STEP 6 -- INSTALLING INDOOR EXPANSION VALVE 

 A.

ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.

NOTE

 -

 CONFIRM PROPER THERMAL CONTACT BETWEEN

VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU­
LATING THE SENSING BULB ONCE INSTALLED.

 B.

CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE VAPOR LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS­
TRATED BELOW.

THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
WHICH PROVIDES ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR
FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE THE

 LENNOX SL18XP1

PRODUCT SPECIFICATION BULLETIN (EHB)

 FOR APPROVED EXPANSION VALVE KITS AND APPLICATION INFORMATION.

 A.

REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON­
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR ASSEM­
BLY.

 B.

INSTALL ONE OF THE PROVIDED TEFLON

®

 RINGS AROUND THE

STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE THE
CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON

®

 RING

WITH REFRIGERANT OIL.

 C.

ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATE­
LY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS
ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.

 D.

PLACE THE REMAINING TEFLON

®

 WASHER AROUND THE OTHER END

OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON

®

 RING WITH REFRIG­

ERANT OIL.

 E.

ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN­
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.

VAPOR LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 TURN

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.

ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.

12

BULB

VAPOR LINE

NOTE - NEVER MOUNT

THE SENSING BULB ON

BOTTOM OF LINE.

BULB

BULB

BULB

9 O'CLOCK TO

3 O'CLOCK

1

2

3

4

5

6

7

8

9

10

11

12

1/8 TURN

FIGURE 13

Содержание Dave Lennox Signature XC17

Страница 1: ...rsonal inju ry or loss of life Installation and service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or maint...

Страница 2: ...1 2 1003 35 1 2 902 18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 AND 030 41 1041 036 A...

Страница 3: ...ts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on th...

Страница 4: ...Size barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER...

Страница 5: ...rs before unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Ta...

Страница 6: ...t wires between the thermostat and the furnace air han dler control and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is use...

Страница 7: ...ault setting is OFF Note If the jumper is miss ing the default is OFF 2 Defrost Auto is set to OFF Defrost will run and terminate based on J1 setting 3 Defrost Auto is set to ON Defrost termination se...

Страница 8: ...is required for this model only when used with the ComfortSense 7000 thermostat catalog number Y0349 Resistor Kit catalog number 47W97 is required and must be ordered separately 3 Air handler control...

Страница 9: ...alog number 47W97 is required and must be ordered separately 3 Cut on board link W951 clippable wire from R O HEAT PUMP for heat pump applications 4 Cut on board link clippable wire DS R for Humiditro...

Страница 10: ...s are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem perfo...

Страница 11: ...e care not to twist or damage distributor tubes during this pro cess 4 Remove and discard fixed orifice valve stem assembly if present and Teflon washer as illustrated above 5 Use a field provided fit...

Страница 12: ...ogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines sq...

Страница 13: ...ditionalwater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connect...

Страница 14: ...VALVE KITS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR ASSEM BLY B INSTALL ONE OF THE PROVIDED TEFLO...

Страница 15: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Страница 16: ...OW NITROGEN CONNECT GAUGE SET A B C D LINE SET AND INDOOR COIL NOTE Remove cores from service valves if not al ready done FIGURE 15 EVACUATE LINE SET AND INDOOR COIL The unit is shipped with a factory...

Страница 17: ...gauge valve 1 to 2 psig in order to release the va cuum in the line set and indoor unit 9 Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Slowly open the service valves Re...

Страница 18: ...iary drain if installed Check the area around the outdoor unit monthly and re move any obstructions that may restrict airflow to the outdoor unit This would include grass clippings leaves or papers th...

Страница 19: ...eplace air filters in indoor unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks o...

Страница 20: ...tes START UP CHECKS Refrigerant Type Rated Load Amps Actual Amps Rated Volts Actual Volts Condenser Fan Full Load Amps Actual Amps COOLING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Am...