Page 7
1-
Placement −
Be aware some localities are adopting
sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmis-
sion.
2-
Line Set Isolation −
The following illustrations demon-
strate procedures which ensure proper refrigerant line
set isolation. Figure 8 shows how to install line sets on
vertical runs. Figure 9 shows how to install line sets on
horizontal runs. Figure 10 shows how to make a transi-
tion from horizontal to vertical. Finally, figure 11 shows
how to place the outdoor unit and line set.
Refrigerant Line Sets
How To Install Vertical Runs
(new construction shown)
PVC Pipe
Fiberglass
Insulation
Caulk
Outside Wall
Vapor Line
(wrapped with Armaflex)
Liquid Line
IMPORTANT - Refrigerant
lines must not contact
structure.
Outside Wall
Inside Wall
Liquid Line
Vapor Line
IMPORTANT - Refrigerant
lines must not contact wall.
Wood Block
Between Studs
Strap
Sleeve
Wood Block
Strap
Sleeve
Wire Tie
Wire Tie
Wire Tie
NOTE - Similar installation practices should be used if
line set is to be installed on exterior of outside wall.
Figure 8