Page 19
CBX32MV
HORIZONTAL DRAIN PAN
(REMOVE FROM UNIT)
UP-LOAD /
DOWNFLOW
DRAIN PAN
Figure 6. Downflow Discharge Position
SIDE
VIEW
2” WIDE FOAM TAPE
DRIP SHIELD
1” WIDE FOAM TAPE (LONGER PIECE)
Figure 7. Applying Foam Tape to Drip Shield
COIL
DRIP SHIELD
DRIP PAN
Figure 8. Downflow Drip Shields
6.
Replace the coil assembly and blower if you have
removed it. Replace the coil access panel.
7.
Set the unit so that it is level. Using sheet metal screws,
connect the return and supply air plenums as required.
NOTE - For downflow application, metal or class I supply
and return air plenums must be used.
COMBUSTIBLE FLOOR
ADDITIVE BASE
PROPERLY SIZED
FLOOR OPENING
AIR
HANDER
UNIT
Figure 9. Combustible Flooring Additive Base
8.
For downflow installation on combustible flooring, an
additive base must be used as illustrated in figure 9 on
page 19.
9.
Cut an opening appropriately sized for combustible
base. Base dimensions are illustrated in figure 10.
After opening has been cut, set the additive base into
opening. Connect outlet air plenum to the additive
base. Set the unit on the additive base so flanges of
the unit drop into the base opening and seal against
the insulation strips. The unit is now locked in place.
Install return air plenum and secure with sheet metal
screws.
TOP VIEW
OPENING
1‐5/8 (41)
SIDE VIEW
1‐5/8 (41)
11‐3/8
(289)
2 (51)
1‐5/8 (41)
24 (610) -068 ONLY
22‐1/8 (562) OTHER MODELS
5/8 (16)
13‐3/8 (340)
SUPPLY AIR OPENING
INCHES (MM)
-018/-024 08-1/4 (464)
-024/-030 and up 23-1/4 (591)
-018/-024 15
(381)
-024/-030 AND
UP 20 (508)
Figure 10. Downflow Combustible Base Dimensions
Brazing Connections
WARNING
Polyol ester (POE) oils used with HFC-410A refrigerant
absorb moisture very quickly. It is very important that
the refrigerant system be kept closed as much as
possible. DO NOT remove line set caps or service valve
stub caps until you are ready to make connections.