24

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

BLOWER CONTROL CIRCUIT WIRING

120V, 60HZ, 1PH  

Factory Wired

Ground

Field Wired

Junction Box 

Tab Intact

Tab 

Broken

Plug blower

into this 

receptacle

ne

er

G - 

dn

uor

G

* Wall-mounted

ON/ OFF Blower 

Switch or Variable 

Speed Control Switch. 

Blower

eti

h

W - 

lar

tu

eN 12

VA

- B

la

ck

Green

Ground

Screw

W

hi

te

Gr

ee

n

Neutral 

Side of

Receptacle

Hot

Side of

Receptacle

Red

Black

Figure 38 - 

J-BOX WIRING

Step 6. CONNECTING GAS LINE 

All codes require a shut-off valve mounted in 

the supply line.  The orientation of the shut-off 

valve should face the front. 

Figure 39 

 illustrates 

two methods for connecting the gas supply.  

A Sediment Trap is recommended to prevent 

moisture and debris in gas line from damaging 

the valve.

The flex-line method is acceptable in the U.S.A. 

where local codes permit, however, Canadian 

requirements vary depending on locality. Instal-

lation must be in compliance with local codes.  

These appliances are equipped with a gas flex-

line for use in connecting the unit to the gas line.  

See 

Figure 39  

for flex-line description.  The 

flex-line is rated for both natural and propane 

gas.  A manual shut off valve is also provided 

with the flex-line.

Step 5.

 

WIRING - OPTIONAL FORCED AIR 

BLOWER KIT 

(millivolt models only)

(See Figure 36 on Page 23)

An  electrical  outlet  box  is  provided  for  the 

installation of the LBLK-100 forced air blower 

kit.  Electrical power must be provided to this 

box to operate these blowers. Install the blower 

kit  according  to  the  installation  instructions 

provided with the kit.

If the blower kit is to be installed at the time of 

installation or at a later date, the main power sup-

ply and wall switch must be installed at the time of 

installation.  This will require that the electrical 

connections must be made BEFORE the fireplace 

is framed and enclosed in the finished walls.  

Route a 3-wire, 120 VAC, 60 Hz, 1 ph power 

supply and connect to electrical receptacle wires 

and wall switch or wall rheostat.

Gas Valve

Burner

ON/OFF Switch

Push Button

Piezo Igniter

Figure 40 - Control Compartment

Glass Door

Gas Shut-

Off Valve

Gas Flex-

Line

Gas

Valve

3/8" NPT  x 

Flare Fitting 

3/8" Flex Tubing 

3/8" Nipple

3/8" Union

3/8" Close 

Nipple

3/8" Shut-off Valve 

1/2" x 3/8" 

Reducer

Gas 

Stub 

1/2" x 3/8" Flare 

Shut-off Valve 

Gas Solid Line Connector

Gas Flex Line Connector

*Sediment

   Trap

3"

Min

Figure 39 - 

GAS CONNECTION

If required, access the valve (see

 Figure 40

 ) by 

opening the lower control panel  (see instruction 

sheet provided with the facade kit for additional 

information about the control panel).

The millivolt and electronic control valve has a 

3/8" (10 mm) NPT thread gas supply inlet.

Bring the shutoff valve on the end of the flex-line 

over to the hard pipe and tighten with wrenches 

from above through the firebox opening.

Secure  all  joints  tightly  using  appropriate 

tools and sealing compounds (ensure propane 

resistant compounds are used in propane ap-

plications).   It is recommended to seal around 

the gas line to prevent cold air leakage.

Note: The gas supply line 

must be installed in accor-

dance with building codes 

by a qualified installer 

approved and/or licensed 

as required by the locality.  

In the Commonwealth of 

Massachusetts, installation 

must be performed by a 

licensed plumber or gas 

fitter.

f i r e - p a r t s . c o m

Содержание ADAGIO-EN

Страница 1: ...isseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur...

Страница 2: ...ssories that will require electrical power are to be installed the electrical power must be provided at the time of appliance installation The Electronic appliances have an electronic intermittent pil...

Страница 3: ...Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of th...

Страница 4: ...edition NOTE Flame appearance will diminish 4 per thousand feet Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas drill size inches Propane drill size inches Adagio 000 51 H0922...

Страница 5: ...and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line ho...

Страница 6: ...tional Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccording to the installation cod...

Страница 7: ...r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i...

Страница 8: ...insulate the space between the appliance and the area above it Shelf Height see table Shelf Above Fireplace Top Vent Drywall Header Top Spacers 4 102mm u4 clearance is required above the elbow for ins...

Страница 9: ...upport Thefireplaceshouldbesecuredtothesidefram ingmembersusingtheunit snailingflangeson each side of the fireplace front see Figure 11 Use 8d nails or their equivalent Figure 11 Left Side Front Corne...

Страница 10: ...nce below the vent This does not include the suggested 1 4 rise per foot for horizontal runs With the facade installed required sold separately the appliancebasewillneedtobeelevatedaminimumof3 4 above...

Страница 11: ...o change or discontinuance without notice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of...

Страница 12: ...sooting severe delayed ignition orothermalfunctions Anydamageresulting from an improper installation such as this is not covered under the limited warranty Never use galvanized or plastic pipe Refer...

Страница 13: ...on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap pliances and must never be connected to a flue servingasolidfuelburningappliance The vent...

Страница 14: ...5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0...

Страница 15: ...of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer...

Страница 16: ...ulk ing or mastic around the circumference of the joint to provide a water tight seal Figure 22 Storm Collar Flashing Figure 23 If the vent system extends more than 5 1 5 m above the roof flashing sta...

Страница 17: ...VF uCeiling Firestop Spacer SV4 5VF u Ceiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4...

Страница 18: ...nces for elbows as indicated in Figure 20 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sid...

Страница 19: ...vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem topointwheretheterminusofthelastse...

Страница 20: ...1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 30 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VER...

Страница 21: ...f 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 30 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spa...

Страница 22: ...ck out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent...

Страница 23: ...U P 2 1 N E E R G BLUE 20 BLACK 16 WHITE FIELD WIRED FACTORY WIRED Turn The Appliance Mounted ON OFF Burner Control Switch To The OFF Position If An Optional Control Switch Is Installed Optional Blowe...

Страница 24: ...ns provided with the kit If the blower kit is to be installed at the time of installationoratalaterdate themainpowersup plyandwallswitchmustbeinstalledatthetimeof installation This will require that t...

Страница 25: ...ions provided in the Care and Operation Manual For piezo igniter location see Figure 40 on Page 24 millivolt appliances only Note LightingInstructionsarealsofoundonthe literature tag tied to the gas p...

Страница 26: ...installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engi neered to give the appli...

Страница 27: ...ole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 47 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into...

Страница 28: ...ner when installing the door Take care when seat ing the top door gasket so that it is not obstructed by the refractory panel If the doorfeelsrestrictedwhenlatching thetop door gasket may not be prope...

Страница 29: ...rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minut...

Страница 30: ...equirements Wall Details Complete finished interior wall To install the appliance facing flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 54 u 4...

Страница 31: ...ntrelasetiquetasadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeel...

Страница 32: ...750 247M Vent Sections ListedSecureFlex Components Cat No Model Description These termination kits include firestop spacer gear clamps and flex adaptor H1969 SF4 5HT 2 HorizontalSquareTermina tion wit...

Страница 33: ...anufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproductionofcarbon monoxid...

Страница 34: ...t Orifice Thermopile on millivolt pilot assem blies only Millivolt Electronic Pilot Assemblies SIT Electronic Pilot Pilot Orifice B Retrieve the burner and slide the venturi tube over the orifice see...

Страница 35: ...35 NOTES fire parts com...

Страница 36: ...oducts reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fir...

Отзывы: