background image

Page 4

Fan off" timings (time that the blower operates after the

heat demand has been satisfied) are determined by the arĆ
rangement of a jumper across pins on the BCC2-2 blower

control board. See figure 2. To adjust fan off " timings, gentĆ
ly  disconnect  jumper  and  reposition  across  pins  correĆ

sponding with new timing. Fan on" time is factory set at 45
seconds and is not adjustable.
Figure 4 shows the various fan off" timings and how jumpĆ

er should be positioned. Unit is shipped with a factory fan
off" setting of 90 seconds. Fan off" time will affect comfort

and efficiency and is adjustable to satisfy individual apĆ
plications.

3-Door Interlock Switch (S51)

A door interlock switch rated 16A at 125VAC is located beĆ
hind the blower access panel. The switch is wired in series

with line voltage. When the blower door access panel is reĆ
moved the unit will shut down.

B-Blower Motors and Capacitors

All G17 units use direct drive blower motors. All motors

used are 120V permanent split capacitor motors to ensure
maximum efficiency. See table1 for ratings.

TABLE 1

G17 BLOWER RATINGS 120V 1PH

BLOWER MOTOR

HP

Q2

Q3
Q3/4

CAP

1/2

1/3

1/4

5MFD 370V

5MFD 370V
7.5MFD 370V

Q5/6

Q4

Q4/5

1/2

7.5MFD 370V

3/4

40MFD 370V

3/4

40MFD 370V

C-Blocked Vent Shutoff Switch (S62)

The blocked vent shutoff switch or spill switch (S62) is loĆ

cated on the right side of the draft diverter. The switch is a
high  temperature  N.C.  SPST  manualĆreset  limit  conĆ

nected in series with ignition control A3. The  switch opens
when excess heat is sensed in the draft diverter. Excess

heat in the draft diverter can be caused by a blocked vent
or reversed draft (outside air coming down the flue).  Limits

on early production units open at 300

_

F+12

_

F (149

°

 C) on

a  temperature  rise.    Later  production  units  use  a  limit
which opens at 262

_

F+12

_

F (128

°

 C). It cannot be adĆ

justed.

D-Flame Rollout Switch (S47)

Flame rollout switch is a high temperature limit located on
top of the burner box. The limit is a N.C. SPST manualĆreset

limit connected in series with the ignition control A3. When
S47 senses rollout, the ignition control immediately stops

ignition and closes the gas valve. If unit is running and flame

rollout is detected, the gas valve will close and ignition conĆ
trol will be disabled.  Rollout can be caused by a reverse

draft, blocked flue or lack of combustion air.  The switch is
factory set and cannot be adjusted. See table 2. The switch

can be manually reset. To manually reset a tripped switch,

push the red reset button located on the control.

TABLE 2

FLAME ROLLOUT SWITCH SETPOINTS

HEATING INPUT KBTUH

SETPOINT

50, 75
100, 125

260

°

F + 12

°

F

300

°

F + 12

°

F

E-Limit Control (S10)

The primary limit (S10) on G17 units is located in the middle of

the heating vestibule wall.  When excess heat is sensed in the
heat exchanger, the limit will open and interrupt current to the

gas valve. If the limit is tripped, the BCC2-2 energizes the
blower. The limit automatically resets when unit temperature

returns to normal. Table  3 shows the temperatures at which
the limit trips on a temperature rise and then closes on a temĆ

perature fall.

TABLE 3

UNIT MODEL NO.

TEMP. RISE

TEMP. FALL

G17Q2-50 Series
G17Q3-75 Series
G17Q3/4-100 Series

G17Q5/6-100 Series
G17Q5/6-125 Series

130

°

F + 5

°

F

100

°

F + 10

°

F

180

°

F + 5

°

F

150

°

F +  8

°

F

180

°

F + 5

°

F

150

°

F + 10

°

F

250

°

F + 5

°

F

220

°

F +  8

°

F

180

°

F + 5

°

F

150

°

F +  10

°

F

PRIMARY LIMIT TEMPERATURES

INSULATING COVER (s)

FIGURE 5

G17 SERIES UNITS

LIMIT CONTROL FOR

SP
ADE CONNECT

ORS

INSULA

TING COVER

LIMIT

LIMIT

F-Robertshaw Electronic Ignition

The Robertshaw electronic ignition is an intermittent pilot

ignition control module located on the vestibule panel. See
figure 1. When there is a call for heat, the control generates

a spark to ignite the pilot, after which the control senses the
flame. If the flame current is too weak (less than 1 microĆ

amp) the control will shutdown and de-energize the gas
valve. Flame current should be between 1 and 5 microĆ

amps. See figure 6.

DANGER

Shock hazard.

Spark related components contain high voltage.

 disconnect power before servicing.  Control is

not field repairable.  If control is inoperable, simĆ

ply replace entire control.

Can cause injury or death.  Unsafe operation will

result if repair is attempted.

Содержание G17Q2-50

Страница 1: ...ines and procedures outlined in this manual except where noted are recommended only and do not constitute code Model No Input Btuh Output Btuh A F U E Flue connection in diameter round Temperature rise range F High static certified by A G A in wg Gas Piping Size I P S inches Natural LPG Blower wheel nominal diameter x width in Blower motor hp Number and size of filters in Electrical characteristic...

Страница 2: ...E PILOT ELECTRODE ASSEMBLY LIMIT W R W Y T G 90 150 270 210 24V TCOM VALVE SENSE G17 CONTROL BOX BCC2 BLOWER CONTROL CENTER INB N1 CABN XFMRN N CAB L1 A XFMR D D H ACC FIGURE 2 NEUTRAL TERMINALS ACCESSORY TERMINAL THERMOSTAT CONNECTIONS BLOWER TIME ADJUSTMENT JUMPER HEATING SPEED TAP TERMINAL COOLING SPEED TAP TERMINAL DUMMY TERMINALS GROUND SCREW DOOR INTERLOCK SWITCH 120VAC 24VAC TRANSFORMER NOT...

Страница 3: ...ich controls the blower and monitors primary limit and gas valve operation The control has a non adjustable factory preset on fan timĆ ing Fan off timings are adjustable The board is divided into two sections 120 and 24VAC Line voltage comes into the board on the 120VAC side See figure 2 CAB and XFMR send 120VAC to the damper motor and transformer respectively The active cooling and heating blower...

Страница 4: ...ted in series with the ignition control A3 When S47 senses rollout the ignition control immediately stops ignition and closes the gas valve If unit is running and flame rollout is detected the gas valve will close and ignition conĆ trol will be disabled Rollout can be caused by a reverse draft blocked flue or lack of combustion air The switch is factory set and cannot be adjusted See table 2 The s...

Страница 5: ...t and outlet pressure taps are located on the valve A pilot adjusting screw and regulator adjustment screw figĆ ures 7 and 9 are located on the valve Refer to figure 8 for exact location of valve features FIGURE 7 Robertshaw 7200 gas valve shown GAS VALVE SELECTOR ARM IN OFF POSITION REGULATOR COVER SCREW ADJUSTING SCREW SPRING TYPICAL ACCESS TO REGULATOR FOR ADJUSTMENT AND L P CHANGEOVER An LPG c...

Страница 6: ...pped for service to the damper door or burner box The spring must be removed in order to remove the damper door After service is complete the spring must rest snugly in notch for damper prove switch to function properly Do not force door open damage to the spring and motor may ocĆ cur Take care to open damper door slowly DAMPER PROVE SWITCH SPRING SPRING FITS SNUGLY IN NOTCH FIGURE 11 AXLE DAMPER ...

Страница 7: ...gas supply FIGURE 13 MANUAL MAIN SHUT OFF VALVE WILL NOT HOLD TEST PRESSURE IN EXCESS OF 0 5 PSIG 14 W C GAS VALVE CAP GAS PIPING TEST PROCEDURE FIELD PROVIDED LINE PRESSURE TAP When checking piping connections for gas leaks use preĆ ferred means Kitchen detergents can cause harmful corroĆ sion on various metals used in gas piping Use of a specialty Gas Leak Detector is strongly recommended It is ...

Страница 8: ...tion of 2 000 ft 610 m or more above sea level Tables 5 and 6 show the derated manifold pressure for high altitude operation with both natural and LP Propane gas Operating this appliance at the manifold pressure specified on the tables will ensure proper unit heat input at high altitude Consult your gas utility for the local natural gas heating value 2 25 wc Altitude Heating Value Btu Ft Ft 900 95...

Страница 9: ...emperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable inĆ crease blower speed to reduce temperature To change blower speed taps see the Blower Speed Taps section in this manual C External Static Pressure 1 Measure tap locations as shown in figure 15 2 Punch a 1 4 diameter hole in supply and return air pleĆ nums Ins...

Страница 10: ...m filter applications for use on G17Q5 6 100 and G17Q5 6 125 reĆ quire an optional kit available from Lennox G17X models are factory equipped for use with bottom return air only If side reĆ turn air is desired an optional kit is available See figure 17 Filters must be cleaned or replaced when dirty to assure proper unit operation Replace with same hogshair type filter material cut to specific meas...

Страница 11: ...h burner with a bottle cleaning brush See figĆ ure 21 6 Replace burners making sure to fully engage in rear receiving slot in heat exchanger See figure 22 ReseĆ cure gas manifold and supply piping 7 Resecure damper assembly damper prove switch cover and burner box top Carefully open damper by hand to ensure that the damper spring closes damper correctly and that the damper prove switch is engaged ...

Страница 12: ...loses assuming the flame rollout switch S47 and blocked vent shutoff switch S62 are closed 24VAC is supplied to the TH terminal of the electronic control A3 7 Through the electronic control the pilot valve P of the gas valve opens The spark electrode ignites the pilot and the flame sensor senses the pilot 8 When flame is sensed the main gas valve opens and supplies the burners with gas 9 Terminal ...

Страница 13: ...EPLACE BCC2 1 NO IS 120VAC ACROSS N1 CAB CHECK DAMPER MOTOR WIRING AND DAMPER MOTOR YES YES ARE BURNERS LIT NO CHECK 1 DAMPER MOTOR 2 IGNITION CONTROL 3 GAS VALVE 4 IGNITOR 5 LIMIT SWITCHES 6 PROVE SWITCH YES IS BLOWER RUNNING ON LOW SPEED 45 SEC AFTER FURNACE LIGHTS NO IS 120VAC ACROSS N1 H YES IS 24VAC ACROSS T V REPLACE BCC2 1 NO NO CHECK WIRING YES IS 120VAC ACROSS N1 ACC YES REMOVE R W JUMPER...

Отзывы: