background image

CLEANING TOP

FIGURE 19

CLEANING

PORTS

FIGURE 20

CLEANING INSIDE

FIGURE 21

FIGURE 22

BURNER SLOT ENGAGEMENT

ENGAGE

BURNER

IN SLOT

Page 11

CAUTION

Potential for unit damage.

Use extreme care when opening damper door to

prevent permanent damage to the damper door.

Can cause damage to damper motor resulting in

improper furnace operation.

6- Remove flue restrictor over flue outlet (Ć50 only).
7- Gas manifold, gas valve and burners do not need to be

removed and can be left in place.

8- Insert a 2 ft. steel rod with a 20 in. length of chain atĆ

tached to one end into top opening of heat exchanger.

Refer to figure 18.

9- Shake rod to drop chain through clamshell into burner

cavity in bottom of heat exchanger.

10- Attach bottom of chain to 2 ft. (600 mm) rod.
11- Push and pull the rods back and forth and up and down

with a vigorous motion. The chain will dislodge the soot

and scale deposits inside the heat exchanger. Repeat
for each clamshell.

12- With a shop vacuum or rags, clean out soot and scale

deposits from bottom of heat exchanger.

To clean burners:

1- Disconnect gas piping.
2- Remove  screws

holding  gas  manĆ
ifold  in  place  and

pull  burners  from
heat exchanger.

3- Clean top of burnĆ

er ports with a wire

brush. See figure 19.

4- Clean  burner  ports

by inserting a cleanĆ

ing tool (made from
a  piece  of  sheet

metal  cut  to  fit  the
burner  ports)  and

work  in  and  out  of
each port. See figure 20.

5- Clean inside of

each  burner

with  a  bottle
cleaning

brush. See figĆ
ure 21.

6- Replace burners making sure to fully engage in rear

receiving slot in heat exchanger. See figure 22. ReseĆ

cure gas manifold and supply piping.

7- Resecure  damper

assembly, damper
prove switch cover

and  burner  box
top. Carefully open

damper by hand to
ensure  that  the

damper 

spring

closes 

damper

correctly  and  that
the  damper  prove

switch is engaged
when damper is open.

8- Install flue restrictor (Ć50 models only).
9- Before  replacing  draft  hood,    flue  pipe  and  access

panels, inspect draft hood gasket.  Replace gasket if
necessary.

10- Carefully  check  all  piping  connections  (factory  and

field) for gas leaks. Use a leak detecting solution or othĆ

er preferred means.

11- Turn on gas and electrical supply.

CAUTION

Potential for gas leaks, fire or explosion.

Some soaps used for leak detection are corrosive

to  certain  metals.    Carefully  clean  piping  thorĆ

oughly after leak detection has been completed.

Can  cause  damage  to  piping  resulting  in  gas

leaks, fire or explosion.

C-Supply Air Blower

1- Check and clean blower wheel.
2- Motors used on the Lennox G17 series units are permaĆ

nently lubricated and need no further lubrication.

A - Flue and Chimney

Flue  must  conform  to  all  AGA/GAMA  venting  requireĆ

ments for Category I Central Furnaces."  Flue pipe deteriĆ
orates from the inside out and must be disconnected in orĆ

der to check thoroughly.  Check flue pipe, chimney and all
connections for tightness and to make sure there is no

blockage or leaks.

B - Electrical

1 - Check all wiring for loose connections.
2 - Check for correct voltage.
3 - Check amp-draw on blower motor.

Содержание G17Q2-50

Страница 1: ...ines and procedures outlined in this manual except where noted are recommended only and do not constitute code Model No Input Btuh Output Btuh A F U E Flue connection in diameter round Temperature rise range F High static certified by A G A in wg Gas Piping Size I P S inches Natural LPG Blower wheel nominal diameter x width in Blower motor hp Number and size of filters in Electrical characteristic...

Страница 2: ...E PILOT ELECTRODE ASSEMBLY LIMIT W R W Y T G 90 150 270 210 24V TCOM VALVE SENSE G17 CONTROL BOX BCC2 BLOWER CONTROL CENTER INB N1 CABN XFMRN N CAB L1 A XFMR D D H ACC FIGURE 2 NEUTRAL TERMINALS ACCESSORY TERMINAL THERMOSTAT CONNECTIONS BLOWER TIME ADJUSTMENT JUMPER HEATING SPEED TAP TERMINAL COOLING SPEED TAP TERMINAL DUMMY TERMINALS GROUND SCREW DOOR INTERLOCK SWITCH 120VAC 24VAC TRANSFORMER NOT...

Страница 3: ...ich controls the blower and monitors primary limit and gas valve operation The control has a non adjustable factory preset on fan timĆ ing Fan off timings are adjustable The board is divided into two sections 120 and 24VAC Line voltage comes into the board on the 120VAC side See figure 2 CAB and XFMR send 120VAC to the damper motor and transformer respectively The active cooling and heating blower...

Страница 4: ...ted in series with the ignition control A3 When S47 senses rollout the ignition control immediately stops ignition and closes the gas valve If unit is running and flame rollout is detected the gas valve will close and ignition conĆ trol will be disabled Rollout can be caused by a reverse draft blocked flue or lack of combustion air The switch is factory set and cannot be adjusted See table 2 The s...

Страница 5: ...t and outlet pressure taps are located on the valve A pilot adjusting screw and regulator adjustment screw figĆ ures 7 and 9 are located on the valve Refer to figure 8 for exact location of valve features FIGURE 7 Robertshaw 7200 gas valve shown GAS VALVE SELECTOR ARM IN OFF POSITION REGULATOR COVER SCREW ADJUSTING SCREW SPRING TYPICAL ACCESS TO REGULATOR FOR ADJUSTMENT AND L P CHANGEOVER An LPG c...

Страница 6: ...pped for service to the damper door or burner box The spring must be removed in order to remove the damper door After service is complete the spring must rest snugly in notch for damper prove switch to function properly Do not force door open damage to the spring and motor may ocĆ cur Take care to open damper door slowly DAMPER PROVE SWITCH SPRING SPRING FITS SNUGLY IN NOTCH FIGURE 11 AXLE DAMPER ...

Страница 7: ...gas supply FIGURE 13 MANUAL MAIN SHUT OFF VALVE WILL NOT HOLD TEST PRESSURE IN EXCESS OF 0 5 PSIG 14 W C GAS VALVE CAP GAS PIPING TEST PROCEDURE FIELD PROVIDED LINE PRESSURE TAP When checking piping connections for gas leaks use preĆ ferred means Kitchen detergents can cause harmful corroĆ sion on various metals used in gas piping Use of a specialty Gas Leak Detector is strongly recommended It is ...

Страница 8: ...tion of 2 000 ft 610 m or more above sea level Tables 5 and 6 show the derated manifold pressure for high altitude operation with both natural and LP Propane gas Operating this appliance at the manifold pressure specified on the tables will ensure proper unit heat input at high altitude Consult your gas utility for the local natural gas heating value 2 25 wc Altitude Heating Value Btu Ft Ft 900 95...

Страница 9: ...emperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable inĆ crease blower speed to reduce temperature To change blower speed taps see the Blower Speed Taps section in this manual C External Static Pressure 1 Measure tap locations as shown in figure 15 2 Punch a 1 4 diameter hole in supply and return air pleĆ nums Ins...

Страница 10: ...m filter applications for use on G17Q5 6 100 and G17Q5 6 125 reĆ quire an optional kit available from Lennox G17X models are factory equipped for use with bottom return air only If side reĆ turn air is desired an optional kit is available See figure 17 Filters must be cleaned or replaced when dirty to assure proper unit operation Replace with same hogshair type filter material cut to specific meas...

Страница 11: ...h burner with a bottle cleaning brush See figĆ ure 21 6 Replace burners making sure to fully engage in rear receiving slot in heat exchanger See figure 22 ReseĆ cure gas manifold and supply piping 7 Resecure damper assembly damper prove switch cover and burner box top Carefully open damper by hand to ensure that the damper spring closes damper correctly and that the damper prove switch is engaged ...

Страница 12: ...loses assuming the flame rollout switch S47 and blocked vent shutoff switch S62 are closed 24VAC is supplied to the TH terminal of the electronic control A3 7 Through the electronic control the pilot valve P of the gas valve opens The spark electrode ignites the pilot and the flame sensor senses the pilot 8 When flame is sensed the main gas valve opens and supplies the burners with gas 9 Terminal ...

Страница 13: ...EPLACE BCC2 1 NO IS 120VAC ACROSS N1 CAB CHECK DAMPER MOTOR WIRING AND DAMPER MOTOR YES YES ARE BURNERS LIT NO CHECK 1 DAMPER MOTOR 2 IGNITION CONTROL 3 GAS VALVE 4 IGNITOR 5 LIMIT SWITCHES 6 PROVE SWITCH YES IS BLOWER RUNNING ON LOW SPEED 45 SEC AFTER FURNACE LIGHTS NO IS 120VAC ACROSS N1 H YES IS 24VAC ACROSS T V REPLACE BCC2 1 NO NO CHECK WIRING YES IS 120VAC ACROSS N1 ACC YES REMOVE R W JUMPER...

Отзывы: