BMS ADDRESS TABLES
CLIMATIC™50 –
Chiller / Heat Pump
–
Customer version
Page 27
CL50-CHILLER-IOM_CUST-0808-E
ModBus, Trend, BACnet & Carel
LOGICAL DATA
@ (hexa) @ (deci) R/W Unit
Description
DS50
01H
1
R/W
0/1
[On/Off] General On/Off of the unit
[Off] Unit OFF - [On] Unit ON
3111
02H
2
R/W
0/1 [Reset] Discharges the safety measures of the unit
3113
03H
3
R/W
0/1
[BMS] BMS On/Off of the unit
[Off] Unit OFF - [On] Unit ON
3112
BMS
04H
4
R/W
0/1
not used
05H
5
R/W
0/1
[BMS] Activation of the Inoccupation mode :
[Off] Occupation mode - [On] Inoccupation mode
3925
Unoc
06H
6
R
0/1
not used
07H
7
R
0/1
not used
08H
8
R
0/1
not used
09H
9
R
0/1
not used
0AH
10
R
0/1
not used
0BH
11
R
0/1
not used
0CH
12
R
0/1
not used
0DH
13
R
0/1
not used
0EH
14
R
0/1
not used
0FH
15
R
0/1
not used
10H
16
R/W
0/1
[Clock] Read / Update the internal clock board of the BM50
[OFF] Read hour & minute - [ON] Write hour & minute
…
11H
17
R
0/1
not used
12H
18
R/W
0/1 [Dry contact] Digital Output, Free 1, BE50-J5-NO1
2151
13H
19
R/W
0/1 [Dry contact] Digital Output, Free 2, BE50-J6-NO2
2152
14H
20
R/W
0/1 [Dry contact] Digital Output, Free 3, BE50-J7-NO3
2153
15H
21
R/W
0/1 [Dry contact] Digital Output, Free 4, BE50-J8-NO4
2154
16H
22
R
0/1
not used
17H
23
R
0/1
not used
18H
24
R
0/1
not used
19H
25
R
0/1
not used
1AH
26
R
0/1
not used
1BH
27
R
0/1
not used
1CH
28
R
0/1
not used
1DH
29
R
0/1
not used
1EH
30
R
0/1
not used
1FH
31
R
0/1
not used
20H
32
R
0/1
not used
21H
33
R
0/1 [Alarm] General alarm
22H
34
R
0/1 [On/Off] Pump, 1
2615
23H
35
R
0/1 [On/Off] Pump, 2
2616
24H
36
R
0/1 [On/Off] Compressor 1, Circuit 1
2316
25H
37
R
0/1 [On/Off] Compressor 2, Circuit 1
2326