Lennox CBX25UH-024 Скачать руководство пользователя страница 12

Page 12

Sealing the Unit 

Seal the unit so that warm air is not allowed into the cabi-

net. Warm air introduces moisture, which results in water 

blow-off problems. This is especially important when the 

unit is installed in an unconditioned area.
If installed in an unconditioned space, sealant should be 

applied around the electrical wires, refrigerant tubing, and 

condensate lines where they enter the cabinet.

 WARNING

There must be an airtight seal between the bottom of 

the air handler and the return air plenum. Use fiberglass 

sealing strips, caulking, or equivalent sealing method 

between the plenum and the air handler cabinet to 

ensure a tight seal. Return air must not be drawn from a 

room where this air handler or any gas-fueled appliance 

(i.e., water heater), or carbon monoxide-producing 

device (i.e., wood fireplace) is installed.

 IMPORTANT

Use duct tape and/ or Permagum to seal closed any 

space around the holes where the drain lines exit the 

cabinet. Warm air must not be allowed to enter through 

any gaps or holes in the cabinet.

Electrical Connections 

 WARNING

Electric shock hazard! - Disconnect all power 

supplies before servicing.
Replace all parts and panels before 

operating.
Failure to do so can result in death or 

electrical shock.

 WARNING

Run  24V  Class  II  wiring  only  through  specified  low 

voltage opening. Run line voltage wiring only through 

specified high voltage opening. Do not combine voltage 

in one opening.

 WARNING

Electric Shock Hazard. Can cause injury or 

death. Unit must be properly grounded in 

accordance with national and local codes.
Line voltage is present at all components 

when unit is not in operation on units with 

single-pole contactors. Disconnect all remote 

electric power supplies before opening 

access panel. Unit may have multiple power 

supplies.

 WARNING

Electric Shock Hazard. 
Can cause injury or death. 
Foil-faced insulation has conductive 

characteristics similar to metal. Be sure there 

are no electrical connections within 13mm 

of the insulation. If the foil-faced insulation 

comes in contact with electrical voltage, the 

foil could provide a path for current to pass 

through to the outer metal cabinet. While 

the current produced may not be enough to 

trip existing electrical safety devices (e.g., 

fuses or circuit breakers), the current can be 

enough to cause an electrical shock hazard 

that could cause personal injury or death.

 WARNING

Electric Shock Hazard. Can cause injury or 

death. Unit must be properly grounded in 

accordance with national and local codes.
Line voltage is present at all components when 

unit is not in operation on units with single-

pole contactors. Disconnect all remote electric 

power supplies before opening access panel. 

Unit may have multiple power supplies.

•   Wiring must conform to local building codes. Refer to 

the following wiring diagrams. See unit nameplate for 

minimum circuit ampacity and maximum over-current 

protection size. 

•   Electrical wiring, disconnect means and over-current 

protection are to be supplied by the installer. Refer to 

the air handler rating plate for maximum over-current 

protection, minimum circuit ampacity, as well as oper-

ating voltage. 

•   The power supply must be sized and protected accord-

ing to the specifications supplied on the product.

• 

 This air handler is factory-configured for 220/240 volt, 

single phase, 50 cycles. 

•   Separate openings have been provided for 24V low 

voltage and line voltage. Refer to the dimension illustra-

tion of specific location. 

•   This unit is provided with holes for conduit. Use provid-

ed caps to seal holes not used. 

• 

 Typical unit wiring is given in figure 19. 

Содержание CBX25UH-024

Страница 1: ...Check the air handler for shipping damage if found im mediately contact the last carrier Check the unit rating plate to confirm that delivered unit matches order General Information The CBX25UH air ha...

Страница 2: ...Page 2 CBX25UH Unit Dimensions Upflow Inches mm...

Страница 3: ...e instructions can result in death explosion or fire IMPORTANT Excessive condensation may occur if the unit is installed in a warm humid place When the unit is installed in an unconditioned space appl...

Страница 4: ...n HORIZONTAL DRAIN PAN MUST BE REMOVED UP FLOW DOWN FLOW DRAIN PAN FIGURE 1 Upflow Configuration HORIZONTAL APPLICATIONS IMPORTANT When removing the coil there is a possibility of danger of equipment...

Страница 5: ...ssembly bottom drain pan and horizontal drain pan as one unit from the air handler FIGURE 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan as a Unit 4 Remove the blow off prevention br...

Страница 6: ...ck into the air handler FIGURE 8 Slide Coil Assembly Bottom Drain Pan and Horizontal Drain Pan Back Into the Air Handler as a Unit 7 Reinstall the brackets that hold the coil and horizontal drain pan...

Страница 7: ...LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER MAIN DRAIN TO APPROVED DRAIN FOR NEGATIVE PRESSURE COILS BLOWER AFTER COIL TRAPS ARE REQUIRED...

Страница 8: ...n is provided in Service and Application Note ACC002 August 2000 INSTALL CONDENSATE DRAIN The air handler is provided with 3 4 NPT condensate drain connections IMPORTANT On some pans the primary and s...

Страница 9: ...completed WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be kept closed as much as possible DO NOT remove li...

Страница 10: ...azing slide the rubber grommets over the refrigerant lines until they are away from the heat source NOTE Place wet rags against piping plate and around suction line connections 4 Connect the suction a...

Страница 11: ...LLOW FILTER ACCESSIBILITY NOTE CBX25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REF...

Страница 12: ...te electric power supplies before opening access panel Unit may have multiple power supplies WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristic...

Страница 13: ...ND 5 5 Replace the air handler access panel SIDE TOP FIGURE 15 Electrical Connections Upflow Configuration NOTE To avoid the possibility of moisture damage to the control in some right hand discharge...

Страница 14: ...U BLK BLK GRN BLUE BLUE BLU BLK GND 1032 1030 1031 1060 NOTES 1 FACTORY SPEED SET TO MEDIUM BLUE FOR 024 030 036 048 AND 060 2 ALL WIRES NOT LABELED ARE PART OF ITEM 1010 240 FIGURE 17 Typical Wiring...

Страница 15: ...r filter in place All factory settings are medium speed All data given while air handler is operating with a dry DX coil All downflow applications run on high speed when utilizing electric heat NOTE R...

Страница 16: ...eeds High Medium Low Pa in w g L s cfm L s cfm L s cfm 25 0 10 675 1430 597 1265 517 1095 50 0 20 632 1340 562 1190 486 1030 75 0 30 585 1240 521 1105 451 955 100 0 40 533 1130 472 1000 394 835 125 0...

Страница 17: ...seconds 4 Motor ramps down to stop 1 SECOND DELAY OFF 100 L s 100 L s 45 SECS COOLING DEMAND 1 2 3 4 FIGURE 20 Blower Time Delay COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for coolin...

Страница 18: ...e cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indi cation that the insulation is in...

Страница 19: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Страница 20: ...ternal Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Tem...

Отзывы: