Main Switch Connection
The details of the electrical connection are explained in the table below, depending on the main switch type (main switch type is
given in the electrical file delivered with the unit):
Type
(QG1)
Reference
(QG1)
Bar or Terminal
Copper or Aluminum
(mm)
Torque
(Nm)
Cable max
(mm2) (OPTION)
INS 125
28910
l: 15
L: ≤ 21
d: ≤ 10
Ø
:
≥
6.2
e: ≤ 2 à 6.4
14 for cable
8 for bar or Terminal
95 (copper)
INS 160
28912
INS 250
31106
l: d+10
L: ≤ 25
d: ≤ 10
Ø
:
≥ 10
e: ≤ 6
15
185 (aluminum)
INS 400
31110
l: d+10
L: ≤ 32
d: ≤ 15
Ø
:
≥ 103
3 ≤ e ≤ 10
50
300 (aluminum)
INS 630
31114
Customer power cable inlet & BUS inlet
One specific plate is located at the bottom of the electrical cabinet
for the power cable inlet. This bottom plate should be cut and
adapted to cable diameter. It’s important to use a cable-seal to
ensure the tightness of the electrical cabinet. To facilitate this
operation this plate is removable; it’s important to put it back in
its initial position.
For the BUS connection, a lateral plate is available on the side of
the electrical cabinet. It’s important to use the cable-seal
delivered on this plate