Page 14

HORIZONTAL RIGHT POSITION

Top Vent Discharge

 

Gas supply piping must be brought into the unit from the bottom

in order to accommodate the flue pipe.

Remove make-up box assembly (2 screws) and cut wire tie to

free make-up box wires. Re-install make-up box on other side

of cabinet.

 

Re-secure make-up box wires by either pulling excess wires

through the blower compartment and securing with supplied

wire tie, or coil excess wire and secure to the gas manifold.

FLOW

AIR

flue transition

vent pipe

pressure switch

cover plate

make-up box

collector box

Figure 20 

HORIZONTAL RIGHT POSITION

Side Vent Discharge - no modifications necessary

FLOW

AIR

Pressure Switch

Flue Transition

Collector Box

Make-Up Box

Vent Pipe

Figure 21 

The EL180UHE series units are classified as fan-assisted 

Category I furnaces when vertically vented according to 

the latest edition of National Fuel Gas Code (NFPA 54 / 

ANSI Z223.1) in the USA. 

A fan-assisted Category I furnace is an appliance equipped 

with an integral mechanical means to either draw or force 

combustion products through the combustion chamber 

and/or heat exchanger. The EL180UHE is not approved 

for use with horizontal venting.

NOTE - 

Use these instructions as a guide. They do not su

-

persed local codes. This funace must be vented according 

to all locawl codes these installation instructions, and the 

provided venting tables in these instructions

The venting tables in this manual were extracted from the 

National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are 

provided as a guide for proper vent installation. Proper 

application, termination, construction and location of vents 

must conform to local codes having jurisdiction. In the ab-

sence  of  local  codes,  the  NFGC  serves  as  the  defining 

document.
Use self-drilling sheet metal screws or a mechanical fas-

tener to firmly secure the vent pipe to the round collar of 

the flue transition. If self-drilling screws are used to attach 

the vent pipe, it is recommended that three be used. Drive 

one self-drilling screw through the front and one through 

each side of the vent pipe and collar. See figure 22.
Install the first vent connector elbow at a minimum of six 

inches (152 mm) from the furnace vent outlet. See figure 

22.

Venting Using a Masonry Chimney

The following additional requirements apply when a lined 

masonry chimney is used to vent this furnace. Masonry 

chimneys used to vent Category I central furnaces must 

be either tile-lined or lined with a listed metal lining sys-

tem or dedicated gas vent. Unlined masonry chimneys are 

prohibited. See figures 23 and 24 for common venting.

A chimney with one or more sides exposed to the outside 

of the structure is considered to be an exterior chimney. 

An exterior masonry chimney that is not tile-lined must be 

lined with B1 vent or a listed insulated flexible metal vent. 

An exterior tile-lined chimney that is sealed and capped 

may be lined with a listed uninsulated flexible metal vent. 

If the existing chimney will not accommodate a listed met-

al liner, either the chimney must be rebuilt to accommo-

date one of these liners or an alternate approved venting 

method must be found.

Insulation for the flexible vent pipe must be an encapsu

-

lated fiberglass sleeve recommended by the flexible vent 

pipe manufacturer. See figure 23.

Refer to the tables and the venting information contained 

in these instructions to properly size and install the venting 

system.

 IMPORTANT

Once the venting system is installed, attach the 

“Disconnected Vent” warning sticker to a visible area 

of the plenum near the vent pipe. See figure 22. The 

warning sticker is provided in the bag assembly. Order 

kit 66W04 for additional stickers..

Содержание EL180UHE SERIES

Страница 1: ...t service agency or the gas supplier CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves...

Страница 2: ...49 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Si...

Страница 3: ...h local building codes In the absence of lo cal codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the follow ing ad...

Страница 4: ...heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL180UHE units may be used for...

Страница 5: ...rial is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety CAUTION Do not install the furnace in a corrosive or cont...

Страница 6: ...the two spac es Each opening must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening mu...

Страница 7: ...hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 6...

Страница 8: ...le mounting leg The bolt and washer must be removed before the furnace is placed into operation After the bolt and washer have been re moved the rigid leg will not touch the blower housing RIGID LEG r...

Страница 9: ...turn Air with transition and filter Figure 8 Figure 9 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with...

Страница 10: ...for clearances to combustible materials as indicated on the unit nameplate Minimum clearances for closet or alcove installations are shown in figure 11 This furnace may be installed in either an attic...

Страница 11: ...filter is being installed as part of this system to ensure better indoor air quality the filter must be properly sized Highefficiency filters have a higher static pressure drop than standardefficiency...

Страница 12: ...4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models Figure 15 shows the combustion air inducer as shipped from the fac tory Mounting Screws Location...

Страница 13: ...arbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Re install pressure switch on the other side of orifice plate and r...

Страница 14: ...ing document Use self drilling sheet metal screws or a mechanical fas tener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the ven...

Страница 15: ...fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met The chimney is currently serving at least one drafthood equipped appliance The ve...

Страница 16: ...ing to approved engineering methods 5 Multiple appliance vents The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent...

Страница 17: ...equivalent insulation qualities 14 All venting pipe passing through floors walls and ceilings must be installed with the listed clearance to combustible materials and be fire stopped according to loca...

Страница 18: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 5...

Страница 19: ...23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 25...

Страница 20: ...ection CAUTION If a flexible gas connector is required or allowed by the authority that has jurisdiction black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet The...

Страница 21: ...985 27 89 873 24 72 791 22 39 728 20 61 677 19 17 635 17 98 600 17 00 2 50 8 2 067 52 502 4020 113 83 2760 78 15 2220 62 86 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1160 32 8...

Страница 22: ...e 27 Electrical WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the un...

Страница 23: ...operly grounded in accordance with national and local codes Accessory Terminals One line voltage EAC 1 4 spade terminal is provided on the furnace integrated control See figure 30 for integrated contr...

Страница 24: ...on or appro priate dual fuel thermostat instructions Indoor Blower Speeds 1 When the thermostat is set to FAN ON the indoor blower will run continuously on the fan speed when there is no cooling or he...

Страница 25: ...to activation of combustion air inducer 12 Flame Sensed without gas valve energized 13 Low Line Voltage Note 1 Notes Note A Heartbeat is indicated by a Slow Flash 1 sec on 1 sec off repeating Note Las...

Страница 26: ...l electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move...

Страница 27: ...ve temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve...

Страница 28: ...ricifice Kit Natuarl Gas Orifice Kit 045 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 070 No Change 80W52 80W51 73W37 11K49 73W81 73W81 110 80W52 80W51 090 8...

Страница 29: ...gas line pressure After one hour of continuous thermostat demand for heat the Watchguard will re set and remake thermostat demand to the furnace and automatically reset the integrat ed control to begi...

Страница 30: ...erating range Thermal Limits should be checked by restricting airflow and not disconnecting the indoor blower For additional details please see Service and Application Note H049 2 Verify that system t...

Страница 31: ...Page 31 EL180UHE BURNER ASSEMBLY REMOVAL Manifold And Gas Valve Retention Rings Cross Over Ignitor Sensor Rollout Switches Burner Detail Front View Figure 33...

Страница 32: ...service agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel...

Страница 33: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Страница 34: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Отзывы: