PROBLEM 5: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER

ENERGIZES, IGNITOR IS ENERGIZED. (CONT.)

Condition

Possible Cause

Corrective Action/Comments

5.1

-- Unit operates with a cooling and

continuous fan demand.

Combustion air blower ener

5.1.1

Check that gas is being supplied to

the unit.

ACTION 1 -- Check line pressure at the gas

valve. Pressure should not exceed 13” WC for

both natural and propane. Line pressure

should read a minimum 4.5” WC for natural

and 8.0”WC for propane.

-- Combustion air blower ener-

gizes with Heating demand.

-- Ignitor is energized but unit fails

to light.

5.1.2

Miswiring of gas valve or loose

connections at multi--pin control

amp plugs or valve.

ACTION 1 -- Check for correct wiring and

loose connections. Correct wiring and/or re-

place any loose connections.

LED#1--Alternating Slow Flash
LED#2--Alternating Slow Flash

5.1.3

Malfunctioning gas valve or igni-

tion control.

ACTION 1 -- Check that 24V is supplied to the

gas valve approximately 35 seconds after

heat demand is initiated.

ACTION 2 -- Replace the valve if 24V is sup-

plied but valve does not open (check for ex-

cessive gas line pressure before replacing

gas valve).

ACTION 3 -- Replace the control board if 24V

is not supplied to valve.

PROBLEM 6: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN

PREMATURELY

Condition

Possible Cause

Corrective Action/Comments

6.1

-- Burners fire with a heating de-

mand.

-- Burners light but unit shuts off

prior to satisfying T--stat demand.

-- Diagnostic lights flash the pres-

sure switch code.

LED#1--Off

LED#2--Slow Flash

6.1.1

Low pressure differential at the

pressure switch.

ACTION 1 -- Check for restricted vent inlet or

exhaust. Remove all blockage.

ACTION 2: Check for proper vent sizing. See

installation instructions.

6.2

-- Combustion air blower energizes

with a heating demand.

B

li ht b t f il t

t

lit

6.2.1

Sensor or sense wire is improperly

installed.

ACTION 1 -- Check that sensor is properly

located (page 10) and that the sense wire is

properly attached to both the sensor and

the control.

-- Burners light but fail to stay lit.

-- After 5 tries the control diagnos-

tics flash the watchguard burners

failed to ignite code.

6.2.2

Sensor or sense wire is broken.

ACTION 1 -- Check for a broken sensor.

ACTION 2 -- Test continuity across the sense

wire. If wire or sensor are damaged replace

the component.

failed to ignite code.

LED#1--Alternating Slow Flash

LED#2--Alternating Slow Flash

6.2.3

Sensor or sensor wire is grounded

to the unit.

ACTION 1 -- Check for resistance between

the sensor rod and the unit ground.

ACTION 2 -- Check for resistance between

the sensor wire and the unit ground.

ACTION 3 -- Correct any shorts found in cir-

cuit.

6.2.4

Control does not sense flame.

ACTION 1 -- Check the microamp signal

from the burner flame. If the microamp sig-

nal is below 0.70 microamps, check the

sense rod for proper location or contamina-

tion.

ACTION 2 -- Replace, clean, or relocate

flame sense rod. If rod is to be cleaned, use

steel wool or replace sensor. DO NOT

CLEAN ROD WITH SAND PAPER. SAND PA-

PER WILL CONTRIBUTE TO THE CONTAMI-

NATION PROBLEM. NOTE: Do not attempt

to bend sense rod.

Содержание G24M SERIES

Страница 1: ...of local or state codes the guidelines and procedures outlined in this manual except where noted are recommended only and do not constitute code SPECIFICATIONS Model No G24M2 X 45 G24M2 60 G24M3 X 60...

Страница 2: ...characteristics 120 volts 60 hertz 1 phase less than 12 amps All models H Optional Accessories Must Be Ordered Extra H LPG propane kit LB 69845L 38K84 LB 69845K 81J14 Twinning Kit 96J69 5 lbs 2 kg Up...

Страница 3: ...6 x 20 x 1 Filter Rack No Size of Filters mm 2 406 x 508 x 25 Down flow Combustible Floor Base LB 79239B 67J92 10 lbs 4 kg LB 79239C 67J93 12 lbs 5 kg Sidewall Power Venting Kit 79J15 25 lbs 11 kg Han...

Страница 4: ...e Also see Filter Air Resistance table G24M4 75 G24M3 4 100 AND G24M3 4 120 BLOWER PERFORMANCE External Static Air Volume at Various Blower Speeds External Static Pressure High Medium High Medium Medi...

Страница 5: ...0 1125 2105 995 1930 910 1675 790 1480 700 30 75 2360 1115 2090 985 1915 905 1670 790 1470 695 40 100 2310 1090 2050 965 1870 880 1650 780 1440 680 50 125 2260 1065 2000 945 1810 855 1610 760 1410 665...

Страница 6: ...RY LIMITS FRONT LOUVERED PANEL DOOR INTERLOCK SWITCH CONTROL BOARD TRANSFORMER PRESSURE SWITCH NOx TURBULATOR LOW PRESSURE SWITCH Propane Only PRIMARY LIMIT FIGURE 2 HEATING COMPONENTS shown in horizo...

Страница 7: ...PRIMARY LIMIT ROLLOUT SWITCHES SURELIGHT IGNITOR FIGURE 4 To Access Blower 1 Turn off power to unit and disconnect L1 and L2 line voltage power 2 Disconnect thermostat wiring connec tions from furnac...

Страница 8: ...Shock hazard Disconnect power before servicing Control is not field repairable If control is inoperable simply replace entire control Can cause injury or death Unsafe operation will result if repair...

Страница 9: ...ration signaled when heating demand initiated at thermostat SLOW FLASH ON Primary or Secondary limit open Units with board 63K8901 or 24L85 Limit must close within 5 trials for ignition or board goes...

Страница 10: ...20 seconds after which the gas valve opens for a 4 second trial for ignition The ignitor stays en ergized for the first second of the 4 second trial G24M units with 63K89 24L85 or 56L83 the ignitor s...

Страница 11: ...e After a demand the combustion air blower continues to operate for 5 seconds post purge before stopping Post purge allows the heat exchanger to be cleared of combustion products Ignition Control The...

Страница 12: ...he indoor blower starts after a 45 second delay Gas valve remains open and blower continues to run until demand stops flame sensor senses loss of flame a limit opens or the prove switch opens If any o...

Страница 13: ...C Out T o Rollout Switches RO IN J20 P20 Pin 15 24VAC In From Rollout Switches SPARK ELECTRODE Male Spark Plug Type High Voltage Out T o Spark Electrode FS J20 P20 Pin 12 Flame Microamp Sensing FIGURE...

Страница 14: ...ly reset a tripped switch push the reset button located on the control FIGURE 12 ROLLOUT SWITCH S47 MANUAL RESET BUTTON E Primary Limit Control S10 FIGURE 13 G24M SERIES UNITS LIMIT CONTROL FOR THIS T...

Страница 15: ...ition control 24V applied to the terminals energizes the valve Inlet and outlet pressure taps are located on the valve A regulator adjustment screw is located on the valve Refer to figure 17 or 18 for...

Страница 16: ...y and Seasonal Checks 1 Inspect electrical wiring both field and factory installed for loose connections Tighten as required 2 Check voltage at disconnect switch Voltage must be within range listed on...

Страница 17: ...ent dam age to gas valve or overfire For natural gas units op erating pressure at unit gas connection must be be tween 5 0 W C and 13 0 W C For L P gas units operating pressure at unit gas connection...

Страница 18: ...itudes Refer to table 12 for pressure switch replacement for models at elevations of 4500 feet 1372m and greater TABLE 11 ALTITUDE feet m GAS FUEL MANIFOLD PRESSURE in W C kPa 0 4500 Natural 3 5 0 87...

Страница 19: ...unit rating plate To Measure Temperature Rise 1 Place plenum thermometers in the supply and return air plenums Locate supply air thermometer in the first horizontal run of the plenum where it will no...

Страница 20: ...SE CURELY IN PLACE E Blower Speed Taps Leaded Motors Blower speed tap changes are made on the SureLight control board See figure 6 Unused taps must be secured on dummy terminals PARK M1 and or PARK M...

Страница 21: ...tial for gas leaks fire or explosion Some soaps used for leak detection are corrosive to certain metals Carefully clean piping thor oughly after leak detection has been completed Can cause damage to p...

Страница 22: ...92 7 7 3 0 5 1 5 0 1 851 6 167 5 75 16 250 5 225 17 5 2 6 7 20 867 21 5 2 5 35 6685 6 7 1 7 5 35 0 5 0 7 0 52 287 6 7 6 85 COMPRESSOR COMMON POWER HEAT INDOOR BLOWER COMMON HS UNIT COMMON HS UNIT COMP...

Страница 23: ...lower nears full speed combustion air prove switch S18 closes 5 When S18 closes assuming the flame rollout switch S47 primary limit S10 and secondary limits S21 are closed the furnace control begins a...

Страница 24: ...N RESET THERMOSTAT LED 5 flash if flame sensed with valve off LED Steady on if control board failure NO NO CHECK TO SEE IF MAIN VALVE IS OFF SEQUENCE HOLDS UNTIL HI LIMIT CLOSES LED 4 flashes NO CHECK...

Страница 25: ...e REMAINS UNCHANGED THROUGHOUT SEQUENCE THERMOSTAT CALLS FOR COOLING SYSTEM FAN SWITCHES TO HEATING SPEED AFTER SELECTED DELAY ACC TERM REMAINS ENERGIZED SYSTEM FAN SWITCHED TO COOLING SPEED ACC TERMI...

Страница 26: ...Pressure Switch delay Once S18 closes a 15 second pre purge follows 4 SureLight control energizes ignitor A 20 second warm up period begins 5 Gas valve opens for a 4 second trial for ignition Ignitor...

Страница 27: ...G SPEED LED 1 SLOW FLASH LED 2 OFF GAS VALVE OFF COMBUSTION AIR BLOWER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence holds until pressure switch closes or thermostat resets cont...

Страница 28: ...TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND IGNITION WATCHGUARD MODE GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 ALT SLOW FLASH LED 2 ALT SLO...

Страница 29: ...CHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY ACB COOL SPEED AND ACC TERM ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS AC...

Страница 30: ...Y THERMOSTAT OPENS COMBUSTION AIR AND HTG ACC TERMINAL DE ENERGIZE SYSTEM FAN SWITCHED TO ACB COOL SPEED ACC TERM REMAINS ON THERMOSTAT OPENS BOARD 63K89 SYSTEM FAN OFF ACC TERM OFF AFTER OFF DELAY CO...

Страница 31: ...ch open ACTION 1 Manually reset the roll out switch by pushing the top button ACTION 2 Determine the cause of the roll out switch activation before leaving furnace out code LED 1 O 1 2 2 Roll out swit...

Страница 32: ...ternating Fast Flash 2 1 2 Broken or failed ignitor ACTION 1 Unplug ignitor and read resis tance across ignitor If resistance does not read between 10 9 and 19 7 ohms replace the ignitor PROBLEM 3 UNI...

Страница 33: ...with a heating demand Diagnostic lights flash the pres sure switch failure code 2 5 min utes after heating demand 4 1 2 Pressure switch does not close due to obstructions in the pressure lines ACTION...

Страница 34: ...atisfying T stat demand Diagnostic lights flash the pres sure switch code LED 1 Off LED 2 Slow Flash 6 1 1 Low pressure differential at the pressure switch ACTION 1 Check for restricted vent inlet or...

Страница 35: ...rsootingdepositsoroth er restrictions in the heat exchanger assem bly Cleanassemblyasoutlinedininstruction manual ACTION 2 ForG24Mgasfurnaces checkfor proper combustion and flow CO2 should measurebetw...

Страница 36: ...ated ACTION 1 Check sense rod for contamina tion or coated surface Clean the sense rod with steel wool or replace sensor DO NOT USE SAND PAPER TO CLEAN ROD SAND PAPER WILL CONTRIBUTE TO THE CON TAMINA...

Отзывы: