• 59 •
1
2
3
Installation manual /
eCOMFORT-MIL150E-0916 / 05/2017
Step 1
Remove the damaged sleeve by operating a longitudinal sec-
tion as in the photo below :
Step 2
Clean the connection with a wire brush and a synthetic
abrasive as one can
fi
nd on the back of kitchen sponges :
Step 3
Clean and dry the connector with paper towels and acetone to remove any grease or surface pollution.
Step 4
Apply polyurethane sealant – like Sika
fl
ex 221 - with a pistol and then spread it over the entire surface to be covered with a brush :
Feel free to add some polyurethane sealant to ensure complete coverage of the area.
4.3.2 - Plate heat exchanger condensers
Use a non corrosive solvent to remove scale deposits. The equipment to be used for external water circulation, the quantity of solvent
and the safety measures to be taken must be approved by the company supplying the cleaning products or by the company conducting
these operations.
4 4- PROCESS FOR REPLACING A COMPRESSOR ON THE FIELD
1.
Unweld discharge and suction line
2.
Unscrew the rails compressor support
3.
Slide the rails of compressors out of the unit
4.
Replace the compressor
5.
Slide again the rails inside the unit and
fi
x the
rails
4 3- CLEANING THE CONDENSER