Lennox G17Q2-50 Скачать руководство пользователя страница 7

Page 7

WARNING

Shock and burn hazard.
G17 units are equipped with an intermittent pilot

ignition system.  Do not attempt to light manually.

4- Set  fan  switch  to  AUTO  or  ON  and  move  system

selection switch to HEAT. Adjust thermostat to a setĆ

ting above room temperature.

5- If unit does not light the first time, it will attempt one

more ignition before locking out.

6- If lockout occurs, repeat steps 1, 2, 3 and 4.

C-Safety or Emergency Shutdown

Turn off  unit power. Close manual and main gas valves.

D-Extended Period Shutdown

Turn off thermostat or set to UNOCCUPIED" mode. Close

all gas valves (both internal and external to unit) to guaranĆ
tee no gas leak into combustion chamber. Turn off power

to unit. All access panels, covers and vent caps must be in
place and secured.

V-HEATING SYSTEM SERVICE CHECKS
A-A.G.A. Applications and Requirements

All units are A.G.A. design certified without modifications.

Refer  to  the  G17  Operation  and  Installation  Instruction
Manual Information.

B-Gas Piping

Gas supply piping should not allow more  than 0.5"W.C.
drop in pressure between gas meter and unit. Supply gas

pipe must not be smaller than unit gas connection.
Compounds used on gas piping threaded joints should be
resistant to action of liquefied petroleum gases.

C-Testing Gas Piping

IMPORTANT

In case emergency shutdown is required, turn off

the main shutĆoff valve and disconnect the main

power to unit.  These controls should be properly

labeled by the installer.

When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged if

subjected to more than 0.5psig (14" W.C.). See figure 13

If

the pressure is equal to or less than 0.5psig (14"W.C.), use

the manual shut-off valve before pressure testing to isoĆ
late furnace from gas supply.

FIGURE 13

MANUAL MAIN SHUT-OFF VALVE

WILL NOT HOLD TEST PRESSURE

IN EXCESS OF 0.5 PSIG (14"W.C.)

GAS VALVE

CAP

GAS PIPING TEST PROCEDURE

FIELD PROVIDED

LINE PRESSURE TAP

When checking piping connections for gas leaks, use preĆ

ferred means. Kitchen detergents can cause harmful corroĆ
sion on various metals used in gas piping. Use of a specialty

Gas Leak Detector is strongly recommended. It is available
through  Lennox  under  part  number  31B2001.  See  Corp.

8411-L10, for further details.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.

D-Testing Gas Supply Pressure

When testing supply gas pressure, connect test gauge to

inlet pressure tap (field provided). See figure 13. Check
gas line pressure with unit firing at maximum rate. Low

pressure may result in erratic operation or underfire. High
pressure can result in permanent damage to gas valve or

overfire. For natural gas units, operating pressure at unit
gas connection must be between 4.5" W.C. and 10.5" W.C.

For L.P. gas units, operating pressure at unit gas connecĆ
tion must be between 10.5" W.C. and 13.5" W.C.
On multiple unit installations, each unit should be checked

separately, with and without units operating. Supply presĆ
sure must fall within range listed in previous paragraph.

E-Check Manifold Pressure

After line pressure has been checked and adjusted, check
manifold pressure. Checks of manifold pressure are made

as verification of proper regulator adjustment. Manifold presĆ
sure for the G17 can be measured at any time the gas valve

is open and is supplying gas to the unit. Normal manifold
pressure for natural gas units is 3.5 in. w.c. For LP/propane

gas the correct manifold pressure is 9.5 in. w.c. See tables 5
and 6 for derated manifold pressure values in high altitude

application for both natural and LP gases. Move pressure
gauge  to  outlet  pressure  tap  located  on  unit  gas  valve

(GV1). See figure 8 for location of pressure tap on gas
valve.

Содержание G17Q2-50

Страница 1: ...ines and procedures outlined in this manual except where noted are recommended only and do not constitute code Model No Input Btuh Output Btuh A F U E Flue connection in diameter round Temperature rise range F High static certified by A G A in wg Gas Piping Size I P S inches Natural LPG Blower wheel nominal diameter x width in Blower motor hp Number and size of filters in Electrical characteristic...

Страница 2: ...E PILOT ELECTRODE ASSEMBLY LIMIT W R W Y T G 90 150 270 210 24V TCOM VALVE SENSE G17 CONTROL BOX BCC2 BLOWER CONTROL CENTER INB N1 CABN XFMRN N CAB L1 A XFMR D D H ACC FIGURE 2 NEUTRAL TERMINALS ACCESSORY TERMINAL THERMOSTAT CONNECTIONS BLOWER TIME ADJUSTMENT JUMPER HEATING SPEED TAP TERMINAL COOLING SPEED TAP TERMINAL DUMMY TERMINALS GROUND SCREW DOOR INTERLOCK SWITCH 120VAC 24VAC TRANSFORMER NOT...

Страница 3: ...ich controls the blower and monitors primary limit and gas valve operation The control has a non adjustable factory preset on fan timĆ ing Fan off timings are adjustable The board is divided into two sections 120 and 24VAC Line voltage comes into the board on the 120VAC side See figure 2 CAB and XFMR send 120VAC to the damper motor and transformer respectively The active cooling and heating blower...

Страница 4: ...ted in series with the ignition control A3 When S47 senses rollout the ignition control immediately stops ignition and closes the gas valve If unit is running and flame rollout is detected the gas valve will close and ignition conĆ trol will be disabled Rollout can be caused by a reverse draft blocked flue or lack of combustion air The switch is factory set and cannot be adjusted See table 2 The s...

Страница 5: ...t and outlet pressure taps are located on the valve A pilot adjusting screw and regulator adjustment screw figĆ ures 7 and 9 are located on the valve Refer to figure 8 for exact location of valve features FIGURE 7 Robertshaw 7200 gas valve shown GAS VALVE SELECTOR ARM IN OFF POSITION REGULATOR COVER SCREW ADJUSTING SCREW SPRING TYPICAL ACCESS TO REGULATOR FOR ADJUSTMENT AND L P CHANGEOVER An LPG c...

Страница 6: ...pped for service to the damper door or burner box The spring must be removed in order to remove the damper door After service is complete the spring must rest snugly in notch for damper prove switch to function properly Do not force door open damage to the spring and motor may ocĆ cur Take care to open damper door slowly DAMPER PROVE SWITCH SPRING SPRING FITS SNUGLY IN NOTCH FIGURE 11 AXLE DAMPER ...

Страница 7: ...gas supply FIGURE 13 MANUAL MAIN SHUT OFF VALVE WILL NOT HOLD TEST PRESSURE IN EXCESS OF 0 5 PSIG 14 W C GAS VALVE CAP GAS PIPING TEST PROCEDURE FIELD PROVIDED LINE PRESSURE TAP When checking piping connections for gas leaks use preĆ ferred means Kitchen detergents can cause harmful corroĆ sion on various metals used in gas piping Use of a specialty Gas Leak Detector is strongly recommended It is ...

Страница 8: ...tion of 2 000 ft 610 m or more above sea level Tables 5 and 6 show the derated manifold pressure for high altitude operation with both natural and LP Propane gas Operating this appliance at the manifold pressure specified on the tables will ensure proper unit heat input at high altitude Consult your gas utility for the local natural gas heating value 2 25 wc Altitude Heating Value Btu Ft Ft 900 95...

Страница 9: ...emperature is too low decrease blower speed If temperature is too high first check the firing rate Provided the firing rate is acceptable inĆ crease blower speed to reduce temperature To change blower speed taps see the Blower Speed Taps section in this manual C External Static Pressure 1 Measure tap locations as shown in figure 15 2 Punch a 1 4 diameter hole in supply and return air pleĆ nums Ins...

Страница 10: ...m filter applications for use on G17Q5 6 100 and G17Q5 6 125 reĆ quire an optional kit available from Lennox G17X models are factory equipped for use with bottom return air only If side reĆ turn air is desired an optional kit is available See figure 17 Filters must be cleaned or replaced when dirty to assure proper unit operation Replace with same hogshair type filter material cut to specific meas...

Страница 11: ...h burner with a bottle cleaning brush See figĆ ure 21 6 Replace burners making sure to fully engage in rear receiving slot in heat exchanger See figure 22 ReseĆ cure gas manifold and supply piping 7 Resecure damper assembly damper prove switch cover and burner box top Carefully open damper by hand to ensure that the damper spring closes damper correctly and that the damper prove switch is engaged ...

Страница 12: ...loses assuming the flame rollout switch S47 and blocked vent shutoff switch S62 are closed 24VAC is supplied to the TH terminal of the electronic control A3 7 Through the electronic control the pilot valve P of the gas valve opens The spark electrode ignites the pilot and the flame sensor senses the pilot 8 When flame is sensed the main gas valve opens and supplies the burners with gas 9 Terminal ...

Страница 13: ...EPLACE BCC2 1 NO IS 120VAC ACROSS N1 CAB CHECK DAMPER MOTOR WIRING AND DAMPER MOTOR YES YES ARE BURNERS LIT NO CHECK 1 DAMPER MOTOR 2 IGNITION CONTROL 3 GAS VALVE 4 IGNITOR 5 LIMIT SWITCHES 6 PROVE SWITCH YES IS BLOWER RUNNING ON LOW SPEED 45 SEC AFTER FURNACE LIGHTS NO IS 120VAC ACROSS N1 H YES IS 24VAC ACROSS T V REPLACE BCC2 1 NO NO CHECK WIRING YES IS 120VAC ACROSS N1 ACC YES REMOVE R W JUMPER...

Отзывы: