background image

Page 17

Check-out Procedures 

NOTE –

 

Refer to outdoor unit installation instructions for sys-

tem start-up instructions and refrigerant charging instructions. 

PRE-START-UP CHECKS 

•  Is the air handler properly and securely installed?
• 

 If horizontally configured, is the unit sloped up to 

16mm 

toward drain lines?

•  Will the unit be accessible for servicing?
•   Has an auxiliary pan been provided under the unit with 

separate drain for units installed above a finished ceil

-

ing  or  in  any  installation  where  condensate  overflow 

could cause damage?

•   

Have ALL unused drain pan ports been properly 

plugged?

•   Has the condensate line been properly sized, run, 

trapped, pitched, and tested?

•   Is the duct system correctly sized, run, sealed, and in-

sulated?

•  Have all cabinet openings and wiring been sealed?

•   Is the indoor coil factory-installed TXV properly sized for 

the outdoor unit being used?

•   Have all unused parts and packaging been disposed 

of?

• 

Is the filter clean, in place, and of adequate size?

•   Is the wiring neat, correct, and in accordance with the 

wiring diagram?

•  Is the unit properly grounded and protected (fused)?
•  Is the thermostat correctly wired and in a good location?
•  Are all access panels in place and secure?

CHECK BLOWER OPERATION

•  Set thermostat to FAN ON.
•  The indoor blower should come on.

CHECK COOLING OPERATION

•   Set thermostat to force a call for cooling (approximately 

2ºC lower than the indoor ambient temperature).

•   The outdoor unit should come on immediately and the 

indoor blower should start between 30 - 60 seconds lat-

er.

• 

 Check  the  air  flow  from  a  register  to  confirm  that  the 

system is moving cooled air.

•   Set the thermostat 2ºC higher than the indoor tempera-

ture. The indoor blower and outdoor unit should cycle 

off.

Operation  

TIME DELAY RELAY

Blower time delay operation:

1 -   When cooling demand is initiated, there is a 1 

second motor-on delay.

2 -   After the motor-on delay expires, motor ramps up 

to 100% and runs at 100% until cooling demand is 

satisfied.

3 -   Once demand is met, motor runs at 100% for 45 

seconds.

4 -  Motor ramps down to stop.

1

SECOND

DELAY

OFF

100%

L/s

100%

L/s

45

SECS

COOLING

DEMAND

1

2

3

4

FIGURE 20

. Blower Time Delay

COOLING (COOLING ONLY OR HEAT PUMP) 

When the thermostat calls for cooling, 24 volts is put on 

the blower time-delay relay coil and then the indoor blow-

er relay energizes. The normally open contacts close, 

causing the indoor blower motor to operate. The circuit 

between 

R

 and 

Y

 is completed, closing the circuit to the 

contactor in the outdoor unit, starting the compressor and 

outdoor fan motor. 
On heat pumps, circuit 

and 

O

 energizes the reversing 

valve, switching the valve to the cooling position. (The re-

versing valve remains energized as long as the thermo-

stat selector switch is in the 

COOL

 position.) 

At the completion of the cooling demand the indoor blower 

and outdoor unit should cycle off. Air handler should cycle 

off 45 seconds after the outdoor unit shuts off. 

HEATING (HEAT PUMP) 

When the thermostat calls for heating, 24 volts is applied 

to the blower time-delay relay coil. Then, normally open 

contacts close, causing the indoor blower motor to oper-

ate. The circuit between 

R

 and 

Y

 is completed, closing 

the circuit to the contactor in the outdoor unit, starting the 

compressor and outdoor fan motor. 
If the room temperature continues to decrease, the cir-

cuit between 

R

 and 

W1

 is completed by the second-stage 

heat room thermostat. Circuit 

R-W1

 energizes a heat se-

quencer. The completed circuit will energize supplemen-

tal electric heat (if applicable). Units with a second heat 

sequencer can be connected with the first sequencer to 

W1

 on the thermostat. They may also be connected to 

a second heating stage 

W2

 on the thermostat sub-base. 

EMERGENCY HEAT (HEATING HEAT PUMP) 

If the selector switch on the thermostat is set to the emer-

gency heat position, the heat pump will be locked out of 

the heating circuit, and all heating will be electric heat (if 

applicable). A jumper should be placed between 

W2

 and 

on the thermostat sub-base so that the electric heat con-

trol will transfer to the first-stage heat on the thermostat. 

This will allow the indoor blower to cycle on and off with the 

electric heat when the fan switch is in the AUTO position.

Содержание CBX25UH-024

Страница 1: ...Check the air handler for shipping damage if found im mediately contact the last carrier Check the unit rating plate to confirm that delivered unit matches order General Information The CBX25UH air ha...

Страница 2: ...Page 2 CBX25UH Unit Dimensions Upflow Inches mm...

Страница 3: ...e instructions can result in death explosion or fire IMPORTANT Excessive condensation may occur if the unit is installed in a warm humid place When the unit is installed in an unconditioned space appl...

Страница 4: ...n HORIZONTAL DRAIN PAN MUST BE REMOVED UP FLOW DOWN FLOW DRAIN PAN FIGURE 1 Upflow Configuration HORIZONTAL APPLICATIONS IMPORTANT When removing the coil there is a possibility of danger of equipment...

Страница 5: ...ssembly bottom drain pan and horizontal drain pan as one unit from the air handler FIGURE 5 Remove Coil Assembly Bottom Drain Pan and Horizontal Drain Pan as a Unit 4 Remove the blow off prevention br...

Страница 6: ...ck into the air handler FIGURE 8 Slide Coil Assembly Bottom Drain Pan and Horizontal Drain Pan Back Into the Air Handler as a Unit 7 Reinstall the brackets that hold the coil and horizontal drain pan...

Страница 7: ...LOCATED ABOVE A FINISHED SPACE THE SECONDARY DRAIN PAN MUST HAVE A LARGER FOOTPRINT THAN THE AIR HANDLER MAIN DRAIN TO APPROVED DRAIN FOR NEGATIVE PRESSURE COILS BLOWER AFTER COIL TRAPS ARE REQUIRED...

Страница 8: ...n is provided in Service and Application Note ACC002 August 2000 INSTALL CONDENSATE DRAIN The air handler is provided with 3 4 NPT condensate drain connections IMPORTANT On some pans the primary and s...

Страница 9: ...completed WARNING Polyol ester POE oils used with HFC 410A refrigerant absorb moisture very quickly It is very important that the refrigerant system be kept closed as much as possible DO NOT remove li...

Страница 10: ...azing slide the rubber grommets over the refrigerant lines until they are away from the heat source NOTE Place wet rags against piping plate and around suction line connections 4 Connect the suction a...

Страница 11: ...LLOW FILTER ACCESSIBILITY NOTE CBX25UH SERIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REF...

Страница 12: ...te electric power supplies before opening access panel Unit may have multiple power supplies WARNING Electric Shock Hazard Can cause injury or death Foil faced insulation has conductive characteristic...

Страница 13: ...ND 5 5 Replace the air handler access panel SIDE TOP FIGURE 15 Electrical Connections Upflow Configuration NOTE To avoid the possibility of moisture damage to the control in some right hand discharge...

Страница 14: ...U BLK BLK GRN BLUE BLUE BLU BLK GND 1032 1030 1031 1060 NOTES 1 FACTORY SPEED SET TO MEDIUM BLUE FOR 024 030 036 048 AND 060 2 ALL WIRES NOT LABELED ARE PART OF ITEM 1010 240 FIGURE 17 Typical Wiring...

Страница 15: ...r filter in place All factory settings are medium speed All data given while air handler is operating with a dry DX coil All downflow applications run on high speed when utilizing electric heat NOTE R...

Страница 16: ...eeds High Medium Low Pa in w g L s cfm L s cfm L s cfm 25 0 10 675 1430 597 1265 517 1095 50 0 20 632 1340 562 1190 486 1030 75 0 30 585 1240 521 1105 451 955 100 0 40 533 1130 472 1000 394 835 125 0...

Страница 17: ...seconds 4 Motor ramps down to stop 1 SECOND DELAY OFF 100 L s 100 L s 45 SECS COOLING DEMAND 1 2 3 4 FIGURE 20 Blower Time Delay COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for coolin...

Страница 18: ...e cabinet which leads to sheet metal corrosion and subsequently component failure REPAIRING DAMAGED INSULATION Areas of condensation on the cabinet surface are an indi cation that the insulation is in...

Страница 19: ...Duct Temperature ___________ THERMOSTAT Adjusted and Programmed Return External Static ______ ______ Total External Static ______ ______ 6 Supply Duct Temperature ___________ Temperature Drop _______...

Страница 20: ...ternal Static ______ ______ 6 6 Supply Duct Temperature ___________ Temperature Drop ___________ TEMPERATURE RISE Heating Mode Return Duct Temperature __________ Supply Duct Temperature __________ Tem...

Отзывы: