background image

Page 17

SL18XP1 SERIES

Deep Vacuum Gauge Response and 

System Conditions

FIGURE 16

Triple Evacuation Method

The triple evacuation method should only be used when
system does not contain any water in liquid form and vacu­
um pump is only capable of pulling down to 28 inches of
mercury (711mm Hg). Refer to figure 17 and proceed as
follows:

EVACUATE

BREAK VACUUM WITH DRY NITROGEN

WAIT

BREAK VACUUM WITH DRY NITROGEN

WAIT

EVACUATE

CHECK FOR TIGHT, DRY SYSTEM (IF IT HOLDS DEEP VACUUM)

CHARGE SYSTEM

Triple Evacuation Sequence

EVACUATE

FIGURE 17

1. Pull system down to 28 inches of mercury (711mm Hg)

and allow pump to continue operating for an additional
15 minutes.

2. Close manifold valves or valve at vacuum pump and

shut off vacuum pump.

3. Connect a nitrogen cylinder and regulator to system

and fill with nitrogen until system pressure is 2 psig.

4. Close nitrogen valve and allow system to stand for one

hour. During this time, dry nitrogen will diffuse
throughout the system, absorbing moisture.

5. Repeat this procedure as indicated in figure 17.
6. After the final evacuate sequence, confirm there are

no leaks in the system. If a leak is found, repeat the en­
tire process after repair is made.

7. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20

*

minute period after shutting off the vacuum

pump and closing the manifold gauge valves.

8. Disconnect the manifold hose from the vacuum pump

and connect it to an inverted cylinder of HFC

*

410A

positioned to deliver liquid refrigerant. Open the mani­
fold gauge valve 1 to 2 psig in order to release the va­
cuum in the line set and indoor unit.

9. Perform the following:

Close manifold gauge valves.

Shut off HFC

*

410A cylinder.

Slowly open the service valves.

Refer to the charging sticker on the unit to com­
plete the outdoor unit installation.

Charging 

The SL18XP1 unit is factory-charged with enough
HFC-410A refrigerant to accommodate a 15-foot length of
refrigerant piping. Charge should be checked and adjusted
using the tables provided on the charging procedure stick­
er on the unit access panel. Detailed information is given in
the SL18XP1 Installation and Service Procedures manual,
which is available on DaveNet.

Heat Pump Control -- Defrost Operation 

A full description of the heat pump control can be found in
the detailed installation and service procedure manual
available on DaveNet. The defrost termination pins (E47)
must be set on the heat pump control prior to starting the
system to ensure proper defrost operation.

The heat pump control (A175) measures differential tem­
peratures to detect when the system is performing poorly
because of frost build-up on the outdoor coil. The heat
pump control self-calibrates when the defrost system
starts and after each system defrost cycle. The heat pump
control monitors ambient temperature, outdoor coil tem­
perature, and total run-time to determine when a defrost
cycle is required. The coil temperature sensor is designed
with a spring clip to allow mounting to the outside coil tub­
ing. The location of the coil sensor is important for proper
defrost operation.

NOTE -

 The heat pump control accurately measures the

performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the heat pump control initiates de­
frost cycles.

Содержание Dave Lennox Signature XC17

Страница 1: ...rsonal inju ry or loss of life Installation and service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or maint...

Страница 2: ...1 2 1003 35 1 2 902 18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 AND 030 41 1041 036 A...

Страница 3: ...ts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on th...

Страница 4: ...Size barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER...

Страница 5: ...rs before unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Ta...

Страница 6: ...t wires between the thermostat and the furnace air han dler control and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is use...

Страница 7: ...ault setting is OFF Note If the jumper is miss ing the default is OFF 2 Defrost Auto is set to OFF Defrost will run and terminate based on J1 setting 3 Defrost Auto is set to ON Defrost termination se...

Страница 8: ...is required for this model only when used with the ComfortSense 7000 thermostat catalog number Y0349 Resistor Kit catalog number 47W97 is required and must be ordered separately 3 Air handler control...

Страница 9: ...alog number 47W97 is required and must be ordered separately 3 Cut on board link W951 clippable wire from R O HEAT PUMP for heat pump applications 4 Cut on board link clippable wire DS R for Humiditro...

Страница 10: ...s are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem perfo...

Страница 11: ...e care not to twist or damage distributor tubes during this pro cess 4 Remove and discard fixed orifice valve stem assembly if present and Teflon washer as illustrated above 5 Use a field provided fit...

Страница 12: ...ogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines sq...

Страница 13: ...ditionalwater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connect...

Страница 14: ...VALVE KITS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY B INSTALL ONE OF THE PROVIDED TEFLO...

Страница 15: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Страница 16: ...OW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not al ready done FIGURE 15 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a factory...

Страница 17: ...gauge valve 1 to 2 psig in order to release the va cuum in the line set and indoor unit 9 Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Slowly open the service valves Re...

Страница 18: ...iary drain if installed Check the area around the outdoor unit monthly and re move any obstructions that may restrict airflow to the outdoor unit This would include grass clippings leaves or papers th...

Страница 19: ...eplace air filters in indoor unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks o...

Страница 20: ...tes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps COOLING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Am...

Отзывы: