background image

Page 4

REQUIREMENTS

In the US, installation of Lennox gas central furnaces
must conform with local building codes or, in the abĆ

sence of local codes, with the current National Fuel Gas
Code  (ANSI-Z223.1).  The  National  Fuel  Gas  Code  is
available from:

American National Standards Institute, Inc.

1430 Broadway
New York, NY  10018

All  G20R units are A.G.A. (American Gas Association)
and C.G.A (Canadian Gas Association) certified.

NOTE-G20RXE series units (units equipped with flame

rods) are certified for use with natural gas only.

Air supply for combustion and ventilation must conĆ
form to the methods outlined in the current National
Fuel Gas Code.

WARNING

Product contains fiberglass wool.
Disturbing  the  insulation  in  this  product  during

installation, maintenance, or repair will expose you

to fiberglass wool. Breathing this may cause lung

cancer. (Fiberglass wool is known to the State of

California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,

and eye irritation.
To reduce exposure to this substance or for further

information,  consult  material  safety  data sheets

available from address shown below, or contact

your supervisor.

Lennox Industries Inc.

P.O. Box 799900

Dallas, TX 75379-9900

The furnace is certified for installation clearances to
combustible material as listed on the appliance rating
plate and in table 1:

Clearances

Location

Inches (mm)

Service access

To combustible

materials

From draft hood relief

opening

Front

Top, side and rear

Flue

Front

36 in. (914mm)*

1 in. (25mm)

6 in. (152mm)**

6 in. (152mm)

NOTE-Service access clearance must be maintained.

TABLE 1

* If tight installation, front service clearance may be 24" (610mm).

** Clearance is 1" (25mm) for type B1 vent.

Accessibility and service clearances must take preceĆ
dence over fire protection clearances.
Vent installations shall be in accordance with the curĆ
rent GAMA/A.G.A. venting tables manual (502,567M),
or applicable provisions of local building codes. Vent

connectors serving appliances vented by natural draft
shall not be connected into any portion of mechanical
draft systems operating under positive pressure.

NOTE-For installation on combustible floors, appliance

shall not be installed directly on carpeting, tile, or other

combustible material other than wood flooring.

For installation in a residential garage, unit must be
installed so that burner(s) and ignition source are loĆ
cated no less than 18 in. (457 mm) above floor. Furnace

must be located or protected to avoid physical damage
by vehicles.

Unit  must  be  adjusted  to  obtain  a  temperature  rise
within the range specified on appliance rating plate.

The draft hood shall be installed in the same atmospheric
pressure zone as the combustion air inlet to the furnace.

G20R unit must be installed so that electrical compoĆ
nents are protected from water.
When  furnace  is  used  in  conjunction  with  cooling
units, it shall be installed in parallel with, or on the upĆ
stream side of, cooling units to avoid condensation in
the heating element. With a parallel flow arrangement,

damper (or other means to control the flow of air) shall
be adequate to prevent chilled air from entering the
furnace and, if manually operated, must be equipped
with means to prevent operation of either unit, unless

damper is in the full heat" or cool" position.
When installed, furnace must be electrically grounded
in accordance with local codes or, in the absence of loĆ
cal  codes,  with  the  current  National  Electric  Code,

ANSI/NFPA No. 70. The National Electric Code (ANSI/
NFPA No. 70) is available from:

National Fire Protection Association
470 Atlantic Avenue
Boston, MA  02210

Field wiring connection with unit must meet or exceed
specifications  of  type  T  wire  and  withstand  a  63

F

(17

C) temperature rise. When furnace is installed so

that  supply  ducts  carry  air  circulated  by  furnace  to

areas outside space containing furnace, return air shall
be handled by a duct(s) sealed to the furnace casing
and terminating outside space containing furnace.

This  furnace  is  certified  for  installation  clearances  to

combustible material as listed on appliance rating plate
and in table 1. Accessibility and service clearances must
take precedence over fire protection clearances.

n Canada, installation of C.G.A. certified units must conĆ

form with current Standard CAN/CGA-B149.1 Installation
Code for Natural Gas Burning Appliances and Equipment"
and CAN/CGA-B149.2 Installation Code for Propane Gas
Burning  Appliances  and  Equipment,"  local  plumbing  or

waste water codes and other applicable local codes. AuĆ
thorities having jurisdiction should be consulted before
installation. Adequate clearance shall be made around air

Содержание G20R series

Страница 1: ...BLESHOOTING 20 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WHAT TO DO IF YOU SMELL GAS If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance Installation and service must be performed ...

Страница 2: ...ecĆ tion or to help in alignment with cooling coil ă Dimensions before flanges are bent as shipped Dimensions after flanges are bent Dimension after flange furnished is field installed on unit M d l N A B C C D D E Model No inch mm inch mm inch mm inch mm inch mm inch mm inch mm G20RQ2 3 X EĆ50 G20RQ3 X EĆ75 16Ć1 4 413 14Ć1 8 359 10Ć3 4 273 12 305 1Ć1 2 38 2Ć1 8 54 3Ć1 8 79 G20RQ4 X EĆ75 21Ć1 4 54...

Страница 3: ...Y LIMIT CONTROL CABINET ROLL OUT SWITCH GAS VALVE PILOT ELECTRODE ASSEMBLY FLUE TRANSITION LOWER ACCESS PANEL FILTER ACCESS DOOR DOOR INTERLOCK SWITCH BCC CONTROL REMOVABLE STRIP BLOCKED VENT SHUT OFF SWITCH DAMPER MOTOR GEAR PATCH PLATE PATCH PLATE SPRING DAMPER SWITCH DAMPER SWITCH COVER ROLL OUT SWITCH DAMPER BURNER BOX DAMPER BOX PARTS ARRANGEMENT G20R Units Shown REMOVABLE BURNER BOX TOP FIGU...

Страница 4: ...stible material other than wood flooring For installation in a residential garage unit must be installed so that burner s and ignition source are loĆ cated no less than 18 in 457 mm above floor Furnace must be located or protected to avoid physical damage by vehicles Unit must be adjusted to obtain a temperature rise within the range specified on appliance rating plate The draft hood shall be inst...

Страница 5: ...xhaust vents and gas pipĆ ing A portion of this information has been reprinted with permission from the National Fuel Gas Code ANSI Z223 1 This reprinted material is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety In Canada refer to the standard CAN CGA B149 1 and B149 2 installation codes Combustion Air Require...

Страница 6: ...ATER HEATER OPENINGS To Adjacent Room FIGURE 3 NOTE Each opening shall have a free area of at least one square inch per 1 000 Btu per hour of the total input rating of all equipment in the enclosure but not less than 100 square inches G20R FURNACE CHIMĆ NEY OR GAS VENT Air from Outside If air from outside is brought in for combustion and venĆ tilation the confined space must have two permanent ope...

Страница 7: ... FLOOR UNIT Front to Rear Side to Side in mm in mm Q2 3 50 Q3 75 Q4 75 Q3 4 100 Q5 100 Q3 125 Q4 5 125 Q4 5 150 20 1 2 20 1 2 20 1 2 20 1 2 520 520 520 520 12 1 4 17 1 4 22 1 4 27 1 4 311 438 565 692 NOTE Floor opening dimensions listed are 1 4 6mm larger than unit openings 2 Flange warm air plenum and lower into opening 3 Use duckbill pliers to bend unit flanges out from openĆ ing Install provide...

Страница 8: ...turn air plenum A door must never be used as a portion of the return air duct system Allow absolutely no sagging cracks gaps etc For no reason should return and supply air duct systems ever be connected to or from other heatĆ ing devices such as a fireplace or stove etc Fire explosion carbon monoxide poisoning personal injury and or property damage could result WARNING Blower door must be securely...

Страница 9: ...lothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathĆ room exhausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace dampers 4 Follow the lighting instructions Place the appliance being inspected in operation Adjust thermostat so appliance will operate continuously 5 Test for spill...

Страница 10: ... properly labeled by the inĆ staller FIGURE 12 GROUND JOINT UNION AUTOMATIC GAS VALVE with manual shut off valve FIELD PROVIDED AND INSTALLED GROUND JOINT UNION LEFT SIDE PIPING STANDARD RIGHT SIDE PIPING ALTERNATE AUTOMATIC GAS VALVE with manual shut off valve DRIP LEG DRIP LEG MANUAL MAIN SHUT OFF VALVE With 1 8 NPT Plugged Tap Shown MANUAL MAIN SHUT OFF VALVE With 1 8 NPT Plugged Tap Shown TABL...

Страница 11: ...0 110 43 3700 104 77 3450 97 69 3250 92 03 4 101 6 4 026 102 260 23000 651 27 15800 447 39 12800 362 44 10900 308 64 9700 274 67 8800 249 18 8100 229 36 7500 212 37 7200 203 88 6700 189 72 NOTE Capacity given in cubic feet of gas per hour kilo liters of gas per hour and based on 0 60 specific gravity gas ...

Страница 12: ...plugs are provided on both sides of cabinet to facilitate wiring 3 Install room thermostat according to instructions proĆ vided with thermostat 4 Install a separate fused disconnect switch near the unit so power can be turned off for servicing 5 Route thermostat wire as shown in figure 14 Keep wire away from draft hood and flue pipe Do not route wire across draft hood 6 Complete wiring connections...

Страница 13: ...NAL COOLING SPEED TAP TERMINAL DUMMY TERMINALS CONTINUOUS FAN TERMINAL THERMOSTAT JUMPER Electronic or Mechanical FIGURE 16 Y R W G G W Y T R BCC CONTROL THERMOSTAT IGNITION CONTROL GAS VALVE DAMPER DOOR SWITCH FLAME ROLLOUT SWITCH PRIMARY LIMIT BLOCKED VENT SHUTOFF SWITCH BLACK WHITE TO COMPRESSOR CONTACTOR FIELD INSTALLED LOW VOLTAGE FIELD INSTALLED LINE VOLTAGE TYPICAL G20R FIELD WIRING DIAGRAM...

Страница 14: ...Page 14 FIGURE 17 TYPICAL G20R WIRING DIAGRAM ...

Страница 15: ...l automatically light The pilot goes out when there is no demand for heat WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life Gas Valve Operation Figures 19 20 1 STOP Read the safety information at the beginning of this section 2 Set thermostat to lowest setting See figure 18 3 Turn off all electrical power ...

Страница 16: ... Gas Pressure 1 Check gas line pressure with unit firing at maximum rate A minimum of 4 5 w c 1 12kPa for natural gas or 10 5 w c 2 61kPa for LP propane gas should be maintained 2 After line pressure has been checked and adjusted check manifold pressure Correct manifold presĆ sure for LP propane gas is 9 5 w c 2 36kPa No adĆ justment is needed in high altitude applications A natural gas to LP prop...

Страница 17: ...ning 5 Grasp blower motor harness connector located on back on motor Depress lock tab and pull connector from motor 6 Pull harness connector and wires through blower acĆ cess panel opening 7 Select desired taps for heating and cooling White common Red heating Black cooling 8 Depress harness connector tab to release wire termiĆ nal Select connector location for new speed refer to unit wiring diagra...

Страница 18: ...wing procedure and figure 27 to clean filter TABLE 5 MODEL NO FILTER SIZE Q2 3 50 Q3 75 Q4 75 Q3 4 100 Q5 100 Q3 125 Q4 5 125 20 X 10 X 1 20 X 12 X 1 20 X 14 X 1 Q4 5 150 20 X 16 X 1 FIGURE 27 BLOWER RIGHT FILTER LEFT FILTER LEFT SUPPORT ANGLE RIGHT FILTER SUPPORT ANGLE ON THREE SIDES 150 UNITS MAKE SURE FILTER IS PLACED INTO THIS CHANNEL 150 UNITS ROTATE FILTER TO REMOVE TAB 1 Turn off electric p...

Страница 19: ...h Continue with items 13 through 15 below and reinstall flame rods and springs 13 Clean top of burner ports with a wire brush See figĆ ure 29 14 Clean burner ports by inserting a cleaning tool made from a piece of sheet metal cut to fit the burner ports and work in and out of each port See figure 30 15 Clean inside of each burner with a bottle cleaning brush See figure 31 CLEANING TOP FIGURE 29 CL...

Страница 20: ... burner with pilot mount Flue baffles Pilot electrode assembly Primary limit control Flame roll out switch Blocked vent shut off switch Damper motor Damper switch Couplings Damper spring Grommets G20RE START UP AND PERFORMANCE CHECK LIST Filter Clean Secure Supply Voltage Electrical Connections Tight START UP AND PERFORMANCE CHECK LIST Job Name Job Location Installer Unit Model No Furnace Btu Inpu...

Страница 21: ... REPLACE BCC NO IS 120VAC ACROSS N CAB CHECK DAMPER MOTOR WIRING AND DAMPER MOTOR YES YES IS UNIT LIT NO CHECK 1 DAMPER MOTOR 2 IGNITION CONTROL 3 GAS VALVE 4 IGNITOR 5 LIMIT SWITCHES 6 PROVE SWITCH YES IS BLOWER RUNNING ON LOW SPEED 45 SEC AFTER FURNACE LIGHTS NO IS 120VAC ACROSS N H YES IS 24VAC ACROSS C V REPLACE BCC NO NO CHECK WIRING YES IS 120VAC ACROSS N ACC YES REMOVE R W JUMPER AFTER THE ...

Отзывы: