Page 8

CAUTION

Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.

WARNING

Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil
mixture. Check the high and low
pressures before applying heat.

BRAZE LINE SET

Cloths must remain water-saturated throughout the brazing and
cool-down process.

6

After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both
services valves to cool piping. Once piping is cool, remove all water-saturated cloths.

PREPARATION FOR NEXT STEP

7

WRAP SERVICE VALVES

To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
additional water-saturated cloths under the valve body to protect the base paint.

4

FLOW NITROGEN

Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration
gauge set into the valve stem port connection on the liquid service
valve and out of the suction / vapor valve stem port. See steps 

3A, 3B

and 

3C

 on previous page and below for manifold gauge setup.

5

SUCTION / VAPOR LINE

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

LIQUID LINE

WATER-SATURATED

CLOTHS

WATER-SATURATED CLOTHS

6A

6B

SUCTION / VAPOR SERVICE

PORT MUST BE OPEN AND

SERVICE PORT CORE RE­

MOVED TO ALLOW EXIT POINT

FOR NITROGEN FLOW

IMPORTANT !

Allow braze joint to cool. Apply additional
water-saturated cloths to help cool brazed
joints. Do not remove water-saturated cloths
until piping has cooled. Temperatures above
250ºF will damage valve seals.

WARNING

FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE

may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.

Do not open service valves until refrigerant lines and
indoor coil have been leak-tested and evacuated. Refer
to Installation and Service Procedures manual found on
DAVENET.

 1.

Braze liquid line to liquid line service valve.

 2.

Braze suction / vapor line to suction / vapor service valve.

IMPORTANT !

Use silver alloy brazing rods with 5%
minimum silver alloy for copper-to-copper
brazing and 45% alloy for copper-to-brass
or copper-to-steel brazing.

FIGURE 4

Содержание Dave Lennox Signature XP25

Страница 1: ...LATION INSTRUCTIONS Dave Lennox Signature Collection XP25 System HEAT PUMPS 507005 01 7 2018 PACKING LIST OUTDOOR UNIT WARRANTY CARD GROMMETS 2 BUSHING 1 RAST 6 PIN CONNECTOR 1 WARNING Improper instal...

Страница 2: ...WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUN...

Страница 3: ...nt or scratched While handling or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged UNIT DIMENSIONS INCHES MM 4 5 8 117 BASE WITH...

Страница 4: ...ressors have an internal vacuum pro tector that will unload scrolls when suction pressure goes below 20 psig A hissing sound will be heard when the compressor is running unloaded Protector will reset...

Страница 5: ...Sizes for Horizontal Runs Required Vapor Riser Size 024 180 150 60 60 7 8 5 8 036 180 150 60 60 7 8 3 4 048 180 150 60 60 7 8 7 8 060 180 150 60 60 7 8 7 8 Table 3 Liquid Line Diameter Selection Table...

Страница 6: ...the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LIN...

Страница 7: ...rvice port nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refri...

Страница 8: ...ted nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction vapor valve stem port See steps 3A 3B and 3C on p...

Страница 9: ...ASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon...

Страница 10: ...he cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Страница 11: ...and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned...

Страница 12: ...e care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the unit the control and the...

Страница 13: ...rminals PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMP...

Страница 14: ...nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any...

Страница 15: ...play and push button operations are available on the unit access panel and in the XP25 Installation and Service Procedures Corp 1252 L11 System Component Configuration Outdoor Unit All outdoor unit se...

Страница 16: ...ls to operate check the following before calling for service S Verify room thermostat settings are correct S Verify that all electrical disconnect switches are ON S Check for any blown fuses or trippe...

Отзывы: