Oil Boiler Cleaning:

1. 

Shut off all electrical power to boiler / burner and shut 

off fuel oil supply.

2. 

Remove vent pipe from top of boiler. Inspect pipe and 

chimney for signs of corrosion and deterioration. Clean 

out base of chimney. If vent pipe shows any signs of 

corrosion or deterioration, replace it immediately. If 

chimney damage or deterioration is discovered, contact 

a service technician.

3. 

Remove top jacket panel screws (5), brass wing nuts 

(2) holding flue collector top, and flue collector top. In

-

spect gasket on underside of flue collector and replace 

as necessary. 

4. 

Before beginning to clean flue passageways, insure 

combustion chamber blanket is covered. If blanket is 

not covered prior to cleaning, replace blanket once 

cleaning is completed.

5. 

With access to flue passageways, remove soot from 

fireside surfaces by brushing diagonally through flue 

passages (see drawing below). Brushing can be made 

easier by cutting end of flue brush off and inserting 

it into drill. When brushing, take care to not damage 

target wall with flue brush.

6. 

Carefully vacuum soot accumulations from combus-

tion chamber area, take care to not damage any of 

refractory or blanket insulation. To gain access to 

combustion chamber first check that shut off valve 

on fuel oil line is closed and disconnect fuel oil line. 

Open swing door by removing whiz lock nut holding 

door shut.

7. 

Inspect target wall, fire door refractory, and com

-

bustion chamber blanket (when included) for crack-

ing and deterioration. If there are signs of crack-

ing or deterioration, replace refractory or blanket 

before reassembling burner / front plate.

8. 

Inspect door’s braided gasket for wear and dam-

age. Replace when necessary with braided gasket 

of same material and size. 

9. 

Inspect and clean oil burner.

OIL BOILER / BURNER CLEANING INSTRUCTIONS 

NOTICE

Important operating and maintenance require-

ments:
•  Keep your boiler and the area around it clean 
•  Never burn refuse or any material other than 

specified fuel in your boiler

Figure 14 - 

Brush Diagonally Through Flue 

Passages

Содержание COWB3

Страница 1: ...alteration service or maintenance could result in death or serious injury Refer to this manual for assistance For additional information consult a qualified installer service agency or the oil suppli...

Страница 2: ...or moderate injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury DANGER Indicates a hazardous situation which if not avoided WILL result in death...

Страница 3: ...3 5 8 X 8 X 15 21 6 11 Mbh 1 000 BTU per hour BTU British Thermal Unit Heating Capacity based on 13 CO2 with a 0 02 w c draft over fire and a 1 smoke or less Testing was done in accordance with the D...

Страница 4: ...will automatically lift open Lifting of the safety relief valve can discharge large quantities of steam and hot water which may damage the surroundings Before installing the safety relief valve read t...

Страница 5: ...assage is required for access to another side for cleaning servicing inspection or replacement of any parts that may normally require attention Install boilers at least 6 from combustible material on...

Страница 6: ...IRCULATING PUMP IN RETURN LINE OR AFTER THE EXPANSION TANK SHUT OFF VALVE OIL FILTER OIL LINES FOUNDATIONS TO OUTSIDE LINES TO OTHER APPLIANCES SERVICE LINE OVERCURRENT PROTECTED SAFETY SWITCH 2 FILL...

Страница 7: ...input of all combustion equipment installed in combined space shall be considered in mak ing this determination Each opening shall have minimum free area of one square inch per 1 000 Btu per hour of...

Страница 8: ...the enclosure 3 When communicating with outdoors through hori zontal ducts each opening shall have minimum free area of one square inch per 2 000 Btu per hour of total input rating of all equipment in...

Страница 9: ...discharge piping to avoid reducing safety relief valve relieving capacity below minimum relief valve capacity stated on rating plate Run pipe as short and straight as possible to location protecting...

Страница 10: ...SYSTEMS LARGE WATER CONTENT SYSTEMS PIPING ARRANGED FOR POWER PURGING AIR OUT OF THE SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYSTEM WITH WATER OPTION 1 SYSTEM PIPING Figure 7 Bypas...

Страница 11: ...YFROM EXPANSION TANK NOTE CIRCULATORCANALSOBEINSTALLEDON RETURN PIPING PIPING ARRANGED FOR POWER PURGING AIR OUTOFSYSTEMPIPING REFERTOTHISMANUAL S SECTIONON FILLINGTHESYSTEMWITHWATER OPTION 1 Figure 8...

Страница 12: ...PS AWAY FROM EXPANSION TANK PIPING ARRANGED FOR POWER PURGING AIR OUT OF SYSTEM PIPING REFER TO THIS MANUAL S SECTION ON FILLING THE SYS TEM WITH WATER OPTION 1 SYSTEM PIPING Figure 9 System Piping Ar...

Страница 13: ...ON SUPPLY PIPING PUMPS AWAY FROM EXPANSION TANK PER THIS MANUAL USE OPTION 2 IN FILLING THE SYSTEM WITH WATER THIS PIPING ARRANGEMENT CAN BE USED WITH ZONE VALVES OR ZONE CIRCULATORS SYSTEM PIPING Fig...

Страница 14: ...s are used Tankless coils are meant to provide domestic hot water for intermittent draws not continuous flow NOTICE Do not use tankless coil if your water is excessively hard with lime or other deposi...

Страница 15: ...mption Tankless coil performance will fall as concentration of antifreeze is increased Refer to boiler and piping water volumes tables BOILER WATER VOLUMES Number of Boiler Section Total Volume Gallon...

Страница 16: ...IMNEY SIZES FIRING RATE gph CHIMNEY HEIGHT ft NOMINAL CHIMNEY ROUND LINER INSIDE SQUARE LINER INSIDE 0 60 1 30 15 8 x 8 6 6 x 6 1 31 1 80 15 8 x 8 7 6 x 6 1 81 1 75 20 8 x 8 8 6 x 6 For elevations abo...

Страница 17: ...17 TYPICAL CHIMNEY CONNECTION Figure 12 Typical Chimney Connection...

Страница 18: ...volt electrical supply to L1 and L2 terminals on limit and two thermostat wires to T and T terminals on same limit See wiring diagram page 28 Run separate circuit from separate over current protection...

Страница 19: ...ging drain valve runs air free close isolation valve or zone valve Re peat this procedure for remaining heating zones D Once all zones are filled with water and purged of air close power purging drain...

Страница 20: ...desired over fire draft Start Fill entire system with water Vent all air from sys tem following section for Filling The Boiler Fuel Units And Oil Lines Install oil line s to oil burner Recommend using...

Страница 21: ...race measure CO2 and as insurance margin increase air to sufficiently reduce CO2 by to 1 If clean fire cannot be obtained it is necessary to verify burner head and electrode alignment Proper electrode...

Страница 22: ...22 OPERATING THE BOILER Figure 13 Burner Adjustments and Settings...

Страница 23: ...full of vapor or when the combustion chamber is very hot Check Thermostat Operation Follow instructions included with your thermostat Locate thermostat five feet above the floor on inside wall Locate...

Страница 24: ...ent that may lodge on valve seat Permit valve to snap shut Refer to valve manufacturer s instructions packaged for more details Conventional Expansion Tank Tank may become water logged or may receive...

Страница 25: ...by cutting end of flue brush off and inserting it into drill When brushing take care to not damage target wall with flue brush 6 Carefully vacuum soot accumulations from combus tion chamber area take...

Страница 26: ...assembly make sure head location and size if applicable are per manufacturer s recom mendations If burner being used has damaged head replace head with same head recommended for use on this boiler 6 I...

Страница 27: ...tors not heating Open radiator vents to excess air Check flow control valve if used It may be in closed position Circulating pump not running Check over current protection Check relay operation Poor e...

Страница 28: ...8 ELECTRICAL WIRING Figure 16 Boiler Honeywell L7248L Control When Low Limit Is Used Set ELL Parameter On L7248 Honeywell Control To On Boilers Factory Equipped With Tankless Coil Are Factory Set To O...

Страница 29: ...7 Honeywell L7248L Control With Reillo F5 F10 Burner ELECTRICAL WIRING When Low Limit Is Used Set ELL Parameter On L7248 Honeywell Control To On Boilers Factory Equipped With Tankless Coil Are Factory...

Страница 30: ...30 ELECTRICAL WIRING Figure 18 Honeywell L7248L Control Wiring with Zone Pumps and Argo ARM Switching Relay With Tankless coil Shown...

Страница 31: ...burner fan motor to pre purge combustion chamber and oil pump to bring supply oil pressure up to its set point helping to provide clean light off LIMIT CONTROL provided Refer to manufacturer instructi...

Страница 32: ...PRODUCT LITERATURE Lennox Industries Inc Dallas Texas...

Отзывы: