background image

18

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Remember to maintain 1" (25 mm) clearance 

to combustibles, framing members, and attic 

or  ceiling  insulation  when  running  vertical 

chimney sections.

G. Support the vertical run sections - 

See 

Section E

 on 

Page 15.

 

H. Change vent direction -  At transition from or 

to a horizontal/inclined run, install the SV4.5E45 

and SV4.5E90 elbows in the same manner as 

the straight vent sections.  The elbows feature a 

twist section to allow them to be routed about the 

center axis of their initial collar section to align 

with the required direction of the next vent run 

element. Twist elbow sections in a clockwise 

direction only so as to avoid the possibility of 

unlocking any of the previously connected vent 

sections (see 

Figure 18 on Page 15)

.

I. Continue installation of horizontal/inclined 

sections -  Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in Step E. Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 

vent runs using conventional plumber’s tape. 

See 

Figure 27

, 

it is very important that the 

horizontal/inclined  run  be  maintained  in  a 

straight (no dips) and recommended to be in 

a slightly elevated plane, in a direction away 

from the fireplace of 1/4" rise per foot (20 mm 

per meter) which is ideal

, though rise per foot 

run ratios that are smaller are acceptable all the 

way down to at or near level.  

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides 

for all vertical runs; and 3" (76 mm) at the top, 

1" (25 mm) at sides, and 1" (25 mm) at the 

bottom for all horizontal/inclined runs.

Use  a  carpenter’s  level  to  measure  from  a 

constant surface and adjust the support straps 

as necessary. 

HORIZONTAL (OUTSIDE WALL) TERMINATION 

SYSTEM

See 

Figures 27, and Figures 30 to 33 on Pages 

18, 20 and 21 

and their associated Horizontal 

Vent Table which illustrate the various horizontal 

venting configurations that are possible for use 

with these appliances.  Secure Vent™ pipe ap-

plications are shown in these figures; Secure 

Flex™ pipe may also be used. A Horizontal Vent 

Table summarizes each system’s minimum and 

maximum vertical and horizontal length values 

that can be used to design and install the vent 

components in a variety of applications. 

Both of these horizontal vent systems terminate 

through an outside wall. Building Codes limit or 

prohibit terminating in specific areas. Refer to 

Figure 7

 on 

Page 7

 for location guidelines.

Secure Vent SV4.5 direct-vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connection, (refer 

to 

Figure  18

  on 

Page  15

).    All  of  the  appli-

ances covered in this document are fitted with 

collars having locking inclined channels. The 

dimpled end of the vent components fit over 

the appliance collar to create the positive twist 

lock connection.

A. Plan the vent run - 

Analyze the vent routing and determine the 

types and quantities of sections required 4-

1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 

mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm) 

net section lengths are available.  It is recom-

mended that you plan the vent lengths so that a 

joint does not occur at the intersection of ceiling 

or roof joists. Make allowances for elbows as 

indicated in 

Figure 20 on Page 16

Maintain a minimum 1" (25 mm) clearance to 

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm) 

on top, 1" (25 mm) on sides, and 1" (25 mm) 

at the bottom.

B. Frame exterior wall opening - 

Locate  the  center  of  the  vent  outlet  on 

the  exterior  wall  according  to  the  dimen-

sions  shown  in 

Figure  12 

on 

Page  10

.  Cut 

and/or  frame  an  opening,  10-1/2"  x  12-1/8"  

(267 mm x 308 mm) inside dimensions, about 

this center.

C. Frame ceiling opening - If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center (refer 

to 

Figure 17 

on 

Page 15

).

D. Attach vent components to appliance - To 

attach a vent component to the appliance collar, 

align the dimpled end over the collar, adjust-

ing the radial alignment until the four locking 

dimples are aligned with the inlets of the four 

incline channels on the collar (refer to 

Figure 

18

 on 

Page 15

).

Push  the  vent  component  against  the  collar 

until it fully engages, then twist the component 

clockwise, running the dimples down and along 

the incline channels until they seat at the end 

of  the  channels.    The  unitized  design  of  the 

Secure Vent components will engage and seal 

both the inner and outer pipe elements with the 

same procedure.  Sealant and securing screws 

are not required.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section.

E.    Attach  vent  components  to  each  other 

-  Other  vent  sections  may  be  added  to  the 

previously installed section in accordance with 

the  requirements  of  the  vent  tables.    To  add 

another  vent  component  to  a  length  of  vent 

run, align the dimpled end of the component 

over the inclined channel end of the previously 

installed section, adjusting the radial alignment 

until the four locking dimples are aligned with 

the  inlets  of  the  four  incline  channels  of  the 

previous section.  

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component  clockwise  running  the  dimples 

down and along the incline channels until they 

seat at the end of the channels. This seating 

position is indicated by the alignment of the 

arrow and dimple as shown in 

Figure 18 on 

Page 15.

F. Install firestop/spacer at ceiling - 

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex, 

use SF4.5VF firestop/spacer. If there is living 

space  above  the  ceiling  level,  the  firestop/ 

spacer must be installed on the bottom side of 

the ceiling. If attic space is above the ceiling, the 

firestop/ spacer must be installed on the top side 

of the joist.  Route the vent sections through the 

framed opening and secure the firestop/spacer 

with 8d nails or other appropriate fasteners at 

each corner.

Figure 27 

Support the vertical portion of the venting system 

every 8 feet (2.4m) above the fireplace vent outlet.

Ceiling

Fireplace

Vertical

Rise

SV4.5 HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

SV4.5 HT-2

Termination

Shown

Support Brackets

Building

Support

Framing

Horizontal / Inclined Run

SV4.5E90

Elbow

See 

Figure 19 

on 

Page 15

  for vertical 

vent section support.

u

 

When Using Secure Flex, 

Use Firestop / Spacer SF4.5VF

u

 

Firestop / Spacer

SV4.5VF

SV4.5L6/12/24/36/48

Vent Sections

Exterior

Wall

f i r e - p a r t s . c o m

Содержание ADAGIO-EN

Страница 1: ...isseur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur...

Страница 2: ...ssories that will require electrical power are to be installed the electrical power must be provided at the time of appliance installation The Electronic appliances have an electronic intermittent pil...

Страница 3: ...Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstruct the front openings of th...

Страница 4: ...edition NOTE Flame appearance will diminish 4 per thousand feet Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas drill size inches Propane drill size inches Adagio 000 51 H0922...

Страница 5: ...and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line ho...

Страница 6: ...tional Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccording to the installation cod...

Страница 7: ...r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i...

Страница 8: ...insulate the space between the appliance and the area above it Shelf Height see table Shelf Above Fireplace Top Vent Drywall Header Top Spacers 4 102mm u4 clearance is required above the elbow for ins...

Страница 9: ...upport Thefireplaceshouldbesecuredtothesidefram ingmembersusingtheunit snailingflangeson each side of the fireplace front see Figure 11 Use 8d nails or their equivalent Figure 11 Left Side Front Corne...

Страница 10: ...nce below the vent This does not include the suggested 1 4 rise per foot for horizontal runs With the facade installed required sold separately the appliancebasewillneedtobeelevatedaminimumof3 4 above...

Страница 11: ...o change or discontinuance without notice With the facade installed required sold separately the appliance base will need to be elevated a minimum of 3 4 above the floor to allow for the proper fit of...

Страница 12: ...sooting severe delayed ignition orothermalfunctions Anydamageresulting from an improper installation such as this is not covered under the limited warranty Never use galvanized or plastic pipe Refer...

Страница 13: ...on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple ap pliances and must never be connected to a flue servingasolidfuelburningappliance The vent...

Страница 14: ...5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0 0 0 1 1 2 0 9 5 7 0 2 1 0 1 4 5 1 9 5 2 6 7 0 0 2 0 1 3 3 9 5 7 7 0 0...

Страница 15: ...of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer...

Страница 16: ...ulk ing or mastic around the circumference of the joint to provide a water tight seal Figure 22 Storm Collar Flashing Figure 23 If the vent system extends more than 5 1 5 m above the roof flashing sta...

Страница 17: ...VF uCeiling Firestop Spacer SV4 5VF u Ceiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4...

Страница 18: ...nces for elbows as indicated in Figure 20 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sid...

Страница 19: ...vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as describedinStepB Assembletheventsystem topointwheretheterminusofthelastse...

Страница 20: ...1 V to 5 H ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 30 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VER...

Страница 21: ...f 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 30 V H H1 V1 Wall Firestop Spacer SV4 5HF Ceiling Firestop Spa...

Страница 22: ...ck out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent...

Страница 23: ...U P 2 1 N E E R G BLUE 20 BLACK 16 WHITE FIELD WIRED FACTORY WIRED Turn The Appliance Mounted ON OFF Burner Control Switch To The OFF Position If An Optional Control Switch Is Installed Optional Blowe...

Страница 24: ...ns provided with the kit If the blower kit is to be installed at the time of installationoratalaterdate themainpowersup plyandwallswitchmustbeinstalledatthetimeof installation This will require that t...

Страница 25: ...ions provided in the Care and Operation Manual For piezo igniter location see Figure 40 on Page 24 millivolt appliances only Note LightingInstructionsarealsofoundonthe literature tag tied to the gas p...

Страница 26: ...installation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engi neered to give the appli...

Страница 27: ...ole on the bottom of log D over pin 3 4 Place the right front log E as shown in Figure 47 Position the hole on the bottom of log E over pins 4 and 5 6 Ember Placement Separate the Embers rockwool into...

Страница 28: ...ner when installing the door Take care when seat ing the top door gasket so that it is not obstructed by the refractory panel If the doorfeelsrestrictedwhenlatching thetop door gasket may not be prope...

Страница 29: ...rod and associated adjustable air shutter is patented technology Flame ad justments can be made quickly and accurately to taste without the need of disassembling the appliance and waiting for 30 minut...

Страница 30: ...equirements Wall Details Complete finished interior wall To install the appliance facing flush with the finished wall position framework to accommodate the thickness of the finished wall Figure 54 u 4...

Страница 31: ...ntrelasetiquetasadhesivasmultiling es proporcionadas con estas instrucciones y prosiga de la siguiente manera 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifiquequeel...

Страница 32: ...750 247M Vent Sections ListedSecureFlex Components Cat No Model Description These termination kits include firestop spacer gear clamps and flex adaptor H1969 SF4 5HT 2 HorizontalSquareTermina tion wit...

Страница 33: ...anufacturer s instructions and all applicable codes and requirementsoftheauthorityhavingjurisdiction Iftheinformationinthese instructionisnotfollowedexactly afire explosionorproductionofcarbon monoxid...

Страница 34: ...t Orifice Thermopile on millivolt pilot assem blies only Millivolt Electronic Pilot Assemblies SIT Electronic Pilot Pilot Orifice B Retrieve the burner and slide the venturi tube over the orifice see...

Страница 35: ...35 NOTES fire parts com...

Страница 36: ...oducts reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fir...

Отзывы: