Page 14
XP17
System Status, Fault and Lockout LED
Codes
LED codes are displayed using various LEDs located on
the heat pump control (A175). See figure 3 for locations of
heat pump control LEDs.
DS11 AND DS14 — SYSTEM STATUS, FAULT AND
LOCKOUT LED CODES
DS11 (Green) and DS14 (Red) LEDs indicate
non-communicating mode diagnostics conditions that are
listed in table 5.
These LEDs display fault conditions in unit cooling and
heating capacity, dehumidification mode, anti-short cycle
lockout, high and low pressures, discharge line
temperature, outdoor temperature, and discharge sensor
failures.
DS15 AND DS13 — COMPRESSOR FAULT AND
LOCKOUT LED CODES
DS15 (Yellow) and DS13 (Red) LEDs indicate diagnostics
conditions that are listed in table 6.
These LEDs display the most common compressor or
compressor related fault conditions in the unit. When an
abnormal condition is detected, this function
communicates the specific condition through LEDs. The
diagnostic function is capable of detecting both mechanical
and electrical system abnormal conditions.
IMPORTANT
DS15 and DS13 compressor LED fault and lockout
codes do not provide safety protection. The is a
monitoring function only and cannot control or shut down
other devices
.
RESETTING FAULT AND LOCKOUT LED CODES
All LED fault and lockout codes can be reset manually or
automatically:
1.
Manual Reset
Manual reset can be achieve by one of the following
methods:
Disconnecting
R
wire from the heat pump's
R
terminal.
Turning the indoor unit off an on again
After power up, existing code will display for 60
seconds and then clear.
2.
Automatic Reset
After a fault or lockout is detected, the heat pump
control continues to monitor the unit's system and
compressor operations. When/if conditions return to
normal, the alert code is turned off automatically.
Table 5. System Status, Fault and Lockout LED Codes and Related iComfort
t
-Enabled Thermostat Alert Codes
System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then
system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Heat Pump Control
LEDs
iComfort
t
-enabled
Thermostat
Display
Condition
Possible Cause(s)
Solution
DS11
Green
DS14 Red
SYSTEM STATUS
Off
Off
Not
applicable
Power problem
1. No power (24V) to
heat pump control
terminal's R and C or
heat pump control
failure.
2. Heat pump control
failure.
1
Check control transformer power (24V).
2
If power is available to control and LED(s) do not
light, replace the heat pump control.
Simultaneous slow flash
Not
applicable
Normal operation
Unit operating normally or in standby mode.
Alternating slow flash
Not
applicable
5-minute
anti-short cycle
delay
Initial power up, safety trip,
end of room thermostat de
mand.
None required (Jumper FIELD TEST (E33) pins to
override)
Simultaneous fast
flashes
Moderate /
Critical Alert
Code 180
Ambient sensor
problem
If sensor detects an open, shorted or out-of-temperature range. heat pump control
will revert to time/temperature defrost operation. System will still heat or cool.
Alternating fast flash
Moderate /
Critical Alert
Code 417
Coil sensor
problem
If the outdoor coil temperature sensor is detected as being open or shorted, the
heat pump control will not perform defrost operations.
On
On
Not
applicable
Heat pump
control failure
Indicates that heat pump control has an internal component failure. Cycle 24 volt
power to heat pump control. If code does not clear, replace the heat pump control.
Содержание iComfort SL18XC1 Series
Страница 44: ...Page 44 XP17 Figure 21 Typical XP17 Wiring XP17 XX 230 06...
Страница 45: ...Page 45 XP17 Factory Wiring Diagrams Figure 22 Typical Factory Wiring XP17 XX 230 01...
Страница 46: ...Page 46 XP17 Figure 23 Typical Factory Wiring XP17 XX 230 02...
Страница 47: ...Page 47 XP17 Figure 24 Typical Factory Wiring XP17 XX 230 03 and 05...
Страница 48: ...Page 48 XP17 Figure 25 Typical Factory Wiring XP17 XX 230 06...