PSIG. Confirm that the system is prop
erly charged with refrigerant. Check condenser fan motor, TXV, indoor unit blower motor, stuck re
versing valve or clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm clears
after a power reset.
Содержание iComfort SL18XC1 Series
Страница 44: ...Page 44 XP17 Figure 21 Typical XP17 Wiring XP17 XX 230 06...
Страница 45: ...Page 45 XP17 Factory Wiring Diagrams Figure 22 Typical Factory Wiring XP17 XX 230 01...
Страница 46: ...Page 46 XP17 Figure 23 Typical Factory Wiring XP17 XX 230 02...
Страница 47: ...Page 47 XP17 Figure 24 Typical Factory Wiring XP17 XX 230 03 and 05...
Страница 48: ...Page 48 XP17 Figure 25 Typical Factory Wiring XP17 XX 230 06...