background image

Page 7

Condensate Drain

 IMPORTANT

On units of this type, where the blower “draws” rather than “blows” air through the coil, traps must be installed in the 

condensate drain lines (primary and auxiliary, if used). Traps prevent the blower from drawing air through the drain lines 

into the air supply.

ABOVE

FINISHED

SPACE?

OVERFLOW DRAIN LINE

ALWAYS RUN AN OVERFLOW DRAIN LINE.  IF NOT POSSIBLE TO

ROUTE  OVERFLOW  DRAIN  LINE,  INSTALL  LOW  VOLTAGE

OVERFLOW  SWITCH  KIT. WIRE  KIT  TO  SHUT  DOWN

COMPRESSOR PER INSTRUCTIONS.

NO

YES

LENNOX #

X3169

CLEAN OUT

VENT

PRESS IN

(DO NOT GLUE)

VENT MUST EXTEND

ABOVE HEIGHT OF

COIL DRAIN PAN BY

TWO INCHES (51MM)

1” X 3/4” X 3/4”

REDUCING

TEE WITH

PLUG

LENNOX

1

 P-TRAP

49P66, J-TRAP #

91P90 OR ANY

PVC SCH 40 P- OR

J-TRAP 3/4”

OVERFLOW

DRAIN

AIR HANDLER DRAIN PAN

WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A

3/4” (19.1MM) SECONDARY DRAIN LINE MUST BE:

CONNECTED TO SECONDARY DRAIN PAN 

OR

CONNECTED TO THE OVERFLOW DRAIN OUTLET OF

THE AIR HANDLER DRAIN PAN.

TRAPS  MUST  BE  DEEP  ENOUGH  TO  OFFSET  MAXIMUM  STATIC  DIFFERENCES  —

GENERALLY, TWO INCHES (51MM).

DRAIN  LINE  SHOULD

SLOPE A MINIMUM OF

ONE  INCH  PER  10

FEET  (25MM  PER  3

METERS)

NOTE 

—  WHEN  A  AIR  HANDLER  IS  LOCATED

ABOVE  A  FINISHED  SPACE  THE  SECONDARY

DRAIN PAN MUST HAVE A LARGER FOOTPRINT

THAN THE AIR HANDLER.

MAIN

DRAIN

TO APPROVED

DRAIN

FOR  NEGATIVE  PRESSURE  COILS  (BLOWER

AFTER COIL) TRAPS ARE REQUIRED ON ALL

DRAIN LINES CONNECTED TO COIL.

COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET

AND  MALE  ADAPTER,  TWO  PART  DESIGN  FOR  USE  WHERE

OBSTRUCTIONS PREVENT DIRECT THREADING

SECONDARY

DRAIN PAN

2”

(51MM)

TRAP DEPTH

1

 LENNOX P-TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J-TRAP 91P90.

2

 PIPE NIPPLE PROVIDED IN BAG ASSEMBLY - SCH 80, 3/4” I. D. X 5” - 34K7401 (1): CUT THE PIPE IN HALF AND USE IT TO ROUTE THE  MAIN DRAIN.

MAIN

DRAIN

PROVIDED

PIPE NIPPLE

 2

CUT  TO

REQUIRED

LENGTH

SIDE VIEW

FIGURE 10

. Typical Main and Overflow Drain

 IMPORTANT

A field-fabricated secondary drain pan, with a drain pipe 

to the outside of the building, is required in all installations 

over a finished living space or in any area that may be 

damaged by overflow from the main drain pan. In some 

localities, local codes may require a secondary drain 

pan for any horizontal installation.

SLOPING THE UNIT

Make sure the unit is sloped (similar to the slope shown 

in figure 11) so that the drain pan will empty completely 

without water standing in the pan.

THIS CORNER SHOULD BE 16 MM (+/- 3 MM) HIGHER

THAN DRAIN CORNER

DRAIN CORNER

LE

VE

L P

LA

NE

FIGURE 11

. Sloping the Unit for Proper Drainage 

Содержание CBX25UH-024

Страница 1: ...Check the air handler for shipping damage if found im mediately contact the last carrier Check the unit rating plate to confirm that delivered unit matches order General Information The CBX25UH air ha...

Страница 2: ...Page 2 CBX25UH Unit Dimensions Upflow Inches mm...

Страница 3: ...e instructions can result in death explosion or fire IMPORTANT Excessive condensation may occur if the unit is installed in a warm humid place When the unit is installed in an unconditioned space appl...

Страница 4: ...n HORIZONTAL DRAIN PAN MUST BE REMOVED UP FLOW DOWN FLOW DRAIN PAN FIGURE 1 Upflow Configuration HORIZONTAL APPLICATIONS IMPORTANT When removing the coil there is a possibility of danger of equipment...

Страница 5: ...ssembly bottom drain pan and horizontal drain pan as one unit from the air handler FIGURE 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan as a Unit 4 Remove the blow off prevention br...

Страница 6: ...ck into the air handler FIGURE 8 Slide Coil Assembly Bottom Drain Pan and Horizontal Drain Pan Back Into the Air Handler as a Unit 7 Reinstall the brackets that hold the coil and horizontal drain pan...

Страница 7: ...LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER MAIN DRAIN TO APPROVED DRAIN FOR NEGATIVE PRESSURE COILS BLOWER AFTER COIL TRAPS ARE REQUIRED...

Страница 8: ...n is provided in Service and Application Note ACC002 August 2000 INSTALL CONDENSATE DRAIN The air handler is provided with 3 4 NPT condensate drain connections IMPORTANT On some pans the primary and s...

Страница 9: ...completed WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be kept closed as much as possible DO NOT remove li...

Страница 10: ...azing slide the rubber grommets over the refrigerant lines until they are away from the heat source NOTE Place wet rags against piping plate and around suction line connections 4 Connect the suction a...

Страница 11: ...LLOW FILTER ACCESSIBILITY NOTE CBX25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REF...

Страница 12: ...te electric power supplies before opening access panel Unit may have multiple power supplies WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristic...

Страница 13: ...ND 5 5 Replace the air handler access panel SIDE TOP FIGURE 15 Electrical Connections Upflow Configuration NOTE To avoid the possibility of moisture damage to the control in some right hand discharge...

Страница 14: ...U BLK BLK GRN BLUE BLUE BLU BLK GND 1032 1030 1031 1060 NOTES 1 FACTORY SPEED SET TO MEDIUM BLUE FOR 024 030 036 048 AND 060 2 ALL WIRES NOT LABELED ARE PART OF ITEM 1010 240 FIGURE 17 Typical Wiring...

Страница 15: ...r filter in place All factory settings are medium speed All data given while air handler is operating with a dry DX coil All downflow applications run on high speed when utilizing electric heat NOTE R...

Страница 16: ...eeds High Medium Low Pa in w g L s cfm L s cfm L s cfm 25 0 10 675 1430 597 1265 517 1095 50 0 20 632 1340 562 1190 486 1030 75 0 30 585 1240 521 1105 451 955 100 0 40 533 1130 472 1000 394 835 125 0...

Страница 17: ...seconds 4 Motor ramps down to stop 1 SECOND DELAY OFF 100 L s 100 L s 45 SECS COOLING DEMAND 1 2 3 4 FIGURE 20 Blower Time Delay COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for coolin...

Страница 18: ...e cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indi cation that the insulation is in...

Страница 19: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Страница 20: ...ternal Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Tem...

Отзывы: