• 34 •
Application Guide • FLEXY FX-AGU-1112-E
ELECTRICAL DATA
CONTROL variables
Lennox CLIMATIC 50 and BMS
Modbus, Trend or BACnet
.
Specifi cation of the Bus:
Type:
RS485
Speed: (Adjustable on
CLIMATIC 50
via display DS50; Setting 3933)
1200
2400
4800
9600
19200
Parity: Fixed
no parity (N)
Length: Fixed
8 bits (8)
Stop bit: Fixed
2 bits (2)
Spécifi cation du protocole:
Mode: Fixed
R.T.U. for Modbus
Address of slave: (Adjustable on
CLIMATIC 50
via display DS50; Setting 3931)
1
to 200
Supported functions, for Modbus:
Reading Bits : 1 or 2
Reading Words : 3 or 4
Writing simple Bit : 5
Writing simple Word : 6
Functionality `Watchdog’ on CLIMATIC 50.
The automat
CLIMATIC 50
being passive on the bus it cannot detect any cut of communication with the BMS. From where in the event
of cut of communication the Roof-Top would continue to function with the last adjustments emitted by the BMS. To avoid operation,
penalizing the correct operation of the Roof-Top, the BMS must regularly write in the word 01h a value different from 0. The automat
CLIMATIC 50
decreases the value of the word 01h of 5 units every 5 seconds.
If the BMS writes the value 1000 in the word 01h, in the event of cut of communication at the end of 16 minutes 40 seconds the ins-
tructions emitted by the BMS are not taken more into account by the software of the automat
CLIMATIC 50
. I.e. the following points
are not took into account by the program of the automat
CLIMATIC 50
if the word 01h is equal to 0
Points concerned with the word 01h
Words :
02H / 03H / 04H / 05H / 06H / 07H / 08H
Bits :
03H / 04H / 06H / 07H / 08H / 09H / 0AH / 0BH / 0CH / 0DH / 0EH
This functionality does not prohibit the writing of the bit or of the word, those are always readable on our display DS50 (show in
mode BMS via the key `Prg’)
This list might slighlty change depending of software version, please contact your Lennox sales of
fi
ce to get the most up to date version