TABLE 4

Multiple Appliance for Interior and Exterior Masonry Chimney

Type B Double Wall Vent Connectors Serving a Single Furnace

with Masonry Chimney Vent Adapter Kit and One or More Drafthood−Equipped Appliances

Vent

Height

H

(ft)

Connector

Rise

R

(ft)

Type B Double Wall Connector Diameter − (inches)

6 in.

7 in.

8 in.

Appliance  Input Rate in Thousands of Btu per Hour

NAT
Max

NAT
Max

NAT
Max

6

1
2
3

101
124
143

141
173
203

201
232
270

8

1
2
3

105
127
145

148
179
206

210
240
276

10

1
2
3

108
129
148

153
184
209

216
247
281

15

1
2
3

114

134
153

164
192
215

229
260
292

20

1
2
3

119

138
157

173
199
222

239
270
301

30

1
2
3

127
145
163

187
209
233

255
287
317

35

1
2
3

131
149
167

194
216
240

265
297
332

TABLE 5

Multiple Appliance for Interior and Exterior Masonry Chimney

MASONRY CHIMNEY INTERNAL AREA

Height

H

(ft)

Minimum Internal Area of Chimney (Square Inches)

38

50

63

Combined Appliance Input Rating in Thousands of Btu Per Hour

NAT

+NAT

NAT

+NAT

NAT

+NAT

6

103

143

188

8

119

163

218

10

131

177

236

15

152

212

283

20

172

243

325

30

198

278

381

35

NR

291

401

NR − Not recommended for vent configuration.

Содержание 92W76

Страница 1: ...ed in masonry chimney vent applications in accordance with limitations set by NFPA 54 and the International Mechanical Code The included vent tables and guidelines must be followed exactly to ensure p...

Страница 2: ...10 F 12 C Pittsburgh 1 F 17 C Salt Lake City 3 F 16 C St Louis 2 F 17 C Requirements The room temperature surrounding the furnace and vent connectors must be at least 60 F 16 C The space surrounding t...

Страница 3: ...mney and vent connector per table 3 and figure 2 when a single appliance is being vented into an interior masonry chimney Size the chimney and vent connector per tables 4 and 5 and figure 3 when using...

Страница 4: ...le Lined Masonry Chimney Serving a Single Furnace Equipped with Vent Adapter Kit and One or More Drafthood Equipped Appliances Typical Application Shown FIGURE 3 TILE LINED MASONRY CHIMNEY PERMANENTLY...

Страница 5: ...145 148 179 206 210 240 276 10 1 2 3 108 129 148 153 184 209 216 247 281 15 1 2 3 114 134 153 164 192 215 229 260 292 20 1 2 3 119 138 157 173 199 222 239 270 301 30 1 2 3 127 145 163 187 209 233 255...

Страница 6: ...sing mortar or brick must be replaced Tile liner and top seal must be in good condition If necessary make repairs All debris mortar tile fuel oil residue etc must be removed from chimney clean out Til...

Страница 7: ...to the furnace flue tran sition and the vent pipe at all times 6 The vent adapter assembly includes a blocked vent switch which must be wired into the furnace combustion air proving pressure switch a...

Страница 8: ...al setting 11 Test the furnace for proper draft and spillage a Inspect the venting system for proper size and horizontal pitch Determine that there is no blockage restriction leakage corrosion or othe...

Отзывы: