506257-01
Issue 1330
Page 7 of 29
Figure 7
Figure 8
Outside Wall
Wood Block
Between Studs
IMPORTANT: Refrigerant
lines must not contact wall.
Vapor Line Liquid Line
Wire Tie
Inside Wall
Strap
Sleeve
Wire Tie
Wire Tie
Strap
Wood Block
Sleeve
Vapor Line Wrapped
with Armaflex
Liquid Line
Caulk
PVC Pipe Fiberglass
Insulation
Outside Wall
IMPORTANT:
Refrigerant
lines must not
contact structure.
Anchored
Heavy Nylon
Wire Tie
Wall
Stud
Metal Sleeve
Vapor Line Wrapped
in Armaflex
–
Liquid Line
Wall
Stud
Automotive
Muffler-Type
Hanger
Strap Liquid
Line to Vapor
Line
Metal Sleeve
Vapor Line Wrapped
in Armaflex
–
Liquid Line
Strap Liquid
Line to Vapor
Line
Refrigerant Line Sets: Transition from Vertical to Horizontal
Refrigerant Line Sets: Installing Vertical Runs (new construction shown)
NOTE: Similar Installation practices should
be used if line set is to be installed on
exterior of outside wall.