background image

Page 15

Charging

This system is charged with R410A refrigerant which oper-
ates at much higher pressures than R22. The check/ex-
pansion valve provided with the unit is approved for use
with R410A. Do not replace it with a valve designed for use
with R22. This unit is NOT approved for use with coils which
include metering orifices or capillary tubes.

Processing Procedure

The unit is factory−charged with the amount of R410A re-
frigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with a 15
foot (4.6 m) line set. For varying lengths of line set, refer to
table 2 for refrigerant charge adjustment.

Table 2

Liquid Line Set

Diameter

Oz. per 5 ft. (grams per 1.5 m) adjust 

from 15 ft. (4.6 m) line set*

3/8 in.

(10 mm)

3 ounces per 5 feet

(85g per 1.5 m)

*If line length is greater than 15 ft. (4.6 m), add this amount.
If line length is less than 15 ft. (4.6 m), subtract this amount.

IMPORTANT

Mineral oils are not compatible with R410A. If oil
must be added, it must be a polyol ester oil.

The compressor is charged with sufficient polyol ester
oil for line set lengths up to 50 feet (15.2 m).  Do not add
any more than 7 oz. of oil.If oil must be added to the
compressor in the field, Copeland has approved Mobil
EAL

t

 Arctic 22CC and ICI EMKARATE

t

 RL32CF.

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is deter-

mined by the unit’s refrigerant metering device and the out-
door ambient temperature

.

Measure the liquid line temperature and the outdoor ambi-
ent temperature as outlined below:

 1 − Close manifold gauge set valves. Connect manifold

gauge set to service valves as shown in figure 16:
 

 

low pressure gauge to 

vapor 

valve service port

 

 

high pressure gauge to 

liquid 

valve service port

Connect the center manifold hose to an upright cylin-
der of R410A .

 2 − Set the room thermostat to call for heat. This will create

the necessary load for properly charging the system in
the cooling cycle.

 3 − Use a digital thermometer to record the outdoor ambi-

ent temperature.

 4 − When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68

F

(20

C). When pressures have stabilized, use a digital

thermometer to record the liquid line temperature.

 5 − The outdoor temperature will determine which charg-

ing method to use. Proceed with the appropriate charg-
ing procedure.

Weighing in the Charge TXV Systems – 

Outdoor Temp < 65

F (18

C)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, the refrigerant charge should be
weighed into the unit. Do this after any leaks have been re-
paired.

 1 − Recover the refrigerant from the unit.

 2 − Conduct a leak check, then evacuate as previously

outlined.

 3 − Weigh in the unit nameplate charge.

If weighing facilities are not available or if you are charging
the unit during warm weather, follow one of the other proce-
dures outlined below.

Subcooling Method

Outdoor Temp. < 65°F (18°C)

When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the out-
door coil to achieve pressures in the 325−375 psig
(2240−2585 kPa) range. These higher pressures are nec-
essary for checking the charge. Block equal sections of air
intake panels and move obstructions sideways until the liq-
uid pressure is in the 325−375 psig (2240−2585 kPa) range.
See figure 15.

Blocking Outdoor Coil

cardboard or
plastic sheet

Outdoor coil should be

blocked one side

at a time with cardboard

or plastic sheet until proper

testing pressures

are reached.

Figure 15

 1 − With the manifold gauge hose still on the liquid service

port and the unit operating stably, use a digital ther-
mometer to record the liquid line temperature.

 2 − At the same time, record the liquid line pressure reading.
 3 − Use a temperature/pressure chart for R410A to deter-

mine the saturation temperature for the liquid line pres-
sure reading. See table 6.

 4 − Subtract the liquid line temperature from the saturation

temperature (according to the chart) to determine sub-
cooling. 

(Saturation temperature − Liquid line tem-

perature = Subcooling)

 5 − Compare the subcooling value with those in table 3. If

subcooling is greater than shown, recover some refrig-
erant. If subcooling is less than shown, add some re-
frigerant. Be aware of the R410A refrigerant cylinder. It

Содержание HPXA15 SERIES

Страница 1: ...a qualified installer or service agency INSTALLATION INSTRUCTIONS HPXA15 SERIES UNITS HEAT PUMP UNITS 504 713M 02 04 Supersedes 12 02 Table of Contents HPXA15 Outdoor Unit 1 Shipping Packing List 1 G...

Страница 2: ...in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 16 3 4 2 7 8 5 1 2 HPXA15 024 mm 708 657 759 311 570 367 562 425 730 140 HPXA15 030 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8 17 1 4 3...

Страница 3: ...s 1 Place a sound absorbing material such as Isomode under the unit if it will be installed in a location or posi tion that will transmit sound or vibration to the living area or adjacent buildings 2...

Страница 4: ...y support the unit Consult local codes for rooftop applications If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be constructed See figure 3 Size barrier at least...

Страница 5: ...eld wiring diagram NOTE A complete unit wiring diagram is located in side the unit control box cover 3 Install room thermostat ordered separately on an in side wall approximately in the center of the...

Страница 6: ...Corp 9351 L9 for proper size type and application of field fabricated lines Valve sizes are also listed in table 1 Refrigerant Connections HPXA15 Matched with New Indoor Coil and Line Set If an existi...

Страница 7: ...ure 9 shows how to install line sets on horizontal runs Figure 10 shows how to make a transi tion from horizontal to vertical Finally figure 11 shows how to place the outdoor unit and line set Refrige...

Страница 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Страница 9: ...e Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 10 Outsid...

Страница 10: ...Engineering Handbook for approved TXV match ups and application information Check expansion valves equipped with Chatleff fittings are available from Lennox Refer to the Engineering Handbook for appli...

Страница 11: ...ine valve Disconnect all power to the existing outdoor unit Re fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system Disconn...

Страница 12: ...se at up to 800 psi of pressure with a 4000 psi burst rating Service Valves Access the liquid line and vapor line service valves figures 13 and 14 and gauge ports are used for leak testing eva cuating...

Страница 13: ...al injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system use a regu...

Страница 14: ...set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid...

Страница 15: ...e 4 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line te...

Страница 16: ...lations Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the syste...

Страница 17: ...door Coil E t i Ai HPXA15 024 HPXA15 030 HPXA15 036 HPXA15 042 HPXA15 048 HPXA15 060 Entering Air Temp F C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 65 18 3 252 131...

Страница 18: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Страница 19: ...t control defrost relay time delay diagnostic LEDs and a terminal strip for field wiring connections See figure 17 The control provides automatic switching from normal heating operation to defrost mod...

Страница 20: ...The service light thermostat provides a signal which activates the room ther mostat service light during periods of inefficient operation Diagnostic LEDs The defrost board uses two LEDs for diagnosti...

Страница 21: ...re lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Отзывы: