Page 11
XP14 SERIES
STEP 4 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
wiring must conform with current local codes and the cur
rent Canadian Electrical Code (CEC).
Refer to the furnace or air handler installation instructions
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
Use the transformer provided with the furnace or air handler
for low‐voltage control power (24VAC - 40 VA minimum)
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be properly
grounded in accordance with national
and local codes.
Line voltage is present at all
components when unit is not in
operation on units with single‐pole
contactors. Disconnect all remote
electric power supplies before opening
access panel. Unit may have multiple
power supplies.
IMPORTANT !
If unit is equipped with a crankcase heater, it
should be energized 24 hours before unit start-up
to prevent compressor damage as a result of slug
ging.
WARNING
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this
product.
CAUTION
Failure to use properly sized wiring and circuit breaker
may result in property damage. Size wiring and circuit
breaker(s) per Product Specifications bulletin (EHB)
and unit rating plate.
CAUTION
ELECTROSTATIC
DISCHARGE
(ESD)
Precautions and
Procedures
Electrostatic discharge can affect
electronic components. Take care
during unit installation and service to
protect the unit's electronic controls.
Precautions will help to avoid control
exposure to electrostatic discharge by
putting the unit, the control and the
technician at the same electrostatic
potential. Touch hand and all tools on
an unpainted unit surface before
performing any service procedure to
neutralize electrostatic charge.
Refer to the unit nameplate for minimum circuit ampacity,
and maximum fuse or circuit breaker (HACR per NEC).
Install power wiring and properly sized disconnect switch.
NOTE -
Units are approved for use only with copper
conductors. Ground unit at disconnect switch or
connect to an earth ground.
SIZE CIRCUIT AND INSTALL SERVICE
DISCONNECT SWITCH
1
NOTE -
24VAC, Class II circuit connections are
made in the control panel.
Install room thermostat (ordered separately) on an
inside wall approximately in the center of the conditioned
area and 5 feet (1.5m) from the floor. It should not be
installed on an outside wall or where it can be affected
by sunlight or drafts.
THERMOSTAT
5 FEET
(1.5M)
INSTALL THERMOSTAT
2
SERVICE
DISCONNECT
SWITCH
MAIN FUSE
BOX/BREAKER
PANEL
FIGURE 12