background image

506257-01

Issue  1330

Page 24  of  29

HOMEOWNER INFORMATION

In order to ensure peak performance, your system must be 

properly maintained.  Clogged filters and blocked airflow 

prevent your unit from operating at its most efficient level.

Ask your dealer to show you where the indoor unit’s filter is 

located.  It will be either at the indoor unit (installed internal 

or external to the cabinet) or behind a return air grille in the 

wall or ceiling in your home.  Check the filter monthly and 

clean or replace it as needed.

Disposable filters should be replaced with a filter of the same 

type and size.  If you are unsure of the filter you need for 

your system, contact your dealer.

Many indoor units are equipped with reusable foam filters.  

These filters can be cleaned with a mild soap and water 

solution.  Rinse the filter thoroughly and let dry completely 

before returning to unit or grille.

The filter and all access panels must be in place any 

time the unit is in operation.

Some systems are equipped with an electronic air cleaner, 

designed to remove the majority of airborne particles from 

the air passing through the cleaner.  If your system includes 

an electronic air cleaner, ask your dealer for maintenance 

instructions.

Inspect and clean indoor coil.  The indoor evaporator coil 

is equipped with a drain pan to collect condensate formed 

as the system removes humidity from the inside air.  Have 

your dealer show you the location of the drain line and how 

to check for obstructions.  This also applies to an auxiliary 

drain, if one is installed.

Inspect and clean outdoor coil:

Make sure no obstructions restrict airflow to the outdoor unit.  

Leaves, trash, or shrubs crowding the unit can cause it to 

work harder and use more energy.  Keep shrubbery trimmed 

away from the unit and periodically check for debris which 

collects around the unit.

The outdoor coil may require frequent cleaning, depending 

on environmental conditions.  Clean the outdoor coil with an 

unpressurized water hose to remove surface contaminants 

and debris.  It may be necessary to flush the outdoor coil 

more frequently if it is exposed to

to substances which are corrosive or which block airflow 

across the coil (such as pet urine, cottonwood seeds, etc...).

Heat Pump Operation

Heat pump units have several characteristics you should 

be aware of:

Heat pumps satisfy heating demand by delivering large 

amounts of 

warm air

 into the living space.  This is quite 

different from gas-fired, oil-fired, or electric furnaces which 

deliver  lower  volumes  of  considerably 

hotter air

 to heat 

the space.

Do not be alarmed if you notice frost on the outdoor coil in 

the winter months.  Frost develops on the outdoor coil during 

the heating cycle when temperatures are below 45°F.  An 

electronic control activates a defrost cycle lasting 5 to 15 

minutes at preset intervals to clear the outdoor coil of the 

frost.  A shift in sound type does occur during the defrost 

mode.

During the defrost cycle, you may notice steam rising from 

the unit.  This is a normal occurrence.  The thermostat may 

engage auxiliary heat during the defrost cycle to satisfy a 

heating demand.  The unit will return to normal operation 

at the conclusion of the defrost cycle.

In case of extended power outage....

If the outdoor temperature is below 50°F and power to the 

outdoor unit has been interrupted for 6 hours or longer.  

observe  the  following  when  restoring  power  to  the  heat 

pump system.

Set the room thermostat selctor to the “Emergency Heat” 

setting to obtain temporary heat for a minimum of 6 

hours.   This  will  allow  system  refrigerant  pressures  and 

temperatures enough time to return to a stabilized condition.

In  the  “Emergency  Heat”  mode,  all  heating  demand  is 

satisfied by auxiliary heat; heat pump operation is locked 

out.  After a 6 hour “warmup” period, the thermostat can then 

be switched to the “Heat” setting and normal heat operation 

may resume.

Thermostat Operation

Though  your  thermostat  may  vary  somewhat  from  the 

description below, its operation will be similar.

Temperature Setting Levers

Most heat pump thermostats have two temperature selector 

levers: one for heating and one for cooling.  Set the levers or 

dials to the desired temperature setpoints for both heating 

and cooling.  Avoid frequent temperature adjustment; turning 

the unit off and back on before presssures equalize puts 

stress on unit compressor.

Turn  all  electric  power  to  unit  OFF  at  disconnect 

switch(es)  before  performing  any  maintenance 

operations on system.  Unit may have multiple power 

supplies.  Electrical shock could cause personal injury 

or death.

  WARNING

Содержание Allied Air 4HP18LT- 24

Страница 1: ...tallation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to avoid shar...

Страница 2: ...for use by qualified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Cod...

Страница 3: ...or 2 per 5 This will prevent ice from building up under the unit during a defrost cycle Refer to following roof mounting section for barrier construction if unit must face prevailing winter winds If...

Страница 4: ...o this section as well as the section that follows entitled Flushing Existing Line Set and Indoor Coil If this unit is being matched with an approved line set or indoor coil which was previously charg...

Страница 5: ...Connection Procedure 1 Cut ends of refrigerant lines square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of line 2 Before making line set connections use dry nit...

Страница 6: ...r use either metal strapping material or anchored heavy nylon wire ties Strapping Material around vapor line only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then s...

Страница 7: ...Refrigerant lines must not contact structure Anchored Heavy Nylon Wire Tie Wall Stud Metal Sleeve Vapor Line Wrapped in Armaflex Liquid Line Wall Stud Automotive Muffler Type Hanger Strap Liquid Line...

Страница 8: ...confirm that the entire system is completely void of refrigerant Disconnect the liquid and suction lines from the existing outdoor unit If the existing outdoor unit is equipped with manual shutoff val...

Страница 9: ...procedure 9 Close the valve on the inverted R 22 cylinder and the gauge set valves Pump the remaining refrigerant out of the recovery machine and turn the machine off 10 Use nitrogen to break the vacu...

Страница 10: ...primary leak seal To Access the Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten...

Страница 11: ...tion refrigerant requirements will vary with lengths Check all joints for leaks Purge nitrogen and R410A mixture Correct any leaks and rechecks Evacuation Evacuating the system of noncondensables is c...

Страница 12: ...ld gauge center port hose to a nitrogen cylinder with pressure regulator set to 150 psig and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the...

Страница 13: ...efrigerant Units are factory charged with the amount of R410A refrigerant indicated on the unit rating plate This charge is based on a matching indoor coil and outdoor coil with 15 line set For varyin...

Страница 14: ...is void of refrigerant or if the outdoor ambient temperature is cool use the weigh in method to charge the unit Do this after any leaks have been repaired 1 Recover the refrigerant from the unit 2 Con...

Страница 15: ...ature from the liquid line temperture to determine the approach temperature T em p F P ressure P sig T em p F P ressure P sig T em p F P ressure P sig 32 100 8 74 214 0 116 396 0 33 102 9 75 217 4 117...

Страница 16: ...8 to perform maintenance checks Table 7 is not a procedure for charging the system Minor variations in these pressures may be due to differences in installations Significant deviations could mean that...

Страница 17: ...ue 1330 Page 17 of 29 Normal Operating Pressures Table 8 L Liquid S Suction Values provided above are typical pressures Indoor unit matchup indoor air quality equipment and indoor load will case press...

Страница 18: ...erature is below 50 F System should be left in the emergency heat mode at least 6 hours to allow the crankcase heater sufficient time to prevent compressor slugging Defrost System The defrost system i...

Страница 19: ...onds going in and out of the defrost mode when the compressor delay jumper is installed NOTE The 30 second off cycle is deactivated if the TEST pin is removed Time Delay The timed off delay is 5 minut...

Страница 20: ...flash a number of times consecutively pause and then repeat the process The number of consecutive flashes correlates to a paticular abnormal condition TRIP LED Red indicates there is a demand signal f...

Страница 21: ...or 21VAC is removed from the module TRIP andALERT LEDs flashing at the same time means control circuit voltage is too low for operation 24VAC Power Wiring The diagnostic module requires a constant nom...

Страница 22: ...ut is 24VAC When the coil is not energized the demand signal input should be less than 0 5VAC Miswired Module Codes Depending on the system configuration some ALERT flash codes may not be active The p...

Страница 23: ...perage draw at the outdoor fan motor compressor and indoor blower motor Values should be compared with those given on unit nameplate Check clean or replace indoor unit filters Check the refrigerant ch...

Страница 24: ...l such as pet urine cottonwood seeds etc Heat Pump Operation Heat pump units have several characteristics you should be aware of Heat pumps satisfy heating demand by delivering large amounts of warm a...

Страница 25: ...he auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperature Indicator The temperture indica...

Страница 26: ...tdoor Fan __________ Maximum Fuse or Circuit Breaker ________________________ Electical Connections Tight Indoor Filter Clean Supply Voltage Unit Off __________ Indoor Blower RPM ___________________ S...

Страница 27: ...EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 ORANGE B4 PURPLE B1 GROUND LUG GROUND L2 L1 208 230 60 1 DUAL CAPACITOR RED COMPRESSOR CONTACTOR BLACK COMPRESSOR CRANKCASE HEATE...

Страница 28: ...er is unable to provide warranty service check online at www alliedair com 3 Be prepared to furnish the following information a complete model and serial number b proof of required periodic maintenanc...

Страница 29: ...t 3 Modification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation...

Отзывы: