eNeRGy-IOM-2020.12-EN
•
50
•
Product range
Unit
Description
Model
Capacity
E14-E19
Standard
PCH 80
16-82 Kw
High
PCH 105
18-100 Kw
E22-E27
Standard
PCH 105
18-100 Kw
High
PCH 210
18-200 Kw
MODEL
PCH080
PCH105
PCH210
min
max
min
max
min
max
Chimney loss -burner ON (hi)
%
0,3
2,4
2,8
2,8
Chimney loss -burner OFF (hi)
%
<0,1
<0,1
<0,1
Max.Condensation produced (1)
l/h
3,3
2,7
5,4
Carbon monoxide CO (0% diO2) (2)
ppm
2
0
0
2
0
2
Nitrogen oxides-Nox -(0% diO2) (3)
mg/kWh
34
45
45
Available flue pressure
Pa
120
120
120
Power supply
V
230Vac -50Hz
Power absorbed
W
40
123
20
130
40
260
Size air inlet/exhaust pipes
mm
80/80
Maximum applicable pressure
Pa
1200
(1) Max. Condensation produced value obtained by test at 30% Nominal load (Qn)
(2) Value reference with gas cat. H (G20)
(3) Value (statistical medium calculation) EN1020 reference gas cat. H (G20)
GAS BURNER
GAS BURNER
Содержание E014AH055FM2M
Страница 2: ......