Page 32
TABLE 19
G61MPVT−60C−110 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air − Bold volumes require field−fabricated transition to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed
Second Stage COOL" Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1485
700
1675
790
1870
885
2080
980
1585
750
1700
800
1905
900
2135 1005
NORM
1350
637
1525
720
1725
815
1895
895
1435
680
1535
725
1740
820
1930
910
1175
555
1335
630
1505
710
1670
790
1280
605
1385
655
1570
740
1755
830
ADJUST"
Switch
Positions
First Stage HEAT" Speed
First Stage COOL" Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1325
625
1505
710
1695
800
1870
885
935
440
1025
485
1155
545
1285
605
NORM
1195
565
1365
645
1550
730
1720
810
840
395
915
430
1050
495
1175
555
1080
510
1205
570
1365
645
1530
720
750
355
800
380
925
435
1050
495
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70
%
of the same second stage COOL speed position.
Continuous Fan Only speed is approximately
38%
of the same second stage COOL speed position − minimum 500 cfm (235 L/s).
TABLE 20
G61MPVT−60C−110 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM.
Return Air Options: Single side return air with optional RAB return base. −
20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable air filter in order to maintain proper air velocity across the filter.
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed
Second Stage COOL" Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1475
695
1670
790
1865
880
2070
980
1555
735
1685
795
1895
895
2130 1005
NORM
1345
635
1500
710
1695
800
1865
880
1415
670
1540
725
1735
820
1930
910
1180
555
1345
635
1510
710
1685
795
1245
590
1350
635
1545
730
1725
815
ADJUST"
Switch
Positions
First Stage HEAT" Speed
First Stage COOL" Speed
1
2
3
4
1
2
3
4
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
cfm
L/s
+
1330
625
1510
715
1695
800
1875
885
1085
510
1155
545
1310
620
1475
695
NORM
1195
565
1375
650
1550
730
1725
815
955
450
1050
495
1185
560
1335
630
1080
510
1210
570
1370
645
1520
715
850
400
920
435
1070
505
1195
565
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately
91%
of the same second stage HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70
%
of the same second stage COOL speed position.
Continuous Fan Only speed is approximately
38%
of the same second stage COOL speed position − minimum 500 cfm (235 L/s).