![Lennox FLEXY FX 025 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/lennox/flexy-fx-025/flexy-fx-025_application-manual_1876891037.webp)
• 35 •
MODBUS - BACNET
@
(hexa)
@
(deci)
DS50
01H
1
R/W
L
3111
02H
2
R/W
L
3112
03H
3
R/W
L
3351 (BMS)
04H
4
R/W
L
3352 (BMS)
05H
5
R/W
L
3935
06H
6
R/W
L
3324 (BMS)
07H
7
R/W
L
3331 (BMS)
08H
8
R/W
L
3332 (BMS)
09H
9
R/W
L
3353 (BMS)
0AH
10
R/W
L
3354 (BMS)
0BH
11
R/W
L
3355 (BMS)
0CH
12
R/W
L
3356 (BMS)
0DH
13
R/W
L
3357 (BMS)
0EH
14
R/W
L
3358 (BMS)
0FH
15
R/W
L
10H
16
R/W
L
…
11H
17
R/W
L
2141
12H
18
R/W
L
2142
13H
19
R/W
L
2143
14H
20
R/W
L
2144
15H
21
R/W
L
2145
16H
22
R/W
L
17H
23
R/W
L
18H
24
R/W
L
19H
25
R/W
L
1AH
26
R/W
L
1BH
27
R/W
L
1CH
28
R/W
L
1DH
29
R/W
L
1EH
30
R/W
L
1FH
31
R/W
L
20H
32
R/W
L
21H
33
R
L
1000
22H
34
R
L
2315
23H
35
R
L
2321
24H
36
R
L
2516
25H
37
R
L
2517
26H
38
R
L
2526
27H
39
R
L
2527
28H
40
R
L
2536
Application Guide • FLEXY FX-AGU-1112-E
ELECTRICAL DATA
CONTROL variables
[On / Off] Unit
[Reset] Discharges the safety measures of the unit
[Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, [On] the
blower is running.
[Enable] Stopping and running of the fan in the «Control Dead Zone». [Off] the blower is
stopped, [On] the blower is running.
[BMS] Activation of the Inoccupation mode [Off] occupation mode - [On] inoccupation
mode
[Room regulation] Choices of the priority of regulation in Heating - [Off] Heat Pump then
Hot water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
[F-Air Reheat] Activate reheating of the fresh air in the dead zone to maintain supply
temperature.
[F-Air Reheat] Choices of the priority of regulation in Heating - [Off] Heat Pump then Hot
water coil or Electric or Gas [On] Hot water coil or Electric or Gas then Heat Pump
[Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped.
[Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, [Off] Stop the
CO2 control on a zone.
[Enable] [OFF] Force the unloading of compressors in cooling mode.
[Enable] [OFF] Force the unloading of compressors in heating mode.
[Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil)
[Enable] [OFF] Force the unloading of humidity control.
not used
[Clock] [OFF] read hour & minute [ON] write hour & minute
[Dry contact] Digital Output, Free 1, BM50-J17-NO12
[Dry contact] Digital Output, Free 2, BE50-J5-NO1
[Dry contact] Digital Output, Free 3, BE50-J6-NO2
[Dry contact] Digital Output, Free 4, BE50-J7-NO3
[Dry contact] Digital Output, Free 5, BE50-J8-NO4
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
[Alarm] General
[On/Off] Fan, Blower
[On/Off] Fan, Extraction
[On/Off] Compressor, 1
[On/Off] Compressor, Heat pump, 1
[On/Off] Compressor, 2
[On/Off] Compressor, Heat pump, 2
[On/Off] Compressor, 3