background image

Page 13

 XP14 SERIES

STEP 5 -- UNIT START-UP

IMPORTANT

If unit is equipped with a crankcase heater, it should be
energized 24 hours before unit start-up to prevent
compressor damage as a result of slugging.

1 - Rotate fan to check for binding.
2 - Inspect all factory- and field-installed wiring for loose

connections.

3 - After evacuation is complete, open the liquid line and

vapor line service valve stems to release the refriger­
ant charge (contained in outdoor unit) into the sys­
tem.

4 - Replace the stem caps and tighten to the value listed

in table 2.

5 - Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted with the power company and the volt­
age condition has been corrected.

6 - Connect manifold gauge set for testing and charging.
7 - Set the thermostat for a cooling demand. Turn on

power to the indoor indoor unit and close the outdoor
unit disconnect switch to start the unit.

8 - Recheck voltage while the unit is running. Power

must be within range shown on the unit nameplate.

9 - Check system for sufficient refrigerant using the pro­

cedures outlined under

 Checking Refrigerant

Charge

.

OPERATING MANIFOLD GAUGE SET AND 
SERVICE VALVES

The liquid and vapor line service valves are used for re­
moving refrigerant, flushing, leak testing, evacuating,
checking charge and charging.
Each valve is equipped with a service port which has a
factory-installed valve stem. Figures 15 and 16 provide
information on how to access and operate both angle-
and ball-type service valves.

Torque Requirements

When servicing or repairing heating, ventilating and air
conditioning components, ensure the fasteners are ap­
propriately tightened. Table 2 lists torque values for fas­
teners.

TABLE 2

TORQUE REQUIREMENTS

Parts

Recommended Torque

Service valve cap

8 ft.- lb.

11 NM

Sheet metal screws

16 in.- lb.

2 NM

Machine screws #10

28 in.- lb.

3 NM

Compressor bolts

90 in.- lb.

10 NM

Gauge port seal cap

8 ft.- lb.

11 NM

IMPORTANT

To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.

Using Manifold Gauge Set

When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.

Manifold gauge set used with HFC-410A refrigerant sys­
tems must be capable of handling the higher system op­
erating pressures. The gauges should be rated for use
with pressures of 0 - 800 psig on the high side and a low
side of 30” vacuum to 250 psig with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psig of pressure with a 4000 psig burst rating.

BALL (SHOWN
CLOSED)

SERVICE PORT

CORE

TO 

OPEN,

 ROTATE STEM

COUNTERCLOCKWISE 90°.

TO 

CLOSE, 

ROTATE STEM

CLOCKWISE 90°.

SERVICE PORT

SERVICE PORT

CAP

STEM CAP

VALVE
STEM

1 - Remove stem cap with an appropriately sized wrench.

2 - Use an appropriately sized wrench to open. To open valve, rotate

stem counterclockwise 90°. To close, rotate stem clockwise 90°.

OPERATING BALL-TYPE SERVICE VALVE

FIGURE 15

Содержание Elite XP14-018-230

Страница 1: ...stment alteration service or maintenance can cause property damage personal in jury or loss of life Installation and service must be performed by a li censed professional installer or equivalent or se...

Страница 2: ...Unit Placement NOTICE Roof Damage This system contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to degrade Failure to follow this notice could result in...

Страница 3: ...or expansion valve approved for use with HFC 410A refrigerant must be ordered separately and installed prior to operating the system LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SL...

Страница 4: ...ated NOTE Some applications may require a field provided 7 8 to 1 1 8 adapter NOTE When installing refrigerant lines longer than 50 feet refer to the Refrigerant Piping Design and Fabrica tion Guideli...

Страница 5: ...eflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CL...

Страница 6: ...r the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE...

Страница 7: ...oths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Страница 8: ...mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon r...

Страница 9: ...e to 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and v...

Страница 10: ...pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positi...

Страница 11: ...ith this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit ratin...

Страница 12: ...AND HIGH VOLTAGE CIRCUITS A B C D 3 FIGURE 13 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT IND...

Страница 13: ...rvice port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When servicing or rep...

Страница 14: ...clockwise ACCESS SERVICE PORT FIGURE 17 Checking Refrigerant Charge The XP14 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge shoul...

Страница 15: ...ed the unit will remain in forced defrost mode until defrost thermostat opens or termin ated on maximum defrost time 14 minutes If the jumper is not removed once 5 seconds has elapsed 7 seconds total...

Страница 16: ...the snow level below the louvered panels NOTE The filter and all access panels must be in place any time the unit is in operation If you are unsure about the filter required for your system call your...

Страница 17: ...con firm that pipes are not rubbing copper to copper Also ensure that refrigerant pipes are not being af fected by indoor air contamination Check condition of insulation on the refrigerant lines Repai...

Страница 18: ...e Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appro...

Отзывы: