• 37 •
MODBUS - BACNET
@
(hexa)
@
(deci)
DS50
01H
1
R/W
1 = 1 s
3934
02H
2
R/W
10 = 1.0°c
3322 (BMS)
03H
3
R/W
10 = 1.0°c
3323 (BMS)
04H
4
R/W
1 = 1%
3312 (BMS)
05H
5
R/W
10 = 1.0°c
3322 (Uno)
06H
6
R/W
10 = 1.0°c
3323 (Uno)
07H
7
R/W
10 = 1.0%
3341 (BMS)
08H
8
R/W
10 = 1.0%
3342 (BMS)
09H
9
R/W
0AH
10
R/W
0BH
11
R/W
0CH
12
R/W
1 = 1h
3121
0DH
13
R/W
1 = 1m
3122
0EH
14
R/W
1 = 1
3123
0FH
15
R/W
1 = 1
3124
10H
16
R/W
1 = 2001
3125
11H
17
R/W
10 = 1.0°c
2824
12H
18
R/W
10 = 1.0%
2828
13H
19
R/W
10 = 1.0°c
2814
14H
20
R/W
10 = 1.0%
2818
15H
21
R/W
16H
22
R/W
17H
23
R/W
18H
24
R/W
19H
25
R/W
1AH
26
R/W
1BH
27
R/W
1CH
28
R/W
1DH
29
R/W
1EH
30
R/W
1FH
31
R/W
20H
32
R/W
21H
33
R
1 = 1
1000
22H
34
R
10 = 1.0°c
2112
23H
35
R
10 = 1.0°c
2111
24H
36
R
10 = 1.0°c
2113
25H
37
R
10 = 1.0°c
2114
26H
38
R
10 = 1.0%
2122
27H
39
R
10 = 1.0
g/Kg
2124
28H
40
R
10 = 1.0%
2121
Application Guide • FLEXY FX-AGU-1112-E
ELECTRICAL DATA
CONTROL variables
[ BMS ] Activation of the control by a computer or an automat - mode BMS is activated if
this value is different from zero, This value is decreased every second
[Occupation][Room SP] Required maximum room temperature in °C. Cooling set point
[Occupation][Room SP] Required minimum room temperature in °C. Heating set point
[Room SP] Required room minimum fresh air rate in % Middle of the dead zone.
[Inoccupation][Room SP] Required maximum room temperature in °C. Cooling set point
[Inoccupation][Room SP] Required minimum room temperature in °C. Heating set point
[Humidity] Desired Maximum relative humidity in Room (in %). – Dehumidi
fi
cation set point.
[Humidity] Desired Minimum relative humidity in Room (in %). – Humidi
fi
cation set point.
not used
not used
not used
[Clock] Hour
[Clock] Minute
[Clock] Day of the month
[Clock] Month
[Clock] Year
[BMS] Room temperature coming from the BMS
[BMS] Room humidity coming from the BMS
[BMS] Outdoor temperature coming from the BMS
[BMS] Outdoor humidity coming from the BMS
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
[Alarm] Code Error
[Temperature] Room
[Temperature] Outdoor
[Temperature] Supply
[Temperature] Return
[Relative Humidity] Room
[Absolute Humidity] Room
[Relative Humidity] Outdoor