Page 34
Unit Start−Up
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been under-
water. A flood−damaged furnace is extremely dan-
gerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified ser-
vice technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
CAUTION
Before attempting to perform any service or mainte-
nance, turn the electrical power to unit OFF at dis-
connect switch.
Priming Condensate Trap
The condensate trap should be primed with water prior to
start−up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into op-
eration.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
4 − Adjust the thermostat to deactivate the heating de-
mand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al-
low the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating de-
mand and again wait for the combustion air inducer to
stop. At this point, the trap should be primed with suffi-
cient water to ensure proper condensate drain opera-
tion.
BEFORE LIGHTING
the unit, smell all around the fur-
nace area for gas. Be sure to smell next to the floor be-
cause some gas is heavier than air and will settle on the
floor.
The gas valve on the G61MPVT is equipped with a gas
control knob. Use only your hand to turn the gas control
knob. Never use tools. If the knob will not push in or turn
by hand, do not try to repair it. Call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.
Placing the furnace into operation:
G61MPVT units are equipped with an automatic ignition
system. Do not attempt to manually light burners on this
furnace. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get
hot when there is no call for heat on units with this ignition
system.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 34)
1 −
STOP
! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do
not
try to light the
burners by hand.
5 − Remove the upper access panel.
6 −
Honeywell VR8205 Gas Valve −
Turn knob on gas
valve clockwise
to
OFF
. Do not force. See figure
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instruc-
tions. If you do not smell gas go to next step.
HONEYWELL VR8205 SERIES GAS VALVE
GAS VALVE SHOWN IN OFF POSITION
MANIFOLD
PRESSURE
TAP
HIGH FIRE
ADJUSTING SCREW
(under cap)
INLET PRESSURE TAP
LOW FIRE
ADJUSTING SCREW
(under cap)
FIGURE 34
8 −
Honeywell VR8205 Gas Valve −
Turn knob on gas
valve counterclockwise
to
ON
. Do not force.
9 − Replace the upper access panel.
10− Turn on all electrical power to to the unit.