background image

Page 15

 XP14 SERIES

Compressor Delay (P5)

The defrost control has a field-selectable function to re­
duce occasional sounds that may occur while the unit is
cycling in and out of the defrost mode.

The compressor will be cycled off for 30 seconds going in
and out of the defrost mode when the compressor delay
jumper is installed.

NOTE -

 The 30‐second compressor feature is ignored

when jumpering the TEST pins.

Time Delay

The timed‐off delay is five minutes long. The delay helps
to protect the compressor from short‐cycling in case the
power to the unit is interrupted or a pressure switch
opens. The delay is bypassed by placing the timer select
jumper across the TEST pins for 0.5 seconds.

Test Mode

The 

TEST

 mode is activated by removing the jumper on

the defrost termination pins (

30

60 

or

 90

) and placing the

jumper on the 

TEST

 pins after 24VAC is applied to the

control. The low pressure input is ignored in

 TEST

 mode.

IMPORTANT

The TEST pins are ignored and the TEST function is
locked out:

S

If the jumper is applied on the TEST pin before
24VAC is applied to the control.

S

If there is a jumper on the 30 or 60 minute defrost
termination pins.

Bypass Anti-Short-Cycle Delay

The 

Y1

 input must be active 

ON

, the high pressure switch

must be closed or a jumper must be installed on the high
pressure terminals of the control.

Initiate a Force Defrost

The 

Y1 

input must be active 

ON

, the high pressure switch

must be closed or a jumper must be installed on the high
pressure terminals of the control, the defrost thermostat
 must be closed or  a jumper must be placed across the

DF

 terminals on the control and the 

O

 terminals must not

have 24VAC (no power to reversing valve) before control
will enter into a force defrost.

Test Mode Sequence

Using the  defrost termination pin, short the 

TEST

 pins for

a period of two seconds:

S

Clear timed lockout / or pressure switch lockout func­
tion.

S

Enter defrost mode.

After entering force defrost, if the jumper is removed be­
fore 5 seconds has elapsed, the unit will remain in forced
defrost mode until defrost thermostat opens or termin­
ated on maximum defrost time (14 minutes). If the jumper
is not removed, once 5 seconds has elapsed (7 seconds
total), the unit will terminate defrost and return to heat

mode. The 

TEST 

mode will then be locked­out and no fur­

ther 

TEST

 mode operation will be executed until the

jumper on the 

TEST 

pins is removed and re­applied to the

applicable defrost termination pins.

IMPORTANT

After testing has been completed, properly reposition test
jumper across desired timing pins.

Service Light Connection

The defrost control includes terminal connections for a
service light which provides a signal that activates the
room thermostat service light during periods of inefficient
operation.

Defrost Control Diagnostic LEDs

The defrost board uses two LEDs for diagnostics. The
LEDs flash a specific sequence according to the condi­
tion.

TABLE 3

DEFROST CONTROL (CMC1) DIAGNOSTIC LEDS

Mode

Green LED (DS2)

Red LED (DS1)

No power to con­
trol

OFF

OFF

Normal operation /
power to control

Simultaneous Slow FLASH

Anti‐short cycle
lockout

Alternating Slow FLASH

High pressure
switch fault

Slow FLASH

OFF

High pressure
switch lockout

ON

OFF

HIGH PRESSURE SWITCH (S4)

This unit is equipped with a high pressure switch which is
located on the liquid line. The SPST, normally closed
pressure switch opens when liquid line pressure rises
above the factory setting of 590 + 15 psig and automati­
cally resets at 418 + 15 psig.

Homeowners Information

CAUTION

Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at discon­
nect switch.

WARNING

The State of California has determined that this product
may contain or produce a chemical or chemicals, in very
low doses, which may cause serious illness or death. It
may also cause cancer, birth defects, or reproductive
harm.

In order to ensure peak performance, your system must
be properly maintained. Clogged filters and blocked air­
flow prevent your unit from operating at its most efficient
level. The system should be inspected and serviced be­
fore each cooling and heating season by a licensed pro­
fessional HVAC service technician (or equivalent).

Содержание Elite XP14-018-230

Страница 1: ...stment alteration service or maintenance can cause property damage personal in jury or loss of life Installation and service must be performed by a li censed professional installer or equivalent or se...

Страница 2: ...Unit Placement NOTICE Roof Damage This system contains both refrigerant and oil Some rubber roofing material may absorb oil causing the rubber to degrade Failure to follow this notice could result in...

Страница 3: ...or expansion valve approved for use with HFC 410A refrigerant must be ordered separately and installed prior to operating the system LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SL...

Страница 4: ...ated NOTE Some applications may require a field provided 7 8 to 1 1 8 adapter NOTE When installing refrigerant lines longer than 50 feet refer to the Refrigerant Piping Design and Fabrica tion Guideli...

Страница 5: ...eflon rings H Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CL...

Страница 6: ...r the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE...

Страница 7: ...oths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated...

Страница 8: ...mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon r...

Страница 9: ...e to 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and v...

Страница 10: ...pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positi...

Страница 11: ...ith this product CAUTION Failure to use properly sized wiring and circuit breaker may result in property damage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit ratin...

Страница 12: ...AND HIGH VOLTAGE CIRCUITS A B C D 3 FIGURE 13 Typical 24VAC Control Wiring Diagrams Field Installed THERMOSTAT INDOOR UNIT R C W1 Y1 O G R C W1 W2 W3 G R C W1 Y1 O COMMON 1ST STAGE AUXILIARY HEAT IND...

Страница 13: ...rvice port which has a factory installed valve stem Figures 15 and 16 provide information on how to access and operate both angle and ball type service valves Torque Requirements When servicing or rep...

Страница 14: ...clockwise ACCESS SERVICE PORT FIGURE 17 Checking Refrigerant Charge The XP14 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge shoul...

Страница 15: ...ed the unit will remain in forced defrost mode until defrost thermostat opens or termin ated on maximum defrost time 14 minutes If the jumper is not removed once 5 seconds has elapsed 7 seconds total...

Страница 16: ...the snow level below the louvered panels NOTE The filter and all access panels must be in place any time the unit is in operation If you are unsure about the filter required for your system call your...

Страница 17: ...con firm that pipes are not rubbing copper to copper Also ensure that refrigerant pipes are not being af fected by indoor air contamination Check condition of insulation on the refrigerant lines Repai...

Страница 18: ...e Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and appro...

Отзывы: