Page 6

TABLE 6

Equivalent Area of Masonry Chimney Liners

Nominal Liner Size

(inches X inches)

Inside Liner
Dimensions

(inches)

Inside Diameter or

Equivalent Diameter

(inches)

Equivalent Area

(square inches)

4 X 8

2−1/2 X 6−1/2

4

12.2

5

19.6

6

28.3

7

38.3

8 X 8

6−3/4 X 6−3/4

7.4

42.7

8

50.3

8 X12

6−1/2 X 10−1/2

9

63.6

10

78.5

12 X12

9−3/4 X 9−3/4

10.4

83.3

11

95

12 X 16

9−1/2 X 13−1/2

11.8

107.5

12

113

14

153.9

16 X 16

13−1/4 X 13−1/4

14.5

162.9

15

176.7

16 X 20

13 X 17

16.2

206.1

18

254.4

20 X 20

16−1/2 X 16−3/4

18.2

260.2

20

314.1

Inspection of Tile−Lined Masonry Chimney

The chimney must be inspected and found to be in good
condition. Chimney construction must conform with the
National Fuel Gas Code NFPA 54/ANSI Z223.1, Standard
for Chimneys, Fireplaces, Vents and Solid−Fuel−Burning
Appliances ANSI/NFPA 211, and to any applicable state
or local codes.
The following conditions must be confirmed before
continuing with installation of the vent system:

  

Chimney must be lined with clay tile.

  

Chimney crown must be in good condition. Missing
mortar or brick must be replaced.

  

Tile liner and top seal must be in good condition. If
necessary, make repairs.

  

All debris (mortar, tile, fuel oil residue, etc.) must be
removed from chimney clean out.

  

Tile liner must be inspected to make sure that tiles
are properly aligned, that all sections are complete
and that there are no gaps. If necessary, make
repairs.

  

Exterior chimneys must serve at least one other
drafthood−equipped appliance. Verify before
continuing.

  

Chimney must be properly sized per these
instructions.

Installation

 1 − Turn off all gas supply and electrical power to unit.

WARNING

These instructions must be followed exactly. This
kit must be installed by a qualified service techni-
cian. Improper installation may result in personal
injury, loss of life, equipment damage, or damage to
the existing masonry chimney.

 2 − A  7/8"  diameter  hole is required to accommodate

the conduit for the wiring from the blocked vent
switch in the vent adapter to the pressure switch in
the furnace. A template is provided to ensure proper
location of the hole in the unit top cap.

The conduit hole must be positioned carefully to
avoid contact between the blocked vent switch
wiring and the combustion air inducer or hot
surfaces inside the furnace.

Содержание 92W76

Страница 1: ...ed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables and guidelines must be followed exactly to ensure p...

Страница 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Страница 3: ...mney and vent connector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using...

Страница 4: ...le Lined Masonry Chimney Serving a Single Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TILE LINED MASONRY CHIMNEY PERMANENTLY...

Страница 5: ...145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 163 187 209 233 255...

Страница 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Страница 7: ...to the furnace flue tran sition and the vent pipe at all times 6 The vent adapter assembly includes a blocked vent switch which must be wired into the furnace combustion air proving pressure switch a...

Страница 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Отзывы: