Lennox EL180UHE SERIES Скачать руководство пользователя страница 5

Page 5

•     Do not install the furnace where drafts might blow di-

rectly into it. This could cause improper combustion and 

unsafe operation.

•     Do not block the furnace combustion air openings with 

clothing, boxes, doors, etc. Air is needed for proper 

combustion and safe unit operation.

•     When the furnace is installed in an attic or other insulat-

ed space, keep insulation away from the furnace.

•    Please consult the manufacturer of your evaporator 

coil for their recommendations on distance required 

between the heat exchanger and their drain pan. Ade-

quate space must be provided between the drain pan 

and the furnace heat exchanger.

NOTE - The Commonwealth of Massachusetts stipu-

lates these additional requirements:

•    Gas furnaces shall be installed by a licensed plumber 

or fitter only.

•    The gas cock must be “T handle” type.
•    When a furnace is installed in an attic, the passageway 

to and service area surrounding the equipment shall 

be floored.

 WARNING

This prodcut contains a chemical known to the State 

of California to cause cancer, birth defects, or other 

reproductive harm.

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufficient 

outdoor air for combustion. Infiltration provided all the air 

that was needed. In today’s homes, tight construction 

practices make it necessary to bring in air from outside for 

combustion. Take into account that exhaust fans, appli-

ance vents, chimneys, and fireplaces force additional air 

that could be used for combustion out of the house. Un-

less outside air is brought into the house for combustion, 

negative pressure (outside pressure is greater than inside 

pressure) will build to the point that a downdraft can oc-

cur in the furnace vent pipe or chimney. As a result, com-

bustion gases enter the living space creating a potentially 

dangerous situation.
In the absence of local codes concerning air for combus-

tion and ventilation, use the guidelines and procedures in 

this section to install EL180UHE furnaces to ensure effi

-

cient and safe operation. You must consider combustion 

air needs and requirements for exhaust vents. A portion of 

this information has been reprinted with permission from 

the National Fuel Gas Code (ANSI-Z223.1). This reprint-

ed material is not the complete and official position of the 

ANSI on the referenced subject, which is represented only 

by the standard in its entirety.

 CAUTION

Do not install the furnace in a corrosive or 

contaminated atmosphere. Meet all combustion and 

ventilation air requirements, as well as all local codes.

 CAUTION

Insufficient combustion air can cause headaches, 

nausea, dizziness or asphyxiation. It will also cause 

excess water in the heat exchanger resulting in rusting 

and premature heat exchanger failure. Excessive 

exposure to contaminated combustion air will result 

in safety and performance related problems. Avoid 

exposure to the following substances in the combustion 

air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials

All  gas-fired  appliances  require  air  for  the  combustion 

process. If sufficient combustion air is not available, the 

furnace or other appliances will operate inefficiently and 

unsafely. Enough air must be provided to meet the needs 

of all fuel-burning appliances and appliances such as ex-

haust  fans  which  force  air  out  of  the  house.  When  fire

-

places, exhaust fans, or clothes dryers are used at the 

same time as the furnace, much more air is necessary 

to ensure proper combustion and to prevent a downdraft. 

Insufficient air causes incomplete combustion which can 

result in carbon monoxide.
In addition to providing combustion air, fresh outdoor air 

dilutes contaminants in the indoor air. These contaminants 

may include bleaches, adhesives, detergents, solvents 

and other contaminants which can corrode furnace com-

ponents.
The requirements for providing air for combustion and 

ventilation depend largely on whether the furnace is in-

stalled in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or 

large equipment room with a volume greater than 50 cubic 

feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com-

bined input rating of all appliances installed in that space. 

This space also includes adjacent rooms which are not 

separated by a door. Though an area may appear to be un

Содержание EL180UHE SERIES

Страница 1: ...t service agency or the gas supplier CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves...

Страница 2: ...49 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Si...

Страница 3: ...h local building codes In the absence of lo cal codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the follow ing ad...

Страница 4: ...heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL180UHE units may be used for...

Страница 5: ...rial is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety CAUTION Do not install the furnace in a corrosive or cont...

Страница 6: ...the two spac es Each opening must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening mu...

Страница 7: ...hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 6...

Страница 8: ...le mounting leg The bolt and washer must be removed before the furnace is placed into operation After the bolt and washer have been re moved the rigid leg will not touch the blower housing RIGID LEG r...

Страница 9: ...turn Air with transition and filter Figure 8 Figure 9 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with...

Страница 10: ...for clearances to combustible materials as indicated on the unit nameplate Minimum clearances for closet or alcove installations are shown in figure 11 This furnace may be installed in either an attic...

Страница 11: ...filter is being installed as part of this system to ensure better indoor air quality the filter must be properly sized Highefficiency filters have a higher static pressure drop than standardefficiency...

Страница 12: ...4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models Figure 15 shows the combustion air inducer as shipped from the fac tory Mounting Screws Location...

Страница 13: ...arbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Re install pressure switch on the other side of orifice plate and r...

Страница 14: ...ing document Use self drilling sheet metal screws or a mechanical fas tener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the ven...

Страница 15: ...fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met The chimney is currently serving at least one drafthood equipped appliance The ve...

Страница 16: ...ing to approved engineering methods 5 Multiple appliance vents The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent...

Страница 17: ...equivalent insulation qualities 14 All venting pipe passing through floors walls and ceilings must be installed with the listed clearance to combustible materials and be fire stopped according to loca...

Страница 18: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 5...

Страница 19: ...23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 25...

Страница 20: ...ection CAUTION If a flexible gas connector is required or allowed by the authority that has jurisdiction black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet The...

Страница 21: ...985 27 89 873 24 72 791 22 39 728 20 61 677 19 17 635 17 98 600 17 00 2 50 8 2 067 52 502 4020 113 83 2760 78 15 2220 62 86 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1160 32 8...

Страница 22: ...e 27 Electrical WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the un...

Страница 23: ...operly grounded in accordance with national and local codes Accessory Terminals One line voltage EAC 1 4 spade terminal is provided on the furnace integrated control See figure 30 for integrated contr...

Страница 24: ...on or appro priate dual fuel thermostat instructions Indoor Blower Speeds 1 When the thermostat is set to FAN ON the indoor blower will run continuously on the fan speed when there is no cooling or he...

Страница 25: ...to activation of combustion air inducer 12 Flame Sensed without gas valve energized 13 Low Line Voltage Note 1 Notes Note A Heartbeat is indicated by a Slow Flash 1 sec on 1 sec off repeating Note Las...

Страница 26: ...l electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move...

Страница 27: ...ve temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve...

Страница 28: ...ricifice Kit Natuarl Gas Orifice Kit 045 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 070 No Change 80W52 80W51 73W37 11K49 73W81 73W81 110 80W52 80W51 090 8...

Страница 29: ...gas line pressure After one hour of continuous thermostat demand for heat the Watchguard will re set and remake thermostat demand to the furnace and automatically reset the integrat ed control to begi...

Страница 30: ...erating range Thermal Limits should be checked by restricting airflow and not disconnecting the indoor blower For additional details please see Service and Application Note H049 2 Verify that system t...

Страница 31: ...Page 31 EL180UHE BURNER ASSEMBLY REMOVAL Manifold And Gas Valve Retention Rings Cross Over Ignitor Sensor Rollout Switches Burner Detail Front View Figure 33...

Страница 32: ...service agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel...

Страница 33: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Страница 34: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Отзывы: