Lennox COWB3 Скачать руководство пользователя страница 7

7

Provide adequate supply of combustion air in accordance 

with requirements of authority having jurisdiction. In ab-

sence of such requirements

• United States. NFPA 31: Installation of Oil Burning 

Equipment

• Canada. CSA B139: Installation of Oil Burning 

Equipment

EXAMPLE 1: Boiler Located in Unconfined Space

If your boiler is in an open area (un-partitioned basement) 

in conventional house, air that leaks through cracks around 

doors and windows will usually be adequate to provide air 

for combustion. Doors should not fit tightly. Do not caulk 

cracks around windows.

An unconfined space is defined as space whose volume is 

not less than 50 cubic feet per 1,000 Btu per hour of total 

input rating of all appliances installed in that space.

EXAMPLE 2: Boiler Located in Confined Space

A. 

   

All Air from Inside the Building:

 Confined space 

shall be provided with two permanent openings communi-

cating directly with additional room(s) of sufficient volume 

so the combined volume of all spaces meets the criteria for 

unconfined space. Total input of all combustion equipment 

installed in combined space shall be considered in mak-

ing this determination. Each opening shall have minimum 

free area of one square inch per 1,000 Btu per hour of total 

input rating of all combustion equipment in the confined 

space, but not less than 100 square inches. One opening 

shall be within 12 inches of top and one within 12 inches of 

bottom of the enclosure.

Example: Your boiler is rated at 100,000 Btu per hour. Wa

-

ter heater is rated at 30,000 Btu per hour. Total is 130,000 

Btu per hour. You need two grilles, each with 130 square 

inches of FREE opening. Metal grilles have about 60% FREE 

opening. To find louvered area needed, multiply free open

-

ing required by 1.7 (130 x 1.7 = 221.0 sq. in. louvered 

area). In this example, two grilles each having 8” x 30” 

(240 sq. in.) louvered area would be used.

FRESH AIR FOR COMBUSTION

 WARNING

Asphyxiation, fire hazard. Do not obstruct air 

openings to combustion area. Follow instructions 

below, to maintain adequate combustion air.

!

  

NOTICE

Install outside air intake if you use fireplace or 

kitchen or bathroom exhaust fan. These devices rob 

boiler and water heater of combustion air.

Figure 4 - Air Openings For Boiler Located In 

Confined Space (Utility Room

)

Содержание COWB3

Страница 1: ...alteration service or maintenance could result in death or serious injury Refer to this manual for assistance For additional information consult a qualified installer service agency or the oil suppli...

Страница 2: ...or moderate injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury DANGER Indicates a hazardous situation which if not avoided WILL result in death...

Страница 3: ...3 5 8 X 8 X 15 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the D...

Страница 4: ...will automatically lift open Lifting of the safety relief valve can discharge large quantities of steam and hot water which may damage the surroundings Before installing the safety relief valve read t...

Страница 5: ...assage is required for access to another side for cleaning servicing inspection or replacement of any parts that may normally require attention Install boilers at least 6 from combustible material on...

Страница 6: ...IRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL...

Страница 7: ...input of all combustion equipment installed in combined space shall be considered in mak ing this determination Each opening shall have minimum free area of one square inch per 1 000 Btu per hour of...

Страница 8: ...the enclosure 3 When communicating with outdoors through hori zontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in...

Страница 9: ...discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible to location protecting...

Страница 10: ...SYSTEMS LARGE WATER CONTENT SYSTEMS PIPING ARRANGED FOR POWER PURGING AIR OUT OF THE SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 7 Bypas...

Страница 11: ...YFROM EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLEDON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUTOFSYSTEMPIPING REFERTOTHISMANUAL S SECTIONON FILLINGTHESYSTEMWITHWATER OPTION 1 Figure 8...

Страница 12: ...PS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYS TEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Ar...

Страница 13: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Fig...

Страница 14: ...s are used Tankless coils are meant to provide domestic hot water for intermittent draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposi...

Страница 15: ...mption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section Total Volume Gallon...

Страница 16: ...IMNEY SIZES FIRING RATE gph CHIMNEY HEIGHT ft NOMINAL CHIMNEY ROUND LINER INSIDE SQUARE LINER INSIDE 0 60 1 30 15 8 x 8 6 6 x 6 1 31 1 80 15 8 x 8 7 6 x 6 1 81 1 75 20 8 x 8 8 6 x 6 For elevations abo...

Страница 17: ...17 TYPICAL CHIMNEY CONNECTION Figure 12 Typical Chimney Connection...

Страница 18: ...volt electrical supply to L1 and L2 terminals on limit and two thermostat wires to T and T terminals on same limit See wiring diagram page 28 Run separate circuit from separate over current protection...

Страница 19: ...ging drain valve runs air free close isolation valve or zone valve Re peat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain...

Страница 20: ...desired over fire draft Start Fill entire system with water Vent all air from sys tem following section for Filling The Boiler Fuel Units And Oil Lines Install oil line s to oil burner Recommend using...

Страница 21: ...race measure CO2 and as insurance margin increase air to sufficiently reduce CO2 by to 1 If clean fire cannot be obtained it is necessary to verify burner head and electrode alignment Proper electrode...

Страница 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...

Страница 23: ...full of vapor or when the combustion chamber is very hot Check Thermostat Operation Follow instructions included with your thermostat Locate thermostat five feet above the floor on inside wall Locate...

Страница 24: ...ent that may lodge on valve seat Permit valve to snap shut Refer to valve manufacturer s instructions packaged for more details Conventional Expansion Tank Tank may become water logged or may receive...

Страница 25: ...by cutting end of flue brush off and inserting it into drill When brushing take care to not damage target wall with flue brush 6 Carefully vacuum soot accumulations from combus tion chamber area take...

Страница 26: ...assembly make sure head location and size if applicable are per manufacturer s recom mendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 I...

Страница 27: ...tors not heating Open radiator vents to excess air Check flow control valve if used It may be in closed position Circulating pump not running Check over current protection Check relay operation Poor e...

Страница 28: ...8 ELECTRICAL WIRING Figure 16 Boiler Honeywell L7248L Control When Low Limit Is Used Set ELL Parameter On L7248 Honeywell Control To On Boilers Factory Equipped With Tankless Coil Are Factory Set To O...

Страница 29: ...7 Honeywell L7248L Control With Reillo F5 F10 Burner ELECTRICAL WIRING When Low Limit Is Used Set ELL Parameter On L7248 Honeywell Control To On Boilers Factory Equipped With Tankless Coil Are Factory...

Страница 30: ...30 ELECTRICAL WIRING Figure 18 Honeywell L7248L Control Wiring with Zone Pumps and Argo ARM Switching Relay With Tankless coil Shown...

Страница 31: ...burner fan motor to pre purge combustion chamber and oil pump to bring supply oil pressure up to its set point helping to provide clean light off LIMIT CONTROL provided Refer to manufacturer instructi...

Страница 32: ...PRODUCT LITERATURE Lennox Industries Inc Dallas Texas...

Отзывы: