11 - 

 

Are flame rollout switches tripped? If flame rollout 

switches are tripped, call the service technician for 

inspection.

Heating Sequence Of Operation
(follow steps below or see Figure 29 for more detail)

1 - 

 When

 thermostat calls for heat, combustion air 

blower starts.

2 -   

Combustion air pressure switch proves blower 

operation. Switch is factory-set and requires no 

adjustment.

3 -   After a 15-second prepurge, the hot surface ignitor 

energizes.

4 -   After a 20-second ignitor warm-up period, the gas 

valve solenoid opens. A 4-second trial for ignition 

period begins.

5 - 

 Gas is ignited, flame sensor proves the flame, and 

the combustion process continues.

6 - 

 If  flame  is  not  detected  after  first  ignition  trial, 

the ignition control will repeat steps 3 and 4 four 

more times before locking out the gas valve 

(“WATCHGUARD” flame failure mode). The ignition 

control will then automatically repeat steps 1 

through 6 after 60 minutes.

7 -   To interrupt the 60-minute “WATCHGUARD” period  

move thermostat from “Heat” to “OFF” then back to 

“Heat.” Heating sequence then restarts at step 1. 

Gas Pressure Adjustment

Gas Flow (Approximate)

TABLE 8

GAS METER CLOCKING CHART

EL180UHE 

Unit

Seconds For One Revolution

Natuarl

LP/Propane

1 cu ft 

Dial

2 cu ft 

Dial

1 cu ft 

Dial

2 cu ft 

Dial

-045

80

160

200

400

-070

55

110

136

272

-090

41

82

102

204

-110

33

66

82

164

-135

27

54

68

136

Natural-1000 btu/cu ft  LP-2500 btu/cu ft

Furnace should operate at least 5 minutes before check-

ing gas flow. Determine time in seconds for two revolu

-

tions of gas through the meter. (Two revolutions assures a 

more accurate time.) 

Divide by two 

and compare to time 

in table 8. If manifold pressure matches table 10 and rate 

is incorrect, check gas orifices for proper size and restric

-

tion. Remove temporary gas meter if installed.

NOTE -

 To obtain accurate reading, shut off all other gas 

appliances connected to meter.

Supply Pressure Measurement

A threaded plug on the inlet side of the gas valve provides 

access to the supply pressure tap. Remove the thread-

ed plug, install a field-provided barbed fitting and connect 

a manometer to measure supply pressure. See table 10 

for proper line pressure. Replace the threaded plug after 

measurements have been taken.

Manifold Pressure Measurement

1 -   Remove the threaded plug from the outlet side of 

the  gas  valve  and  install  a  field-provided  barbed 

fitting. Connect to a manometer to measure manifold 

pressure.

2 -   Start unit and allow 5 minutes for unit to reach 

steady state.

3 - 

  While waiting for the unit to stabilize, observe the 

flame. Flame should be stable and should not lift 

from burner. Natural gas should burn blue.

4 - 

 After allowing unit to stabilize for 5 minutes, record 

manifold pressure and compare to value given in 

table 10.

5 -   Shut unit off and remove manometer as soon as an 

accurate reading has been obtained. Take care to 

replace pressure tap plug.

6 -   Start unit and perform leak check. Seal leaks if 

found.

Proper Cumbustion

Furnace should operate a minimum 15 minutes with cor-

rect manifold pressure and gas flow rate before checking 

combustion. Take combustion sample beyond the flue out

-

let and compare to the tables below. 

The maximum car-

bon monoxide reading should not exceed 100 ppm.

TABLE 9

EL180UHE Unit

CO2% Nat

CO2% LP

-045

7.2 - 7.8

7.5 - 9.0

-070
-090
-110
-135

High Altitude

The manifold pressure may require adjustment and com-

bustion air pressure switch may need replacing to ensure 

proper combustion at higher altitudes. Refer to table 10 

for manifold pressure and table 11 for pressure switch 

change and gas conversion kits.

 WARNING

For safety, shut unit off and remove manometer as 

soon as an accurate reading has been obtained. Take 

care to replace pressure tap plug.

Содержание EL180UHE SERIES

Страница 1: ...t service agency or the gas supplier CAUTION As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves...

Страница 2: ...49 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Si...

Страница 3: ...h local building codes In the absence of lo cal codes units must be installed according to the current National Fuel Gas Code ANSI Z223 1 The National Fuel Gas Code is available from the follow ing ad...

Страница 4: ...heater during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit EL180UHE units may be used for...

Страница 5: ...rial is not the complete and official position of the ANSI on the referenced subject which is represented only by the standard in its entirety CAUTION Do not install the furnace in a corrosive or cont...

Страница 6: ...the two spac es Each opening must have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening mu...

Страница 7: ...hour of the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 6...

Страница 8: ...le mounting leg The bolt and washer must be removed before the furnace is placed into operation After the bolt and washer have been re moved the rigid leg will not touch the blower housing RIGID LEG r...

Страница 9: ...turn Air with transition and filter Figure 8 Figure 9 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits are not for use with...

Страница 10: ...for clearances to combustible materials as indicated on the unit nameplate Minimum clearances for closet or alcove installations are shown in figure 11 This furnace may be installed in either an attic...

Страница 11: ...filter is being installed as part of this system to ensure better indoor air quality the filter must be properly sized Highefficiency filters have a higher static pressure drop than standardefficiency...

Страница 12: ...4 inch diameter flue transition is factory installed on the combustion air inducer outlet of all models Figure 15 shows the combustion air inducer as shipped from the fac tory Mounting Screws Location...

Страница 13: ...arbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to free pressure switch wires Re install pressure switch on the other side of orifice plate and r...

Страница 14: ...ing document Use self drilling sheet metal screws or a mechanical fas tener to firmly secure the vent pipe to the round collar of the flue transition If self drilling screws are used to attach the ven...

Страница 15: ...fan assisted furnace may be commonly vented into an existing lined masonry chimney if the following conditions are met The chimney is currently serving at least one drafthood equipped appliance The ve...

Страница 16: ...ing to approved engineering methods 5 Multiple appliance vents The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent...

Страница 17: ...equivalent insulation qualities 14 All venting pipe passing through floors walls and ceilings must be installed with the listed clearance to combustible materials and be fire stopped according to loca...

Страница 18: ...22 339 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 20 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 5 21 71 29 143 38 242 47 367 10 28 64 38 133 5...

Страница 19: ...23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 20 1 21 54 33 99 46 157 62 246 2 2 57 34 105 48 167 64 25...

Страница 20: ...ection CAUTION If a flexible gas connector is required or allowed by the authority that has jurisdiction black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet The...

Страница 21: ...985 27 89 873 24 72 791 22 39 728 20 61 677 19 17 635 17 98 600 17 00 2 50 8 2 067 52 502 4020 113 83 2760 78 15 2220 62 86 1900 53 80 1680 47 57 1520 43 04 1400 39 64 1300 36 81 1220 34 55 1160 32 8...

Страница 22: ...e 27 Electrical WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to protect the un...

Страница 23: ...operly grounded in accordance with national and local codes Accessory Terminals One line voltage EAC 1 4 spade terminal is provided on the furnace integrated control See figure 30 for integrated contr...

Страница 24: ...on or appro priate dual fuel thermostat instructions Indoor Blower Speeds 1 When the thermostat is set to FAN ON the indoor blower will run continuously on the fan speed when there is no cooling or he...

Страница 25: ...to activation of combustion air inducer 12 Flame Sensed without gas valve energized 13 Low Line Voltage Note 1 Notes Note A Heartbeat is indicated by a Slow Flash 1 sec on 1 sec off repeating Note Las...

Страница 26: ...l electrical power to the unit 4 This furnace is equipped with an ignition device which automatically lights the burners Do not try to light the burners by hand 5 Remove the upper access panel 6 Move...

Страница 27: ...ve temporary gas meter if installed NOTE To obtain accurate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve...

Страница 28: ...ricifice Kit Natuarl Gas Orifice Kit 045 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 070 No Change 80W52 80W51 73W37 11K49 73W81 73W81 110 80W52 80W51 090 8...

Страница 29: ...gas line pressure After one hour of continuous thermostat demand for heat the Watchguard will re set and remake thermostat demand to the furnace and automatically reset the integrat ed control to begi...

Страница 30: ...erating range Thermal Limits should be checked by restricting airflow and not disconnecting the indoor blower For additional details please see Service and Application Note H049 2 Verify that system t...

Страница 31: ...Page 31 EL180UHE BURNER ASSEMBLY REMOVAL Manifold And Gas Valve Retention Rings Cross Over Ignitor Sensor Rollout Switches Burner Detail Front View Figure 33...

Страница 32: ...service agency or gas supplier Cabinet Parts Upper access panel Blower panel Top cap Control Panel Parts Transformer Integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel...

Страница 33: ...sted Supply Line Pressure W C ________ 1 VENT EXHAUST PIPE Secure to Unit Elbows Secured to Pipe Vent Pipe Supported 2 Roof Flashing water tight 3 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated if neces...

Страница 34: ...___ 5 COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ 4 5 6 7 DRAIN LINE Leak Free THERMOSTAT Adjusted and Programmed Opera...

Отзывы: