SCHEDULING – CLOCK SETTING
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 10
CL50-CHILLER-IOM_CUST-0808-E
For each time zone, the set following set points following can be modified:
LIST SET POINT BY ZONE
Code
DISPLAY
CONFORT
DISPLAY
MAINTENANCE
Change over control
Cooling / Heating priority
(3311)
Yes
Yes
Water temperature
Cooling Water T° Set point A
(3321)
Yes
Yes
Cooling Water T° Set point B
(3322)
Yes
Yes
Cooling Air Ambient T° Set point A
(3323)
Yes
Yes
Cooling Air Ambient T° Set point B
(3324)
Yes
Yes
Heating Water T° Set point A
(3331)
Yes
Yes
Heating Water T° Set point B
(3332)
Yes
Yes
Heating Air Ambient T° Set point A
(3333)
Yes
Yes
Heating Air Ambient T° Set point B
(3334)
Yes
Yes
Compressor enable
Enable compressor on circuit N°1
(3411)
Yes
Yes
Enable compressor on circuit N°2
(3412)
Yes
Yes
Fan condensing
Fan Mode Set point
(3611)
Yes
Yes
Low Noise Value Set point
(3612)
Yes
Yes
Cooling water pump(s)
Enable pump(s)
(3711)
Yes
Yes
Programming
Beginning of zone; each day
Yes
Yes
Start Uno
(3211)
Yes
Yes
Start z.A
(3212)
Yes
Yes
Start z.B
(3213)
Yes
Yes
Start z.C
(3214)
Yes
Yes
With the DS50, for each set point, press on the key `
PRG
to change the periods and to validate the good set point for the
good zone.
Note
: “Monday” is
considered as the first day of the week for programming the
CLIMATIC™50
.
Factory settings:
“Day A” activated from Monday to Saturday 6h
22h
Night mode (unoccupied) for the remaining of time, Sunday included