DC50 COMFORT DISPLAY
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 17
CL50-CHILLER-IOM_CUST-0808-E
Function
This display is connected remotely; it is intended for users with no technical knowledge. This display gives access to general
operating data of the unit. It does not give access to detailed operating data.
It can be used to set or change the programming of the various time periods and the temperature set point for each period.
It also has the ability to set a 3 hours override and force an unoccupied mode, or any other different time periods,
for a maximum of 7 days. It displays a real time clock and the various fault signals.
Buttons
‘Prg’ Access set points
‘Up’ Access overrides or increase values
‘Clock
Access the clock
‘Enter’, Confirms the selection
‘Esc’ Return to the previous display
‘Down’ Access overrides or decrease values
Brightness/Contrast
The display has a set contrast, but this can be adjusted manually. For manual adjustment of the co
ntrast, press the ‘Prg’ and
‘Clock buttons simultaneously and press buttons
or
to increase or reduce the contrast.
Configuration of the terminal address
Sdc.1
The address of the terminal DC50 must be checked after having
switching on the card.
Access
the
configuration
mode
by
pressing
buttons
simultaneously for at least 5 seconds, until the Sdc.1
screen appears.
Press the ‘Enter’ buttonto position the cursor over the ‘Setting’ line
With button
or
set the address of the display. See table
below for the DC50, then confirm with button
pLan address
with
BM50 connected
DC50 Address
1
17 (local display)
21 (remote display)
2
18 (local display)
22 (remote display)
3
19 (local display)
23 (remote display)
4
20 (local display)
24 (remote display)