18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Remember to maintain 1" (25 mm) clearance
to combustibles, framing members, and attic
or ceiling insulation when running vertical
chimney sections.
G. Support the vertical run sections -
See
Section E
on
Page 15.
H. Change vent direction - At transition from or
to a horizontal/inclined run, install the SV4.5E45
and SV4.5E90 elbows in the same manner as
the straight vent sections. The elbows feature a
twist section to allow them to be routed about the
center axis of their initial collar section to align
with the required direction of the next vent run
element. Twist elbow sections in a clockwise
direction only so as to avoid the possibility of
unlocking any of the previously connected vent
sections (see
Figure 18 on Page 15)
.
I. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step E. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber’s tape.
See
Figure 27
,
it is very important that the
horizontal/inclined run be maintained in a
straight (no dips) and recommended to be in
a slightly elevated plane, in a direction away
from the fireplace of 1/4" rise per foot (20 mm
per meter) which is ideal
, though rise per foot
run ratios that are smaller are acceptable all the
way down to at or near level.
It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.
Use a carpenter’s level to measure from a
constant surface and adjust the support straps
as necessary.
HORIZONTAL (OUTSIDE WALL) TERMINATION
SYSTEM
See
Figures 27, and Figures 30 to 33 on Pages
18, 20 and 21
and their associated Horizontal
Vent Table which illustrate the various horizontal
venting configurations that are possible for use
with these appliances. Secure Vent™ pipe ap-
plications are shown in these figures; Secure
Flex™ pipe may also be used. A Horizontal Vent
Table summarizes each system’s minimum and
maximum vertical and horizontal length values
that can be used to design and install the vent
components in a variety of applications.
Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit or
prohibit terminating in specific areas. Refer to
Figure 7
on
Page 7
for location guidelines.
Secure Vent SV4.5 direct-vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to
Figure 18
on
Page 15
). All of the appli-
ances covered in this document are fitted with
collars having locking inclined channels. The
dimpled end of the vent components fit over
the appliance collar to create the positive twist
lock connection.
A. Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required 4-
1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572
mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm)
net section lengths are available. It is recom-
mended that you plan the vent lengths so that a
joint does not occur at the intersection of ceiling
or roof joists. Make allowances for elbows as
indicated in
Figure 20 on Page 16
.
Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm)
on top, 1" (25 mm) on sides, and 1" (25 mm)
at the bottom.
B. Frame exterior wall opening -
Locate the center of the vent outlet on
the exterior wall according to the dimen-
sions shown in
Figure 12
on
Page 10
. Cut
and/or frame an opening, 10-1/2" x 12-1/8"
(267 mm x 308 mm) inside dimensions, about
this center.
C. Frame ceiling opening - If the vertical route
is to penetrate a ceiling, use plumb line to locate
the center above the appliance. Cut and/or frame
an opening, 10-1/2" x 10-1/2" (267 mm x 267
mm) inside dimensions, about this center (refer
to
Figure 17
on
Page 15
).
D. Attach vent components to appliance - To
attach a vent component to the appliance collar,
align the dimpled end over the collar, adjust-
ing the radial alignment until the four locking
dimples are aligned with the inlets of the four
incline channels on the collar (refer to
Figure
18
on
Page 15
).
Push the vent component against the collar
until it fully engages, then twist the component
clockwise, running the dimples down and along
the incline channels until they seat at the end
of the channels. The unitized design of the
Secure Vent components will engage and seal
both the inner and outer pipe elements with the
same procedure. Sealant and securing screws
are not required.
Note:
An elbow may also be attached to the
appliance collar. Attach in the same manner
as you would a vent section.
E. Attach vent components to each other
- Other vent sections may be added to the
previously installed section in accordance with
the requirements of the vent tables. To add
another vent component to a length of vent
run, align the dimpled end of the component
over the inclined channel end of the previously
installed section, adjusting the radial alignment
until the four locking dimples are aligned with
the inlets of the four incline channels of the
previous section.
Push the vent component against the previous
section until it fully engages, then twist the
component clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels. This seating
position is indicated by the alignment of the
arrow and dimple as shown in
Figure 18 on
Page 15.
F. Install firestop/spacer at ceiling -
When using Secure Vent, use SV4.5VF firestop/
spacer at ceiling joists; when using Secure Flex,
use SF4.5VF firestop/spacer. If there is living
space above the ceiling level, the firestop/
spacer must be installed on the bottom side of
the ceiling. If attic space is above the ceiling, the
firestop/ spacer must be installed on the top side
of the joist. Route the vent sections through the
framed opening and secure the firestop/spacer
with 8d nails or other appropriate fasteners at
each corner.
Figure 27
Support the vertical portion of the venting system
every 8 feet (2.4m) above the fireplace vent outlet.
Ceiling
Fireplace
Vertical
Rise
SV4.5 HT-2
Termination
Shown
Support Bracket Spacing
Every 5 ft (1.52 m)
SV4.5 HT-2
Termination
Shown
Support Brackets
Building
Support
Framing
Horizontal / Inclined Run
SV4.5E90
Elbow
See
Figure 19
on
Page 15
for vertical
vent section support.
u
When Using Secure Flex,
Use Firestop / Spacer SF4.5VF
u
Firestop / Spacer
SV4.5VF
SV4.5L6/12/24/36/48
Vent Sections
Exterior
Wall
f i r e - p a r t s . c o m
Содержание ADAGIO-EN
Страница 35: ...35 NOTES fire parts com...